| 2008-03-29 15:29:27 | REVIEW #: 1ST |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. ENERGY CALCULATIONS: THERE IS NO COORDINATION |
| | BETWEEN THE INPUT DATA REPORT (IDR), FLOOR PLANS AND |
| | SYSTEM SIZING SUMMARIES. |
| | EXAMPLE 1: BAY 1 CALLS FOR RTUS 1-4 IN THE IDR, BUT THE |
| | FLOOR PLAN SHOWS 7 RTU CURBS. |
| | EXAMPLE 2: IDR CALLS FOR 120,000 BTUH OF COOLING. EVEN |
| | IF MULTIPLIED BY 4 IT ONLY COMES OUT TO 40 TONS OF |
| | COOLING WHEN THE COOLING LOAD CALCULATIONS (SYSTEM |
| | SIZING SUMMARY) CALLS FOR 68.1 TONS. |
| | PLEASE COORDINATE PLANS, CALCULATIONS AND SYSTEM SIZING |
| | SUMMARY TO ACCURATELY REFLECT THE WORK BEING PROPOSED |
| | ON PLANS IN ACCORDANCE WITH FBCB 13-103.2. |
| | |
| | 2. ENERGY CALCULATIONS: WHEN SYSTEM SIZING SUMMARIES |
| | ARE PROVIDED, EACH SYSTEM SHALL BE SIZED AND LISTED |
| | SEPARATELY BY ZONE IN ACCORDANCE WITH FBCB |
| | 13-407.1.ABC.1. THESE ZONES AND INDIVIDUAL SYSTEMS |
| | SHALL BE LISTED ACCORDINGLY IN THE IDR. |
| | |
| | 3. PG M-1, M-2 AND M-3: PLEASE REMOVE ANY PLUMBING WORK |
| | FROM THE MECHANICAL PAGES AS THIS WORK WOULD NOT BE |
| | COVERED UNDER THE SCOPE OF A MECHANICAL PERMIT IN |
| | ACCORDANCE WITH FBCB 101.4.3. |
| | NOTE: REVISION LEGEND ON PLANS INDICATES THAT THERE |
| | HAVE BEEN TWO REVISIONS TO THESE SHEETS BASED ON ?CITY |
| | COMMENTS.? IT IS UNCLEAR AS TO HOW THIS IS POSSIBLE AS |
| | THIS IS THE FIRST TIME ANY PAGES HAVE BEEN SUBMITTED |
| | RELATED TO THIS PERMIT COVERING ANY SCOPE OF MECHANICAL |
| | WORK. |
| | |
| | 4. PG M-1: ACCORDING TO WALL DETAILS ON PG A-8.4, THERE |
| | IS A 12X8 TRANSFER GRILL PENETRATING A 2-HOUR RATED |
| | WALL BETWEEN BAY 2 AND THE EXISTING TENANT SPACE. SHOW |
| | HOW THIS OPENING IS TO BE PROTECTED IN ACCORDANCE WITH |
| | FBCM 607.5.2. ALSO, THERE APPEARS TO BE AN EXIT |
| | ENCLOSURE OR EXIT PASSAGEWAY FROM THE EXISTING TENANT |
| | SPACE AT THIS LOCATION. THIS 12X8 TRANSFER GRILL |
| | APPEARS TO BE FOR THE PURPOSE OF PROVIDING VENTILATION |
| | FOR THIS ENCLOSURE. PENETRATIONS INTO AN EXIT |
| | PASSAGEWAY ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| | PRESSURIZATION IN ACCORDANCE WITH FBCB 1020.5. IF |
| | VENTILATION IS REQUIRED OR DESIRED AT THIS LOCATION, IT |
| | SHALL BE PROVIDED IN ACCORDANCE WITH FBCM 401.4. |
| | |
| | 5. PG M-3: ROOF CURB DETAIL IS OF POOR QUALITY AND NOT |
| | LEGIBLE. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE IN ACCORDANCE |
| | WITH FBCB 106.1.1. ALSO, PROVIDE DETAIL WITH SUPPORTING |
| | WIND LOAD CALCULATIONS (FOR BUILDING PLAN REVIEW) |
| | SHOWING HOW ROOF CURBS ARE TO BE ATTACHED TO THE |
| | BUILDING STRUCTURE TO WITHSTAND ANTICIPATED WIND |
| | PRESSURES ON THE CURB AND RTU BEING SUPPORTED IN |
| | ACCORDANCE WITH FBCM 301.13. |
| | NOTE: WHEN OUTDOOR APPLIANCES (RTU?S) ARE SUBMITTED FOR |
| | REVIEW THEY WILL ALSO BE REQUIRED TO DEMONSTRATE THEIR |
| | DESIGN AND CONSTRUCTION IS CAPABLE OF WITHSTANDING |
| | ANTICIPATED WIND LOADS IN ACCORDANCE WITH THIS SECTION. |
| | THIS IS FOR INFORMATION ONLY AT THIS TIME. |
| | |
| | NOTE: PLEASE INDICATE ON PLANS THE CODES IN EFFECT AT |
| | THE TIME OF PERMIT APPLICATION: 2004 FLORIDA BUILDING |
| | CODE FAMILY WITH 2007 REVISIONS. |
| | |