| 2007-11-19 14:55:00 | ** DENIED 2ND REVIEW ** |
| | |
| | ** AS STATED ON PREVIOUS REVIEW, PLEASE SEE THERE ARE |
| | SOME COMMENTS FROM PREVIOUS REVIEW AND SOME NEW |
| | COMMENTS BASED ON INFORMATION NOW BEING SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SHOW ALL LOCATIONS OF SERVICE EQUIPMENT |
| | ON PLANS FOR LOCATIONS. |
| | CAN NOT VERIFY ITEMS AT THIS TIME FOR TAPPED |
| | CONDUCTORS, DISCONNECTING MEANS, CLEARANCES ETC. |
| | 240.21, 110.26, 240.24, 225.31ETC |
| | AS THE LOCATION OF TRANSFORMER AND MAIN BREAKER PANEL |
| | AT THIS DETACHED STRUCTURE FROM SERVICE LOCATION IS NOT |
| | SHOWN WE ARE UNABLE TO CONFIRM LOCATIONS. |
| | |
| | 2) NOTE: PLEASE SEE THE PREVIOUS NOTES FOR DISCONNECTS |
| | REQUIRED FOR A/C SYSTEM AHU AND CU> |
| | PLEASE SEE THERE ARE BOXES SHOWN ON PLANS WITH CIRCUIT |
| | NUMBERS BUT NO DISCONNECTS PER 440.11. |
| | |
| | 3) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM |
| | AT THIS DETACHED STRUCTURE PER 250.50, 250.32 |
| | |
| | 4) NOTE: PLEASE CLARIFY CONTINUOUS LOADS AND WHERE |
| | THESE ARE SHOWN AT 125%. |
| | NO LOAD CALCULATIONS ACTUALLY SHOWN. |
| | 215.3, 230.42 ETC. |
| | 220.12, 220.14, 220.42, 220.44 ETC. |
| | |
| | 5) NOTE: PLEASE SEE RISER IS STILL INDICATING A NEUTRAL |
| | ON THE LINE SIDE OF THE TRANSFORMER. PLEASE EXPLAIN AS |
| | THIS TRANSFORMER IS A SEPARATELY DERIVED SYSTEM AND |
| | CREATES ITS OWN NEUTRAL. |
| | 250.6, 250.24 ETC. |
| | |
| | 6) NOTE: PLEASE SEE THE METHOD *A* CALCULATIONS NOW |
| | SUBMITTED ARE SIGNED AND SEALED BY AN ARCHITECT WHICH |
| | IS NOT THE ARCHITECT OR ENGINEER OF RECORD. |
| | PLEASE SEE THE CERTIFICATION SHEET IS REQUIRED TO BE |
| | COMPLETED WITH ALL INFORMATION FOR RESPONSIBLE |
| | DESIGNERS. |
| | PLEASE ALSO SEE MISSING OWNER AGENT. |
| | FBC 13-101, FS 471.025 |
| | |
| | 7) NOTE: PLEASE SEE THE LIGHTING AS SHOWN ON PLANS DOES |
| | NOT CORRELATE WITH THE LIGHTING ON THE INPUT DATA |
| | REPORT. |
| | PLEASE CORRELATE AND SUBMIT. |
| | FBC 13-415.1.A, 13-415.2 |
| | |
| | 8) NOTE: PLEASE SEE 13-413.1.ABC.2.2 AND PLACE NOTE ON |
| | PLANS ACCORDINGLY. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |