| 2007-07-30 10:25:41 | ***DENIED*** | | | | | | 1) DOOR SCHEDULE INDICATES A "C" RATING FOR | | | ELECTRICAL/MECHANICAL DOOR. PLEASE PROVIDE RATING IN | | | TERMS OF MINUTES. | | | | | | 2) PLEASE INDICATE UL LISTED CLOSER FOR APPROPRIATE | | | DOOR. | | | | | | 3) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 4) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 5) PLEASE INDICATE MINIMUM INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS IN TERMS OF CLASS | | | A,B ORC. | | | | | | 6) WORK SHALL NOT INTERFERE WITH EXISTING BUILDING FIRE | | | PROTECTION EQUIPMENT AND REQUIRED MEANS OF EGRESS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|