| 2008-08-28 11:46:27 | |
| | ** DENIEDREVISION ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE COORDINATE ALL CIRCUITING ON PLANS WITH |
| | PANEL SCHEDULES AND ALSO WITH THE LIGHTING CONTACTOR |
| | PANELS. |
| | THIS WAS THE SAME AS IN REVIEW NOTES DATED ON 7/15/08 |
| | YET NO CHANGES HAVE BEEN MADE. |
| | FOR EXAMPLE: |
| | PLEASE SEE LIGHTING AND POWER PLANS WHICH BOTH INDICATE |
| | CIRCUITS? 10LA-13 AND 10LA-5 TO BE ON LIGHTING |
| | CONTACTORS YET NEITHER LIGHTING CONTACTOR ON SHEET E6.1 |
| | CONTAINS THESE. THIS IS NOTING ONLY TWO, THERE ARE |
| | OTHERS. |
| | 13-415.1.ABC.1.1, .1.2, .1.3. |
| | FBC 106.1.1 |
| | |
| | 2) NOTE: PLEASE SEE KEY NOTES ON SHEET E3.1 WHICH DOES |
| | NOT CONTAIN A KEYNOTE #6 AS NOTED ON PLANS. (MISPRINT) |
| | FBC 106.1.1 FOR CLARITY AND COORDINATION. |
| | |
| | 3) NOTE: PLEASE SEE SHEET E3.1 AS THIS INDICATES A |
| | *FPL* METER. IT HAS COME TO THIS REVIEWER?S ATTENTION |
| | THAT THERE IS NO FPL METER IN FACT IT IS NOT A TENANT |
| | CHECK METER EITHER. PLEASE VERIFY WHAT THIS DEVICE IS |
| | AND REVISE PLANS ACCORDINGLY. |
| | FBC 106.1.1, 106.3.5.1.2 |
| | NEC |
| | |
| | 4) NOTE: PLEASE REVISE ALL LIGHTING PERFORMANCE |
| | CALCULATIONS. THERE HAVE BEEN REVISIONS TO LIGHTS AND |
| | PLANS YET THE WATTAGE EVEN THOUGH LABELED AS REVISED |
| | DOES NOT COORDINATE. |
| | ONE EXAMPLE OF THIS IS THE STORAGE ROOM # 128 WHICH |
| | INDICATES A TOTAL OF 68WATTS YET THIS IS NOT POSSIBLE |
| | BASED ON THE WATTAGE OF EACH FIXTURE ON N |
| | |
| | |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |