| 2008-04-14 15:47:43 | *****DENIED***** |
| | |
| | |
| | 01.ON SHEET A5.1 SHOW/DISPLAY THE NUMERICAL ADDRESSES |
| | AND/OR UNIT SPACE NUMBERS ON THE APPROPIATE EXTERIOR |
| | ELEVATION WHICH FRONTS OKEECHOBEE BOULEVARD. |
| | |
| | 02.THE INSTALLATION OF SHUTTERS FOR HURRICANE AND/OR |
| | SECURITY PROTECTION SHALL NOT OBSTRUCT VISIBILTY OF |
| | ADDRESSES AND/OR UNIT NUMBERS. |
| | |
| | 03.FIRE DOORS AND FIRE WINDOWS SHALL COMPLY WITH NFPA |
| | 80. |
| | |
| | 04.ON SHEET E-1, PLEASE EXPLAIN REVISION #6 DATED |
| | 11/01/08 (OWNER CHANGES) AS THIS IS THE 1ST FIRE PLAN |
| | REVIEW. |
| | |
| | 05.ON SHEET FA-1, PLEASE EXPLAIN REVISION #6 DATED |
| | 11/01/08 (OWNER CHANGES) AS THIS IS THE 1ST FIRE PLAN |
| | REVIEW. |
| | |
| | 06.ON SHEET FS-1, PLEASE EXPLAIN REVISION #6 DATED |
| | 11/01/08 (OWNER CHANGES) AS THIS IS THE 1ST FIRE PLAN |
| | REVIEW. |
| | |
| | 07.WHEN IT IS NECESSARY TO TO SHUT DOWN THE FIRE |
| | ALARM AND/OR FIRE SPRINKLER SYSTEMS, THE FIRE |
| | DEPARTMENT SHALL BE NOTIFIED WHEN THE SYSTEM IS SHUT |
| | DOWN AND WHEN IT IS RETURNED TO SERVICE. |
| | |
| | 08.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE |
| | FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM REMODEL OR |
| | INSTALLATION. |
| | |
| | 09.KNOX LOCKING CAPS SHALL BE REQUIRED FOR FIRE |
| | DEPARTMENT CONNECTIONS (FDC'S).FOR APPLICATIONS, |
| | CONTACT WEST PALM BEACH FIRE PREVENTION BUREAU AT |
| | 561-804-4724. |
| | |
| | 10. PLEASE EXPLAIN THE ATTACHMENT OF PLAN SHEETS |
| | ADDRESSED 2015 OKEECHOBEE BOULEVARD TO THE SUBMITTED |
| | 2029 OKEECHOBEE PLAN SETS. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE APPROPIATE PLAN EACH |
| | COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |