Plan Review Notes
Plan Review Notes For Permit 07070444
Permit Number 07070444
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-04-14 15:47:43*****DENIED*****
  
  
 01.ON SHEET A5.1 SHOW/DISPLAY THE NUMERICAL ADDRESSES
 AND/OR UNIT SPACE NUMBERS ON THE APPROPIATE EXTERIOR
 ELEVATION WHICH FRONTS OKEECHOBEE BOULEVARD.
  
 02.THE INSTALLATION OF SHUTTERS FOR HURRICANE AND/OR
 SECURITY PROTECTION SHALL NOT OBSTRUCT VISIBILTY OF
 ADDRESSES AND/OR UNIT NUMBERS.
  
 03.FIRE DOORS AND FIRE WINDOWS SHALL COMPLY WITH NFPA
 80.
  
 04.ON SHEET E-1, PLEASE EXPLAIN REVISION #6 DATED
 11/01/08 (OWNER CHANGES) AS THIS IS THE 1ST FIRE PLAN
 REVIEW.
  
 05.ON SHEET FA-1, PLEASE EXPLAIN REVISION #6 DATED
 11/01/08 (OWNER CHANGES) AS THIS IS THE 1ST FIRE PLAN
 REVIEW.
  
 06.ON SHEET FS-1, PLEASE EXPLAIN REVISION #6 DATED
 11/01/08 (OWNER CHANGES) AS THIS IS THE 1ST FIRE PLAN
 REVIEW.
  
 07.WHEN IT IS NECESSARY TO TO SHUT DOWN THE FIRE
 ALARM AND/OR FIRE SPRINKLER SYSTEMS, THE FIRE
 DEPARTMENT SHALL BE NOTIFIED WHEN THE SYSTEM IS SHUT
 DOWN AND WHEN IT IS RETURNED TO SERVICE.
  
 08.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 FIRE ALARM AND/OR FIRE SPRINKLER SYSTEM REMODEL OR
 INSTALLATION.
  
 09.KNOX LOCKING CAPS SHALL BE REQUIRED FOR FIRE
 DEPARTMENT CONNECTIONS (FDC'S).FOR APPLICATIONS,
 CONTACT WEST PALM BEACH FIRE PREVENTION BUREAU AT
 561-804-4724.
  
 10. PLEASE EXPLAIN THE ATTACHMENT OF PLAN SHEETS
 ADDRESSED 2015 OKEECHOBEE BOULEVARD TO THE SUBMITTED
 2029 OKEECHOBEE PLAN SETS.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN EACH
 COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722