Plan Review Notes
Plan Review Notes For Permit 07070433
Permit Number 07070433
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-19 14:55:00** DENIED 2ND REVIEW **
  
 ** AS STATED ON PREVIOUS REVIEW, PLEASE SEE THERE ARE
 SOME COMMENTS FROM PREVIOUS REVIEW AND SOME NEW
 COMMENTS BASED ON INFORMATION NOW BEING SUBMITTED.
  
 1) NOTE: PLEASE SHOW ALL LOCATIONS OF SERVICE EQUIPMENT
 ON PLANS FOR LOCATIONS.
 CAN NOT VERIFY ITEMS AT THIS TIME FOR TAPPED
 CONDUCTORS, DISCONNECTING MEANS, CLEARANCES ETC.
 240.21, 110.26, 240.24, 225.31ETC
 AS THE LOCATION OF TRANSFORMER AND MAIN BREAKER PANEL
 AT THIS DETACHED STRUCTURE FROM SERVICE LOCATION IS NOT
 SHOWN WE ARE UNABLE TO CONFIRM LOCATIONS.
  
 2) NOTE: PLEASE SEE THE PREVIOUS NOTES FOR DISCONNECTS
 REQUIRED FOR A/C SYSTEM AHU AND CU>
 PLEASE SEE THERE ARE BOXES SHOWN ON PLANS WITH CIRCUIT
 NUMBERS BUT NO DISCONNECTS PER 440.11.
  
 3) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM
 AT THIS DETACHED STRUCTURE PER 250.50, 250.32
  
 4) NOTE: PLEASE CLARIFY CONTINUOUS LOADS AND WHERE
 THESE ARE SHOWN AT 125%.
 NO LOAD CALCULATIONS ACTUALLY SHOWN.
 215.3, 230.42 ETC.
 220.12, 220.14, 220.42, 220.44 ETC.
  
 5) NOTE: PLEASE SEE RISER IS STILL INDICATING A NEUTRAL
 ON THE LINE SIDE OF THE TRANSFORMER. PLEASE EXPLAIN AS
 THIS TRANSFORMER IS A SEPARATELY DERIVED SYSTEM AND
 CREATES ITS OWN NEUTRAL.
 250.6, 250.24 ETC.
  
 6) NOTE: PLEASE SEE THE METHOD *A* CALCULATIONS NOW
 SUBMITTED ARE SIGNED AND SEALED BY AN ARCHITECT WHICH
 IS NOT THE ARCHITECT OR ENGINEER OF RECORD.
 PLEASE SEE THE CERTIFICATION SHEET IS REQUIRED TO BE
 COMPLETED WITH ALL INFORMATION FOR RESPONSIBLE
 DESIGNERS.
 PLEASE ALSO SEE MISSING OWNER AGENT.
 FBC 13-101, FS 471.025
  
 7) NOTE: PLEASE SEE THE LIGHTING AS SHOWN ON PLANS DOES
 NOT CORRELATE WITH THE LIGHTING ON THE INPUT DATA
 REPORT.
 PLEASE CORRELATE AND SUBMIT.
 FBC 13-415.1.A, 13-415.2
  
 8) NOTE: PLEASE SEE 13-413.1.ABC.2.2 AND PLACE NOTE ON
 PLANS ACCORDINGLY.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II