| 2007-12-22 12:45:02 | ** DENIED3RDREVIEW ** |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS TWO REVIEWS |
| | WITH RESPECT TO LIGHTING PERFORMANCE CALCULATIONS AND |
| | LIGHTING CONTROLS ARE STILL IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE |
| | CALCULATIONS WHICH ARE BEING SUBMITTED FOR REVIEW ARE |
| | NOW COMPLETE HOWEVER COORDINATION OF PLANS, FIXTURES, |
| | AND CALCULATIONS ARE NEEDED. IN THE MEETING HELD ON |
| | DECEMBER 18TH, 2007 THE PREVIOUS COMMENT WAS GONE OVER |
| | TO MAKE SURE ALL LIGHTING WHICH IS SHOWN ON PLANS IS IN |
| | THE CALCULATIONS NOW SHOWN AND SUBMITTED ON E6.1. THERE |
| | WAS NO COMPLETE REVIEW OF CALCULATIONS THE COMMENT WAS |
| | MADE TO PLEASE BE SURE ALL COORDINATION WAS ADDRESSED. |
| | FIXTURE LEGEND DOES NOT COMPLETE INFORMATION FOR WALL |
| | SCONCES ONLY GIVES THE 40W DESIGNATION WHICH IS OK. ANY |
| | CHANGES OF MINIMUM FIXTURES MAY BE DONE BEFORE |
| | INSTALLATION. |
| | PLEASE SEE BELOW AS THERE ARE SOME EXAMPLES WHICH ARE |
| | BEING GIVEN WHICH NOTES SOME OF THE LOCATIONS ON PLANS |
| | WHICH ARE STILL IN QUESTION. |
| | THESE ARE FOR EXAMPLE: |
| | |
| | PLEASE SEE MISSING ROOM 133 FROM CALCULATIONS. |
| | |
| | PLEASE SEE MISSING ROOM 128 FROM CALCULATIONS. |
| | |
| | PLEASE SEE ROOM 108 AS 6-32W FIXTURES AND 1-J-FIXTURE |
| | WHICH IS 200W IS SHOWN ON PLANS. THIS TOTALS 392W |
| | HOWEVER THE CALCULATION SHOWS DESIGN AS 328W. |
| | |
| | PLEASE SEE ROOM 105 AS PLANS SHOWS 5-32W FIXTURES WHICH |
| | TOTALS 160W YET CALCULATIONS SHOWS DESIGN AS128W. |
| | |
| | PLEASE SEE ROOM 101 (LOBBY) WHICH INDICATES 7-32W, 2-35 |
| | AND 2-40W (WALL SCONCES) WHICH IS 374W YET CALCULATIONS |
| | SHOWS DESIGN AS 310W. |
| | |
| | PLEASE SEE ROOM 112 AS PLANS SHOW 5-32W, 3-32W (UC LTS) |
| | WHICH IS A TOTAL OF 256W, YET THE CALCULATIONS SHOWS |
| | DESIGN AS 192W. |
| | |
| | PLEASE SEE THE CORRIDORS AS THE TOTAL NUMBER OF GENERAL |
| | LIGHTING AND DECORATIVE LIGHTING FIXTURES COMES TO A |
| | TOTAL OF 1462W, YET BASED ON THE TOTAL OF CORRIDOR |
| | DESIGN WATTAGE SHOWN ON TABLE, THE TOTAL IS 1145W. |
| | |
| | ** PLEASE SEE SOME OTHER ROOMS SUCH AS 107 SHOWS 397W |
| | BASED ON PLANS AND FIXTURES SHOWN AND TABLE DESIGN IS |
| | 497W? |
| | |
| | THE ABOVE IS SOME EXAMPLES; PLEASE MAKE SURE ALL |
| | LIGHTING ON PLANS CORRELATES WITH THE LIGHTING |
| | CALCULATIONS. |
| | 13-415.2, 13-415.2.B.1, TABLE 13-415.2.B |
| | |
| | 2) NOTE: PLEASE SEE AS PREVIOUSLY MENTIONED ON BOTH |
| | PREVIOUS REVIEWS, PLEASE COMPLETE AND COORDINATE ALL |
| | LIGHTING CIRCUITS FOR LIGHTING CONTACTORS AND CONTROLS |
| | PER FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE PREVIOUS NOTES GAVE A COUPLE OF EXAMPLES AND |
| | SPECIFICALLY STATED THESE WERE NOT ALL. IN MEETING HELD |
| | DECEMBER 18TH, 2007 A COMMENT WAS MADE TO PLEASE BE |
