| 2007-09-04 12:26:43 | 2007-09-04 12:26:43 |
| | |
| | ** DENIED2ND REVIEW** |
| | |
| | |
| | ** PLEASE SEE THERE ARE COMMENTS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. |
| | ** PLEASE SEE THERE ARE ALSO NEW COMMENTS AS THERE WERE |
| | SEVERAL CHANGES MADE TO PANEL SCHEDULES/RISER WHICH |
| | HAVE CREATED NEW COMMENTS. AS THESE ITEMS WERE NOT ON |
| | PREVIOUS PLANS THIS WAY, THESE NEW COMMENTS COULD NOT |
| | HAVE BEEN MADE ON THE PREVIOUS REVIEW. |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS NOTE #1 WITH RESPECT TO |
| | CODES REQUIRED. PLEASE SEE ARCHITECTURAL COVER SHEET |
| | WHICH NOTES A 2005 NFPA-72. PLEASE KNOW THIS CODE |
| | SHOULD BE THE 2002 NFPA-72. |
| | PLEASE ADJUST. |
| | |
| | ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH |
| | MAY REQUIRE CERTAIN CODES. |
| | |
| | 2) NOTE: PLEASE SEE NOTE #6 FROM PREVIOUS REVIEW WITH |
| | RESPECT TO INFORMATION BEING NEEDED FOR MAXIMUM |
| | LIGHTING POWER DENSITIES. PLEASE SEE 13-415.2, AND |
| | 13-415.2.ABC.1.2 WITH RESPECT TO TRACK LIGHTING. THE |
| | RESPONSE FROM THE DESIGNER MENTIONS LOADS FOR TRACK |
| | LIGHTING BASED ON THE NEC MINIMUM LOADS FOR BRANCH |
| | CIRCUITS AND SERVICE FEEDER LOADS. THIS SECTION OF THE |
| | FBC AND CHAPTER 13 HAS TO DO WITH THE MAXIMUM ALLOWED |
| | LIGHTING LEVELS AND WATTS PER SQ FT BASED ON USE OF THE |
| | SPACE ETC. |
| | PLEASE SEE THERE IS A MAXIMUM TIME OF 30 MINUTES FOR |
| | OCCUPANCY TYPE DEVICES PER THE FBC AND SOME OC TYPE |
| | DEVICES AS NOTED ON LEGEND MENTIONS 2HRS. |
| | PLEASE SEE THAT THE COORDINATION OF LIGHTING, FIXTURES |
| | AND LEVELS CAN NOT FULLY BE DONE AT THIS TIME. PLEASE |
| | SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #8 WITH |
| | RESPECT TO MINIMUM LEVELS FOR ADA COMPLIANCE. THE |
| | RESPONSE LETTER MENTIONS LEVELS AT 70DB, HOWEVER NO |
| | INFORMATION OR LEVELS FOR CANDELA LEVELS COULD BE |
| | LOCATED. |
| | PLEASE SEE THE NOTE BELOW FROM PREVIOUS REVIEW*PLEASE |
| | SEE FBC 2004 11-4.28.1, .2 AND .3(4) AND STATE THE |
| | MINIMUM HORN, STROBE LEVELS ON PLANS FOR ADA REQUIRED |
| | AREAS. DEVICES ARE BEING SHOWN ON PLANS/LEGEND. PLEASE |
| | CORRELATE WITH PLANS, AND FA SHEETS SUBMITTED. |
| | ** PLEASE KNOW THAT THE FIRE ALARM WILL BE UNDER A |
| | SEPARATE PERMIT HOWEVER THE BASE LIFE SAFETY SYSTEM IS |
| | REQUIRED ON BASE PLANS AS SHOWN. DO NOT REMOVE FROM |
| | SETS. |
| | FBC 106.3.5.1.2 |
| | |
| | 4) NOTE:PLEASE SEE PREVIOUS NOTE #10. RESPONSE |
| | MENTIONS LOAD WAS ADJUSTED HOWEVER PLANS SHOW THE SAME |
| | INFORMATION AS ON PREVIOUS CALCULATIONS. PLEASE SEE THE |
| | NEC HANDBOOK AS WATER HEATERS ARE NOW CONSIDERED |
| | *CONTINUOUS LOADS* WHICH REQUIRES THE 125% FOR LOAD. |
| | THIS WAS A CHANGE FROM THE PREVIOUS CODE WHICH ONLY |
| | REQUIRED THE BRANCH CIRCUIT CONDUCTORS AND OVER CURRENT |
| | PROTECTION TO BE DONE AT 125%. |
| | PLEASE ALSO INCLUDE THE WATER HEATER LOAD AT 125% FOR |
| | CONTINUOUS LOAD. PLEASE SEE 422.13 OF THE 2005 NEC. |
| | |
| | 5) NOTE: PLEASE SEE THE PREVIOUS NOTE #11 REQUESTED |
| | COORDINATION AND CHANGES FOR CODE COMPLIANCE FOR |
| | FEEDERS ON RISER AND PANEL SCHEDULES. PLEASE SEE SOME |
| | OF THESE ITEMS WERE CHANGED AND CORRECT HOWEVER PLEASE |
| | SEE SOME ITEMS WERE NOT CHANGED. |
| | PLEASE SEE THE FEEDERS NOTED ON PANEL *H* ARE STILL |
| | SHOWN AS 3/0 WHEN THE RISER AND NOTES TO RISER INDICATE |
| | 1/0. |
| | PLEASE SEE COMMENTS BELOW FOR OTHER ITEMS FOR |
| | COORDINATION. |
| | |
| | 6) NOTE: PLEASE SEE THE PREVIOUS NOTE #12 WHICH |
| | REQUESTED FOR THE OVER CURRENT PROTECTION OF THE |
| | TRANSFORMER AS LISTED ON THE PANEL *H* TO MEET 450.3. |
| | THE RESPONSE LETTER MENTIONS THIS IS TO BE CHANGED TO |
| | 70AMP HOWEVER PLEASE SEE PANEL *H* AS THIS NOW SHOW A |
| | 3-POLE 20AMP BREAKER WITH #3 CONDUCTORS. |
| | PLEASE SEE THE RISER SHOWS OTHER CONDUCTOR SIZES. |
| | PLEASE KNOW THE #3 CONDUCTORS WILL NOT FIT INTO THIS |
| | SIZE BREAKER. |
| | PLEASE SEE THIS 20AMP OVER CURRENT PROTECTION DOES NOT |
| | MEET THE MINIMUM LOADS ON THE TRANSFORMER FROM PANEL |
| | *L1*. |
| | 240.4, 310.16, 110.3,ETC. THERE ARE SEVERAL CODE |
| | SECTIONS, TOO MANY TO LIST. |
| | PLEASE COORDINATE. |
| | |
| | 7) NOTE: PLEASE SEE THE LOAD FOR THE TRANSFORMER HAS |
| | NOW BEEN REVISED AND INDICATES A LOAD OF .5 KVA. THIS |
| | IS NOT POSSIBLE WHEN THE LOAD ON PANEL *L1* IS 42KVA AT |
| | 120/208 VOLTS. THIS LOAD WAS CHANGED FROM PREVIOUS |
| | PLANS. |
| | PLEASE SEE THE TOTAL LOAD ON PANEL *H* HAS NOW GONE |
| | DOWN WITH OUT THIS LOAD OF THE PANEL *L1*. |
| | PLEASE COORDINATE AND ADJUST ALL OF THESE ITEMS. |
| | 240,220, 408.4, 310.16, 215, ETC. |
| | |
| | 8) NOTE: PLEASE SEE PREVIOUS NOTE #14. PLEASE CLARIFY |
| | RATING OF THE PANELS *H* AND *L1*ON RISER AND ON |
| | SCHEDULE. |
| | PANEL *L1* IS SHOWN AS A 225AMP RATED PANEL WITH A |
| | 150AMP MCB, YET RISER SHOWS THIS AS 200AMPS? PLEASE SEE |
| | PANEL *H* IS SHOWN ON SCHEDULE AS 225AMP RATED, WITH |
| | 200AMP RATED MCB. THIS IS OK, HOWEVER THIS IS SHOWN AS |
| | 200AMP ON RISER WITH A 150AMP FEED FROM THE BUS-TAP AND |
| | DISCONNECT. |
| | THE ABOVE NEEDS SOME COORDINATION. |
| | FBC 106.1.2, 106.1.1, 106.3.5.1.2 |
| | FAC 61G15-23.004 |
| | |
| | 9) NOTE: PLEASE SEE PREVIOUS NOTE #16 AS THIS REQUESTED |
| | COORDINATION OF THE PANEL NUMBER OF POLES LISTED ON |
| | PANEL AND SHOWN ON CIRCUITS. |
| | PLEASE SEE PANEL *L1* WAS CORRECTED, HOWEVER PLEASE SEE |
| | PANEL *H* IS STILL SHOWN AS 30 AND 42 CIRCUIT PANELS. |
| | (225AMP RATED PANELS ARE MOST LIKELY NOT AVAILABLE AS |
| | 30POLES) |
| | FBC 106.1.2 |
| | |
| | 10) NOTE: PLEASE SEE PREVIOUS NOTE #17 FOR TRANSFORMER |
| | GROUNDING. A CONDUCTOR SIZE WAS ADDED HOWEVER NO |
| | ATTACHMENT LOCATIONS WERE SHOWN OR NOTED. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE INDICATE THE TRANSFORMER GROUNDING ELECTRODE |
| | SYSTEM PER 250.20, 250.30, 250.66 ETC. PLEASE SHOW |
| | ATTACHMENT WITH THE SIZE OF THE CONDUCTOR. FBC 106.1.2, |
| | 106.3.5.1.2, FAC 61G15-33.004 |
| | |
| | 11) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | PLEASE BE SURE TO CALL TO GO OVER COMMENTS. |
| | |
| | AS PREVIOUSLY STATED: |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-09-04 08:28:17 | 2007-09-04 08:28:17 |
| | REVIEW IN PROGRESS |
| 2007-08-31 16:09:26 | IN ELEC, |