 ** DENIEDREVISION **
  
  
  
 1) NOTE: PLEASE COORDINATE ALL CIRCUITING ON PLANS WITH
 PANEL SCHEDULES AND ALSO WITH THE LIGHTING CONTACTOR
 PANELS.
 THIS WAS THE SAME AS IN REVIEW NOTES DATED ON 7/15/08
 YET NO CHANGES HAVE BEEN MADE.
 FOR EXAMPLE:
 PLEASE SEE LIGHTING AND POWER PLANS WHICH BOTH INDICATE
 CIRCUITS? 10LA-13 AND 10LA-5 TO BE ON LIGHTING
 CONTACTORS YET NEITHER LIGHTING CONTACTOR ON SHEET E6.1
 CONTAINS THESE. THIS IS NOTING ONLY TWO, THERE ARE
 OTHERS.
 13-415.1.ABC.1.1, .1.2, .1.3.
 FBC 106.1.1
  
 2) NOTE: PLEASE SEE KEY NOTES ON SHEET E3.1 WHICH DOES
 NOT CONTAIN A KEYNOTE #6 AS NOTED ON PLANS. (MISPRINT)
 FBC 106.1.1 FOR CLARITY AND COORDINATION.
  
 3) NOTE: PLEASE SEE SHEET E3.1 AS THIS INDICATES A
 *FPL* METER. IT HAS COME TO THIS REVIEWER?S ATTENTION
 THAT THERE IS NO FPL METER IN FACT IT IS NOT A TENANT
 CHECK METER EITHER. PLEASE VERIFY WHAT THIS DEVICE IS
 AND REVISE PLANS ACCORDINGLY.
 FBC 106.1.1, 106.3.5.1.2
 NEC
  
 4) NOTE: PLEASE REVISE ALL LIGHTING PERFORMANCE
 CALCULATIONS. THERE HAVE BEEN REVISIONS TO LIGHTS AND
 PLANS YET THE WATTAGE EVEN THOUGH LABELED AS REVISED
 DOES NOT COORDINATE.
 ONE EXAMPLE OF THIS IS THE STORAGE ROOM # 128 WHICH
 INDICATES A TOTAL OF 68WATTS YET THIS IS NOT POSSIBLE
 BASED ON THE WATTAGE OF EACH FIXTURE ON N
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  