| Plan Review Notes For Permit 07070387 |
| Permit Number |
07070387 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2007-11-16 12:13:04 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | MECHANICAL REVISION | | | *** DENIED *** | | | 1) PLANS ON FILE PAGE A-7.2 SHOWS THE WALLS TO THE | | | TEL/SERVER ROOM ARE ONE HOUR FIRE RATED. THE TWO 14" | | | FLEX DUCTS MAY NOT PENETRATE A RATED WALL, SHOW | | | COMPLIANCE WITH 2004 FBC/M 607.5. ALSO FOR THE 8' | | | EXHAUST DUCT (ON PAGE M-2.1). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|