Plan Review Notes
Plan Review Notes For Permit 07070438
Permit Number 07070438
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-01 07:25:28DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SUBMIT ENERGY CALCULATIONS FOR THE NEW ADDITION AS
 REQUIRED BY FBC CHAPTER 13.
  
 4) SHOW COMPLIANCE WITH R 322.1.1, WHICH REQUIRES AT
 LEAST ONE BATHROOM WITH A DOOR THAT HAS A 29" CLEAR
 OPENING, MEASURED FROM THE FACE OF THE DOOR TO THE
 OPPOSITE STOP WITH DOOR OPEN 90 DEGREES.
  
 5) THE ROOF ZONES COMPONENT AND CLADDING FIGURE ON
 SHEET 2 IS INCORRECT. SEE FIGURE R301.2(8).
  
 6) SPECIFY THE OVERHANG FOR THE FLAT ROOF AT HIS
 CLOSET. SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST
 DECAY AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 7) PROVIDE A WALL SECTION FOR THE SINGLE ASSEMBLY FLAT
 ROOF AT HIS CLOSET. SPECIFY THE ATTIC VENTING AND
 INSULATION. SEE R806.
  
 8) SPECIFY THE STEEL REINFORCING FOR THE 16" X 16"
 FOOTING AT THE INTERIOR LOAD BEARING WALL.
  
 9) SPECIFY THE TRUSS AND RAFTER CONNECTORS AT THE
 INTERIOR BEARING WALL.
  
 10) INDICATE HOW ATTIC VENTILATION AS REQUIRED BY R806
 WILL BE PROVIDED AT THE PORCH AREA. SEE PORCH SECTION 2
 ON 3.
  
 11) THE PORCH SECTIONS ON SHEET 3 HAVE AN OPTION OF
 USING 5/8" T&G PLYWOOD WITH GROOVES 6" OC. THE PLYWOOD
 USED FOR ROOF SHEATHING IS REQUIRED TO COMPLY WITH
 R803.2.1 AND TABLE R503.2.1.1(1) FOR SPANS AND LOADS.
  
 12) SUBMIT PRODUCT APPROVALS FOR WINDOWS, DOORS, STORM
 PANELS, ROOFING MATERIAL FOR THE FLAT AND SLOPED
 ROOFS.
  
 13) SPECIFY WHAT METHOD OF ATTACHMENT WILL BE USED TO
 INSTALL THE ROOF TILES. CIRCLE THE ATTACHMENT METHOD
 THAT WILL BE USED FROM THE ONES LISTED IN THE PRODUCT
 APPROVAL. SPECIFY WHICH ONE OF THE APPROVED ASSEMBLIES
 AND FASTENING OPTION THAT WILL BE USED TO INSTALL THE
 ROOFING MATERIAL FOR THE FLAT ROOF SECTION. IF ENHANCED
 FASTENING IS REQUIRED IN ORDER TO INCREASE THE DESIGN
 PRESSURES FOR THE PERIMETER AND CORNER AREAS, THEN
 SUBMIT RAS 117 CALCULATIONS (IF THIS IS ALLOWED BY
 LIMITATION #7 OF THE NOA).
  
 14) IN ADDITION TO THE STORM PANEL PRODUCT APPROVAL (IF
 NOT USING IMPACT RATED GLASS), SUBMIT A KEY PLAN AND
 INSTALLATION SCHEDULE. SPECIFY THE MOUNT TYPE, ANCHOR
 TYPE AND SPACING, EDGE DISTANCE, ETC. THAT WILL BE USED
 TO INSTALL THE STORM PANELS.
  
 15)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE.
  
 16)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 17) THE WALL SECTION ON SHEET 2 SPECIFIES SHINGLES AND
 THE PORCH SECTION ON SHEET 3 SPECIFIES TILES PLEASE
 CORRECT.
  
 18) THE VALUE OF THE WORK HAS BEEN INCREASED TO $
 73,769.00 BASED ON ICC VALUATION DATA. ADDITIONAL
 PERMIT FEES AND RADON FEES ARE DUE.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  
  