| Notes |
| Date |
Text |
| 2007-08-06 08:43:52 | ---------------DENIED----------------- | | | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 AMENDMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PROVIDE ENERGY CALCULATIONS PER FBC 13-101.1.1 AND | | | FBC 106.3.5.1.4 | | | | | | 2. PROVIDE MEANS OF VENTILATION AND PROVIDE | | | CALCULATIONS BASED ON FBC,M SEC 402 OR 403 PER FBC | | | 106.3.5.1.4 | | | | | | 3. ELECTRICAL PLAN SHOWS CENTRAL A/C SYSTEM. SHOW ALL | | | COMPONENTS, INCLUDING EQUIPMENT SCHEDULE, AND | | | DEMONSTRATE COMPLIANCE WITH FBC,M CHAPTERS 3 AND 6 AS | | | WELL AS FBC CH.13 PER FBC 106.3.5.1.4 | | | | | | 4. MECHANICAL EXHAUST IS REQUIRED FOR TOILET ROOMS PER | | | FBC,M TABLE 403.3. | | | | | | NOTE: A COMPLETE REVIEW IS NOT POSIIBLE AT THIS TIME | | | DUE TO MISSING INFORMATION. ADDITIONAL COMMENTS ARE | | | POSSIBLE ON THE NEXT REVIEW. PROVIDE ALL INFORMATION | | | REQUIRED BY FBC 106.3.5.1.4. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J REGUEIRO | | | 561.805.6719 | | | [email protected] |
|