| 2007-08-06 15:10:46 | ** DENIED ** |
| | |
| | |
| | 1) NOTE: PLEASE INDICATE THE RELEVANT CODES ON PLANS AS |
| | REQUIRED. |
| | PLEASE SEE THE FOLLOWING WHICH WERE ADOPTED AS OF |
| | DECEMBER 8TH, 2006 SHALL BE ON PLANS. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 (NEC). |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE THE TITLE BLOCK INDICATE THE |
| | COMMERCIAL WORK BEING DONE BY A DRAFTING FIRM? PLEASE |
| | SEE FLORIDA STATUTES 471.003 AS THE SCOPE OF WORK FOR |
| | ELECTRICAL AS SHOWN IS REQUIRED TO BE DONE BY AN |
| | ENGINEER. PLEASE ALSO SEE THE ABOVE 471.025 AS PLANS |
| | ARE REQUIRED TO BE SIGNED, DATED AND SEALED BY A |
| | DESIGNER WITH KNOWLEDGE OF ELECTRICAL SYSTEMS AS |
| | DESIGNED. |
| | |
| | 3) NOTE: PLEASE BE SURE THE ADDRESS OF THE BUILDING IS |
| | STATED IN THE TITLE BLOCKS AS REQUIRED. PLEASE KNOW AS |
| | THE SITE AND LOCATION STILL NEEDS TO BE REVIEWED BY THE |
| | ADDRESSING REVIEWER THE BUILDING/STRUCTURE MAY INDEED |
| | BE GIVEN A NEW ADDRESS WHICH WOULD NEED TO BE ON |
| | PLANS. |
| | FAC 61G15-23.002, 61G1-16.004 |
| | |
| | 4) NOTE: PLEASE SEE MISSING DISCONNECT FOR CU AND AHU. |
| | THERE ARE BOXES ON PLANS HOWEVER UNCLEAR IF THESE ARE |
| | THE REQUIRED DISCONNECTS. |
| | 440.11 |
| | |
| | 5) NOTE: PLEASE SEE THE LOCATION OF THE NEW DISCONNECT |
| | WHICH IS TAPPED FROM THE EXISTING MAIN IS NOT BEING |
| | SHOWN TO VERIFY THE TAPPED CONDUCTORS PER 240.21, |
| | 240.4, 310.16. |
| | |
| | 6) NOTE: PLEASE VERIFY THE CONDUCTORS ON THE RISER WITH |
| | THAT IF THE CONDUCTORS SHOWN ON THE PARTIAL LOAD |
| | CALCULATIONS. |
| | PLEASE SEE DIFFERENCES ON THE GROUNDING ELECTRODE |
| | CONDUCTOR. |
| | PLEASE SEE THE 4/0 ARE BEING SHOWN TO A 60AMP |
| | DISCONNECT. |
| | PLEASE ALSO VERIFY THE CONDUCTORS FROM THE NEW |
| | DISCONNECT TO THE NEW BUILDING AS THESE ARE SHOWN AS |
| | #3. |
| | THE COMMENT IS FOR THE SIZE OF THE CONDUCTOR WILL NOT |
| | FIT UNDER THE LUGS ON THE SIZE OF THE EQUIPMENT AS |
| | SHOWN. |
| | ** PLEASE SEE OTHER COMMENTS AS THE RISER WILL CHANGE |
| | AS SUBMITTED. |
| | FBC 106.3.5.1.2, 106.1.2 FOR COORDINATION. |
| | |
| | 7) NOTE: PLEASE SEE MISSING THE DISCONNECTING MEANS AS |
| | THE DETACHED STRUCTURE AS REQUIRED PER 225.31. ( NONE |
| | SHOWN ON THE LINE SIDE OF THE TRANSFORMER.) |
| | |
| | 8) NOTE: PLEASE SEE THE FEEDERS ARE SHOWN TO THE LINE |
| | SIDE OF THE TRANSFORMER WHICH CONTAINS A NEUTRAL? |
| | PLEASE VERIFY AS THIS IS A SEPARATELY DERIVED SYSTEM. |
| | 250.20, 250.30, 250.66 ETC |
| | |
| | 9) NOTE: PLEASE COMPLETE THE GROUNDING ELECTRODE SYSTEM |
| | AND GROUNDING AT THE DETACHED BUILDING PER 250.32 AND |
| | ABOVE COMMENT #8. |
| | |
| | 10) NOTE: PLEASE SHOW THE LOCATION OF ALL SERVICE |
| | EQUIPMENT. PLANS DO NOT INDICATE ANY TRANSFORMER SO THE |
| | LOCATION CAN NOT BE DETERMINED AT THIS TIME. |
| | 240.24, 110.26, 450.9, 450.13 ETC. |
| | |
| | 11) NOTE: PLEASE SUBMIT LOAD CALCULATIONS FOR THE NEW |
| | PANEL *A* AND LOAD FOR BOTH EXISTING AND NEW. ALL |
| | CONTINUOUS LOADS NEED TO BE SHOWN AT 125%. |
| | 215.3, 230.42 ETC. |
| | PLEASE SEE THE LOADS AS SHOWN ON PLANS WITHOUT THE NEW |
| | LOADS ADDED SEEM TO BE VERY CLOSE TO EXCEEDING THE |
| | RATING OF THE SERVICE AND EQUIPMENT. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 12) NOTE: PLEASE PROVIDE AIC RATINGS FOR ALL SERVICE |
| | EQUIPMENT PER 110.9. |
| | FBC 106.1.2 |
| | |
| | 13) NOTE: PLEASE SUBMIT THE VOLTAGE DROP PER |
| | 13-413.1.ABC.1 FOR FEEDERS. PLANS STATE THIS IS |
| | REQUIRED HOWEVER CONTAINS NO INFORMATION ON THIS. |
| | MAY NOT QUOTE CODE REQUIREMENTS IN LIEU OF DETAIL. |
| | |
| | 14) NOTE: PLEASE SEE MISSING ENERGY |
| | CALCULATIONS/PERFORMANCE CALCULATIONS PER 13-101.1.1 |
| | AND TO BE SIGNED, DATED AND SEALED PER 13-101.1.1.1. |
| | PLEASE SEE 13-415.1.AB.1.1, 13-415.1.C, 13-415.2 ETC. |
| | PLEASE BE SURE ALL DOCUMENTS ARE SIGNED, DATED AND |
| | SEALED AS REQUIRED PER 13-103.1.1.1 AND OWNER/AGENT IS |
| | SIGNED. |
| | |
| | 15) NOTE: PLEASE PLACE CONDUCTOR SIZES ON PANEL |
| | SCHEDULE AND CORRELATE WITH THE OVER CURRENT PROTECTION |
| | AS LISTED ON BRANCH CIRCUITS. |
| | 240.4, 310.16, 408.4. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 16) NOTE: PLEASE SEE MISSING FOOTER STEEL AND POSSIBLE |
| | COLD WATER PIPE(WHERE METALLIC). PLEASE SEE THE PERMIT |
| | APPLICATION MENTIONS THE SLAB/FOUNDATION IS UNDER A |
| | SEPARATE PERMIT. THE FOOTER STEEL IS REQUIRED AND |
| | ATTACHMENT MUST BE MADE. |
| | 250.50. |
| | PLEASE KNOW THAT IF THE SLAB/FOUNDATION PERMIT IS |
| | GIVEN, THE ELECTRICAL PERMIT MAY BE DONE SEPARATELY TO |
| | ALLEVIATE ANY *CHIPPING* UP OF A POURED FOOTER WITH OUT |
| | THIS BEING DONE. |
| | |
| | 17) NOTE: ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT |
| | YET SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| | AT THIS TIME. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |