Plan Review Notes
Plan Review Notes For Permit 07070352
Permit Number 07070352
Review Stop E
Sequence Number 3
Notes
Date Text
2007-12-22 12:45:02** DENIED3RDREVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS TWO REVIEWS
 WITH RESPECT TO LIGHTING PERFORMANCE CALCULATIONS AND
 LIGHTING CONTROLS ARE STILL IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE
 CALCULATIONS WHICH ARE BEING SUBMITTED FOR REVIEW ARE
 NOW COMPLETE HOWEVER COORDINATION OF PLANS, FIXTURES,
 AND CALCULATIONS ARE NEEDED. IN THE MEETING HELD ON
 DECEMBER 18TH, 2007 THE PREVIOUS COMMENT WAS GONE OVER
 TO MAKE SURE ALL LIGHTING WHICH IS SHOWN ON PLANS IS IN
 THE CALCULATIONS NOW SHOWN AND SUBMITTED ON E6.1. THERE
 WAS NO COMPLETE REVIEW OF CALCULATIONS THE COMMENT WAS
 MADE TO PLEASE BE SURE ALL COORDINATION WAS ADDRESSED.
 FIXTURE LEGEND DOES NOT COMPLETE INFORMATION FOR WALL
 SCONCES ONLY GIVES THE 40W DESIGNATION WHICH IS OK. ANY
 CHANGES OF MINIMUM FIXTURES MAY BE DONE BEFORE
 INSTALLATION.
 PLEASE SEE BELOW AS THERE ARE SOME EXAMPLES WHICH ARE
 BEING GIVEN WHICH NOTES SOME OF THE LOCATIONS ON PLANS
 WHICH ARE STILL IN QUESTION.
 THESE ARE FOR EXAMPLE:
  
 PLEASE SEE MISSING ROOM 133 FROM CALCULATIONS.
  
 PLEASE SEE MISSING ROOM 128 FROM CALCULATIONS.
  
 PLEASE SEE ROOM 108 AS 6-32W FIXTURES AND 1-J-FIXTURE
 WHICH IS 200W IS SHOWN ON PLANS. THIS TOTALS 392W
 HOWEVER THE CALCULATION SHOWS DESIGN AS 328W.
  
 PLEASE SEE ROOM 105 AS PLANS SHOWS 5-32W FIXTURES WHICH
 TOTALS 160W YET CALCULATIONS SHOWS DESIGN AS128W.
  
 PLEASE SEE ROOM 101 (LOBBY) WHICH INDICATES 7-32W, 2-35
 AND 2-40W (WALL SCONCES) WHICH IS 374W YET CALCULATIONS
 SHOWS DESIGN AS 310W.
  
 PLEASE SEE ROOM 112 AS PLANS SHOW 5-32W, 3-32W (UC LTS)
 WHICH IS A TOTAL OF 256W, YET THE CALCULATIONS SHOWS
 DESIGN AS 192W.
  
 PLEASE SEE THE CORRIDORS AS THE TOTAL NUMBER OF GENERAL
 LIGHTING AND DECORATIVE LIGHTING FIXTURES COMES TO A
 TOTAL OF 1462W, YET BASED ON THE TOTAL OF CORRIDOR
 DESIGN WATTAGE SHOWN ON TABLE, THE TOTAL IS 1145W.
  
 ** PLEASE SEE SOME OTHER ROOMS SUCH AS 107 SHOWS 397W
 BASED ON PLANS AND FIXTURES SHOWN AND TABLE DESIGN IS
 497W?
  
 THE ABOVE IS SOME EXAMPLES; PLEASE MAKE SURE ALL
 LIGHTING ON PLANS CORRELATES WITH THE LIGHTING
 CALCULATIONS.
 13-415.2, 13-415.2.B.1, TABLE 13-415.2.B
  
 2) NOTE: PLEASE SEE AS PREVIOUSLY MENTIONED ON BOTH
 PREVIOUS REVIEWS, PLEASE COMPLETE AND COORDINATE ALL
 LIGHTING CIRCUITS FOR LIGHTING CONTACTORS AND CONTROLS
 PER FBC CHAPTER 13, 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE PREVIOUS NOTES GAVE A COUPLE OF EXAMPLES AND
 SPECIFICALLY STATED THESE WERE NOT ALL. IN MEETING HELD
 DECEMBER 18TH, 2007 A COMMENT WAS MADE TO PLEASE BE
 SURE ALL CIRCUITING FOR LIGHTING ETC WAS COORDINATED ON
 PLANS, PANELS, CONTROLS ETC.
 PLEASE SEE BELOW FOR EXAMPLES:
  
