Plan Review Notes
Plan Review Notes For Permit 07070433
Permit Number 07070433
Review Stop M
Sequence Number 1
Notes
Date Text
2007-08-06 08:43:52---------------DENIED-----------------
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PROVIDE ENERGY CALCULATIONS PER FBC 13-101.1.1 AND
 FBC 106.3.5.1.4
  
 2. PROVIDE MEANS OF VENTILATION AND PROVIDE
 CALCULATIONS BASED ON FBC,M SEC 402 OR 403 PER FBC
 106.3.5.1.4
  
 3. ELECTRICAL PLAN SHOWS CENTRAL A/C SYSTEM. SHOW ALL
 COMPONENTS, INCLUDING EQUIPMENT SCHEDULE, AND
 DEMONSTRATE COMPLIANCE WITH FBC,M CHAPTERS 3 AND 6 AS
 WELL AS FBC CH.13 PER FBC 106.3.5.1.4
  
 4. MECHANICAL EXHAUST IS REQUIRED FOR TOILET ROOMS PER
 FBC,M TABLE 403.3.
  
 NOTE: A COMPLETE REVIEW IS NOT POSIIBLE AT THIS TIME
 DUE TO MISSING INFORMATION. ADDITIONAL COMMENTS ARE
 POSSIBLE ON THE NEXT REVIEW. PROVIDE ALL INFORMATION
 REQUIRED BY FBC 106.3.5.1.4.
  