| 2007-07-18 09:52:49 | |
| | |
| | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS |
| | AMENDED. |
| | |
| | A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED |
| | UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID. |
| | 108.1 FBC. |
| | |
| | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY |
| | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| | COMPLIANCE AND RESUBMIT FOR REVIEW. |
| | |
| | 1} .SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND |
| | 106.3.5.4(8) FBC. |
| | 408.4 CIRCUIT DIRECTORY OR CIRCUIT IDENTIFICATION EVERY |
| | CIRCUIT AND CIRCUIT MODIFICATION SHALL BE LEGIBLY |
| | IDENTIFIED AS TO ITS CLEAR, EVIDENT, AND SPECIFIC |
| | PURPOSE OR USE. THE IDENTIFICATION SHALL INCLUDE |
| | SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| | DISTINGUISHED FROM ALL OTHERS. INCLUDE OCP AND |
| | CONDUCTOR SIZES. |
| | |
| | 2} THE LOCATION OF THE EXISTING 150 AMP PANEL IS IN |
| | VIOLATION OF 110.26 NEC 2005, CLEARANCE REQUIREMENTS. |
| | |
| | 3} THE RISER DIAGRAM INDICATES A DISCONNECT AT THE |
| | METER LOCATION. NO DISCONNECT IS SHOWN ON THE FLOOR |
| | PLAN. PLEASE CLARIFY. THERE ARE TWO RISER DIAGRAMS ON |
| | THE PLAN, A NEW AND EXISTING. INDICATE THE ONE TO BE |
| | USED. |
| | |
| | 4} SHOW THE LOCATION OF THE A/C EQUIPMENT ON THE PLAN. |
| | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14,RECEPTACLE PER 210.63, LIGHT PER 210.70(A) |
| | (3). |
| | |
| | 5} THE WATER HEATER MUST HAVE A DISCONNECTING MEANS PER |
| | 422.31(B), AN DCAN NOT BE A RECEPTACLE AS SHOWN, |
| | 422.16. |
| | |
| | 6} KITCHEN RECEPTACLES MUST COMPLY WITH 210.8(A)(6) |
| | GFI. |
| | |
| | 7} A RECEPTACLE NEEDS TO BE ADDED TO THE MASTER BEDROOM |
| | FOR SPACING REQUIREMENTS OF 210.52(A)(2). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |
| | |
| | |
| | |