| | SURE ALL CIRCUITING FOR LIGHTING ETC WAS COORDINATED ON |
| | PLANS, PANELS, CONTROLS ETC. |
| | PLEASE SEE BELOW FOR EXAMPLES: |
| | |
| | ROOM 120, 130 AS BOTH OF THESE ROOMS CONTAINS A |
| | CIRCULAR NOTE #1 WHICH STATES TO CONNECT TO THE |
| | LIGHTING CLOCK OUTLETS TO THE SAME WALL SCONCE LIGHTING |
| | CIRCUIT IN THAT SPECIFIC ROOM. PLEASE SEE THESE ARE |
| | NOTED AS CIRCUIT 10LA-13 ON POWER PLANS YET THE |
| | LIGHTING PLANS WHICH SHOWS THE LIGHTING CIRCUIT |
| | INDICATES 10LA-15. |
| | |
| | ROOM/LOBBY 101 WHICH INDICATES LIGHTING OUTLETS FOR |
| | CIRCUIT 10LB-16, YET THIS CIRCUIT IS NOT ON EITHER |
| | LIGHTING CONTACTOR LCA OR LCB. PLEASE SEE THE SWITCH IS |
| | STILL ALSO SHOWN AS A STANDARD SINGLE POLE SWITCH FOR |
| | THESE LIGHTING OUTLETS. |
| | PLEASE SEE PANEL SCHEDULE AS CIRCUIT IS NOTED FOR |
| | GENERAL PURPOSE RECEPTACLES |
| | |
| | ROOM 109 AND 111 WHICH CONTAIN CIRCUITS FOR ACCENT |
| | LIGHTING TIED TOGETHER. PLEASE SEE THE ACCENT LIGHTING |
| | OUTLETS ON POWER PLANS FOR THESE ROOMS ARE SHOWN AS |
| | CIRCUIT 10LA7, HOWEVER LIGHTING PLANS SHOW 10LA- AND |
| | 10LA- 11 TIED TOGETHER. |
| | PLEASE ALSO SEE EVEN AS THE PLANS CONTAINS NOTES WHICH |
| | MENTIONS ALL ACCENT LIGHTING TO CONTACTORS, NEITHER |
| | CONTACTOR SCHEDULE LCA OR LCB CONTAIN EITHER10LA-7 OR |
| | 10LA-11? |
| | PLEASE SEE EVEN AS THESE SWITCHED LIGHTING OUTLETS |
| | CONTAIN A NOTE #1 ON ROOM 117 WHICH STATES TO CONNECT |
| | TO WALL SCONCE CIRCUIT IN SAME ROOM, THE WALL SCONCES |
| | IN THIS SAME ROOM 117 DOES NOT CONTAIN ANY CIRCUIT(S). |
| | |
| | ROOM/CORRIDOR 123 CONTAINS A SWITCH WITH A NOTE WHICH |
| | STATES TO HALLWAY WALL SCONCES, YET THE PLANS DOE NOT |
| | SHOW ANY HALLWAY WALL SCONCES? |
| | |
| | *** AS MENTIONED ON PREVIOUS REVIEWS AND MEETING PLEASE |
| | BE SURE ALL ITEMS ON PLANS CORRELATE WITH ALL LIGHTING |
| | CONTROLS REQUIRED IN SECTIONS NOTED ABOVE. SOME OF THE |
| | EXAMPLES AS NOTED ABOVE MAY NOT BE ALL AND ONLY SOME |
| | EXAMPLES WERE GIVEN. |
| | |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO FS |
| | 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR |
| | MINIMUM CODE COMPLIANCE. |
| | PLEASE SEE THAT A FEE OF $7500.00 HAS BEEN ASSESSED AS |
| | REQUIRED BY THE FLORIDA STATUTES. PLEASE ALSO SEE AS |
| | REQUIRED UNDER THE FLORIDA STATUTES FEE MUST BE PAID |
| | BEFORE NEXT RE-SUBMISSION OF PLANS. |
| | THIS IS NOT THE RESPONSIBILITY OF THE CONTRACTOR OR |
| | OWNER. |
| | ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE BEING |
| | RETAINED BY THIS OFFICE. |
| | |
| | *** AS STATED ON PREVIOUS REVIEWS, IF THERE ARE ANY |
| | QUESTIONS, COMMENTS OR IF ANY PARTS OF THE NOTES WHICH |
| | ARE TYPED ARE NOT CLEAR IN ANY WAY, PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE FOR CLARIFICATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |