Plan Review Notes
Plan Review Notes For Permit 07070436
Permit Number 07070436
Review Stop P
Sequence Number 1
Notes
Date Text
2007-10-13 07:06:59DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED.
 PLEASE INDICATE LOCATION OF DRINKING FOUNTAIN AND SHOW
 ON THE SANITARY RISER DIAGRAM.
  
 2. SHT S-1 SANITARY RISER DIAGRAM DOES NOT MEET CODE
 REQUIREMENTS. THE TRAPS FOR THE LAVS ARE INDICATED
 UNDERGROUND AS SHOWN ON THE RISER DIAGRAM. SEE THE RED
 LINED EXAMPLE OF A RISER DIAGRAM THAT MEETS CODE AND
 SHOWS THE REQUIRED DRINKING FOUNTAIN.
  
 3. THE TOILET ROOMS SHALL BE ACCESSIBLE AND SHOULD BE
 TAKEN INTO CONSIDERATION AS THE SANITARY PIPING WILL BE
 IN THE SLAB. THE HOLDER OF THE FOUNDATION PERMIT WILL
 BE PROCEEDING AT THEIR OWN RISK AND WITHOUT ASSURANCE
 THAT A PERMIT FOR THE REMAINDER OF THE WORK WILL BE
 GRANTED AND THAT CORRECTIONS WILL NOT BE REQUIRED IN
 ORDER TO MEET PROVISIONS OF THE TECHNICAL OR ACCESSIBLE
 CODE. SECTION 105.13.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved