| 2007-08-08 10:14:41 | BUILDING PLAN REVIEW |
| | PERMIT: 007070425 |
| | ADD: 201 NARCISSUS AVE |
| | CONT: ROYAL DIAMONS HOMES |
| | TEL: (561)582-3818 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) 2004 FBC EXISTING |
| | 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 3)ALL PLANS SUBMITTED AFTER OCTOBER, 1, |
| | 2004 SHALL BE DESIGNED TO THE 2004 |
| | FLORIDA BUILDING CODE/WITH 2006 REVISIONS. |
| | |
| | 4)PROVIDE THE STRUCTURAL FLOOR LOAD CALCULATIONS FOR |
| | THE FISH TANK AS INDICATEDON SHEET A-1.2 NOTE #7. |
| | |
| | 5)WHEN THE EXISTING FLOOR IS REMOVED, WHAT TYPE OF |
| | MATERIAL WILL BE USED TO REPLACE IT?PROVIDE |
| | INFORMATIONON THE SOUND INSULATION. FBC 1207.3 THE |
| | FLOOR/CEILINGASSEMBLIES BETWEEN DWELLING UNITS SHALL |
| | HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF NOT |
| | LESS THAN 50. SEE FBC 1207 FOR MORE INFORMATION. |
| | |
| | 6)PROVIDE A FINISH SCHEDULE INDICATING THE FINISHES |
| | ON THE FLOOR/CEILINGS AND WALLS. SEE FBC 803/804 AND |
| | 805. |
| | |