| Notes |
| Date |
Text |
| 2008-01-04 08:56:04 | REDLINED GROUND ATTACHMENT FOR TRANSFORMER AS THIS ONLY | | | SHOWS COLD WATER. | | | PLEASE SEE 250.50, 250.58 AS THIS IS REQUIRED TO OTHER | | | THAN COLD WATER. | | | FREQENTLY THE COLD WATER LINE IN A HIGH RISE HAS CPVC | | | OR OTHER DEVICE INSTALLED IN LINE WHICH AFFECTS AN | | | EFFECTIVE PATH AS REQUIRED. | | | MUST HIT A GROUND ELECTRODE RISER OR STRUCTURAL STEEL. |
|