 ROOM 120, 130 AS BOTH OF THESE ROOMS CONTAINS A
 CIRCULAR NOTE #1 WHICH STATES TO CONNECT TO THE
 LIGHTING CLOCK OUTLETS TO THE SAME WALL SCONCE LIGHTING
 CIRCUIT IN THAT SPECIFIC ROOM. PLEASE SEE THESE ARE
 NOTED AS CIRCUIT 10LA-13 ON POWER PLANS YET THE
 LIGHTING PLANS WHICH SHOWS THE LIGHTING CIRCUIT
 INDICATES 10LA-15.
  
 ROOM/LOBBY 101 WHICH INDICATES LIGHTING OUTLETS FOR
 CIRCUIT 10LB-16, YET THIS CIRCUIT IS NOT ON EITHER
 LIGHTING CONTACTOR LCA OR LCB. PLEASE SEE THE SWITCH IS
 STILL ALSO SHOWN AS A STANDARD SINGLE POLE SWITCH FOR
 THESE LIGHTING OUTLETS.
 PLEASE SEE PANEL SCHEDULE AS CIRCUIT IS NOTED FOR
 GENERAL PURPOSE RECEPTACLES
  
 ROOM 109 AND 111 WHICH CONTAIN CIRCUITS FOR ACCENT
 LIGHTING TIED TOGETHER. PLEASE SEE THE ACCENT LIGHTING
 OUTLETS ON POWER PLANS FOR THESE ROOMS ARE SHOWN AS
 CIRCUIT 10LA7, HOWEVER LIGHTING PLANS SHOW 10LA- AND
 10LA- 11 TIED TOGETHER.
 PLEASE ALSO SEE EVEN AS THE PLANS CONTAINS NOTES WHICH
 MENTIONS ALL ACCENT LIGHTING TO CONTACTORS, NEITHER
 CONTACTOR SCHEDULE LCA OR LCB CONTAIN EITHER10LA-7 OR
 10LA-11?
 PLEASE SEE EVEN AS THESE SWITCHED LIGHTING OUTLETS
 CONTAIN A NOTE #1 ON ROOM 117 WHICH STATES TO CONNECT
 TO WALL SCONCE CIRCUIT IN SAME ROOM, THE WALL SCONCES
 IN THIS SAME ROOM 117 DOES NOT CONTAIN ANY CIRCUIT(S).
  
 ROOM/CORRIDOR 123 CONTAINS A SWITCH WITH A NOTE WHICH
 STATES TO HALLWAY WALL SCONCES, YET THE PLANS DOE NOT
 SHOW ANY HALLWAY WALL SCONCES?
  
 *** AS MENTIONED ON PREVIOUS REVIEWS AND MEETING PLEASE
 BE SURE ALL ITEMS ON PLANS CORRELATE WITH ALL LIGHTING
 CONTROLS REQUIRED IN SECTIONS NOTED ABOVE. SOME OF THE
 EXAMPLES AS NOTED ABOVE MAY NOT BE ALL AND ONLY SOME
 EXAMPLES WERE GIVEN.
  
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS FOR
 MINIMUM CODE COMPLIANCE.
 PLEASE SEE THAT A FEE OF $7500.00 HAS BEEN ASSESSED AS
 REQUIRED BY THE FLORIDA STATUTES. PLEASE ALSO SEE AS
 REQUIRED UNDER THE FLORIDA STATUTES FEE MUST BE PAID
 BEFORE NEXT RE-SUBMISSION OF PLANS.
 THIS IS NOT THE RESPONSIBILITY OF THE CONTRACTOR OR
 OWNER.
 ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE BEING
 RETAINED BY THIS OFFICE.
  
 *** AS STATED ON PREVIOUS REVIEWS, IF THERE ARE ANY
 QUESTIONS, COMMENTS OR IF ANY PARTS OF THE NOTES WHICH
 ARE TYPED ARE NOT CLEAR IN ANY WAY, PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE FOR CLARIFICATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]