| 2008-01-04 14:34:18 | REVIEW #: 3RD |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | COMMENT #3 IS THE ONLY OUTSTANDING COMMENT FROM |
| | PREVIOUS REVIEWS. |
| | PG M0.1, REFERENCE TO ASHRAE 62.1-2004 HAS BEEN REMOVED |
| | FROM PLANS. CALCULATIONS ARE DECLARED TO BE BASED ON |
| | FBC, M TABLE 403.3. HOWEVER, NOTE #2 IN THE |
| | CALCULATIONSINDICATES THAT CALCULATIONS ARE BASED ON |
| | VARIABLE OR INTERMITTENT OCCUPANCY. THERE IS NO |
| | PROVISION FOR SUCH CALCULATIONS RELATED TO TABLE 403.3. |
| | THE FULL OUTSIDE AIR RATES ARE TO BE PROVIDED WHENEVER |
| | HE SPACES ARE OCCUPIED. ALSO, THE CONFERENCE AND LOBBY |
| | AREAS HAVE DIFFERENT OCCUPANT LOADS BASED ON TABLE |
| | 403.3 AND THE OUTSIDE AIR REQUIREMENTS FOR THESE AREAS |
| | SHALL BE CALCULATED SEPARATELY AND IN ADDITION TO THE |
| | OFFICE AREAS. IF TABLE 403.3 IS TO BE USED, PLEASE BASE |
| | THE DESIGN ON THE REQUIREMENTS OF THIS SECTION. DO NOT |
| | MIX THE REQUIREMENTS OF 403.3 WITH ASHRA 62.1. PLEASE |
| | CORRECT AND RESUBMIT. |
| | NOTE: IF THIS WERE THE FINAL ISSUE REQUIRED TO BE |
| | RESOLVED FOR PERMIT, IT MAY HAVE BEEN COVERED WITH A |
| | PROVISO. HOWEVER, A PASSED ELECTRICAL REVIEW IS ALSO |
| | PENDING. |
| | |