| Plan Review Notes For Permit 07070436 |
| Permit Number |
07070436 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-13 07:06:59 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. | | | PLEASE INDICATE LOCATION OF DRINKING FOUNTAIN AND SHOW | | | ON THE SANITARY RISER DIAGRAM. | | | | | | 2. SHT S-1 SANITARY RISER DIAGRAM DOES NOT MEET CODE | | | REQUIREMENTS. THE TRAPS FOR THE LAVS ARE INDICATED | | | UNDERGROUND AS SHOWN ON THE RISER DIAGRAM. SEE THE RED | | | LINED EXAMPLE OF A RISER DIAGRAM THAT MEETS CODE AND | | | SHOWS THE REQUIRED DRINKING FOUNTAIN. | | | | | | 3. THE TOILET ROOMS SHALL BE ACCESSIBLE AND SHOULD BE | | | TAKEN INTO CONSIDERATION AS THE SANITARY PIPING WILL BE | | | IN THE SLAB. THE HOLDER OF THE FOUNDATION PERMIT WILL | | | BE PROCEEDING AT THEIR OWN RISK AND WITHOUT ASSURANCE | | | THAT A PERMIT FOR THE REMAINDER OF THE WORK WILL BE | | | GRANTED AND THAT CORRECTIONS WILL NOT BE REQUIRED IN | | | ORDER TO MEET PROVISIONS OF THE TECHNICAL OR ACCESSIBLE | | | CODE. SECTION 105.13. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|