| Date |
Text |
| 2007-09-14 17:47:50 | *****DENIED***** |
| | |
| | |
| | |
| | 01.THE NUMERICAL ADDRESS OF THE PROJECT SITE SHALL BE |
| | IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. |
| | |
| | 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 03.FIRE DEPARTMENT ACCESS ROAD TO THIS STRUCTURE |
| | SHALLBE CABLE OF SUPPORTING THE IMPOSED LOADS OF FIRE |
| | APPARATUS AND SHALL BE PROVIDED WITH A SURFACE SUITABLE |
| | FOR ALL-WEATHER DRIVING CAPABILITIES. |
| | |
| | 04.FIRE DEPARTMENT ACCESS ROADS SHALL HAVE AN |
| | UNOBSTRUCTED WIDTH OF NOT LESS THAN 20 FEET AND AN |
| | UNOBSTRUCTED VERTICAL CLEARANCE OF NOT THAN LESS THAN |
| | 13 FEET 6 INCHES. |
| | |
| | 05.THE PROJECTED SCOPE OF WORK SHALL NOT INTERFERE OR |
| | HINDER EMERGENCY RESPONSE ACCESS TO THE PROPERTY OR |
| | VICINITY THEREOF (INCLUDING FIRE LANES). |
| | |
| | 06.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 07.INDICATE THE OCCUPANCY TYPE.THE APPLICATION HAS |
| | THE CONSTRUCTION OF AN UTILITY BUILDING,WHEREAS PLAN |
| | SHEET A-1 SHOWS THE PROPOSED BUIDLING AS A TEACHING |
| | BUILDING. |
| | |
| | 08.PROVIDE OCCUPANT LOAD AS IN NUMBER OF PERSONS FOR |
| | WHOM MEANS OF EGRESS ARE REQUIRED BASED UPON THE |
| | CHARACTERISTIC OF THE USE OF THE TENANT SPACE. |
| | |
| | 09.PROVIDE A LIFE SAFETY PLAN SHEET INDICATING TRAVEL |
| | DISTANCES TO EXITS, EXIT LIGHTS, EMERGENCY LIGHTING, |
| | AND THE LOCATION OF THE 2A:10BC RATED FIRE |
| | EXTINGUISHER(S). |
| | |
| | 10.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR |
| | THE EXITS, AISLE CORRIDORS, AND ALL OTHER SPACES IN |
| | TERRMS OF CLASS A, CLASS B, OR CLASS C.SPECIFY |
| | INTERIOR FLOOR FINISH IN TERMS OF CLASS I OR CLASS II. |
| | |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDIACTING WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |