Plan Review Notes
Plan Review Notes For Permit 07070352
Permit Number 07070352
Review Stop P
Sequence Number 2
Notes
Date Text
2007-12-03 16:46:11DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
  
 4. THE BASE BUILDING HAS NOT RECIEVED A CERTIFICATE OF
 OCCUPANCY AT THIS TIME. THE BUILDING OFFICIAL HAS
 DETERMINED THAT ALL PLANS SHALL BE REVIEWED BY THE
 DESIGNERS OF THE BASE BUILDING FOR ALL TENANT
 BUILDOUTS. PLANS SHALL BE STAMPED AS REVIEWED BY BASE
 BUILDING DESIGN TEAM PRIOR TO RESUBMITTING FOR REVIEW
 AT THE CITY WPB. (SEE COMMENTS BY MECHANICAL REVIEW,
 (1), ELECTRICAL REVIEW, (4), AND BUILDING (2)).--
 SINCE THE BUILD-OUT G.C. IS A DIFFERENT COMPANY FROM
 THE BASE BUILDING G.C., A LETTER IS REQUIRED FROM THE
 DEVELOPER, SIGNED BY THE BASE BUILD G.C. AND THE SHELL
 G.C., STATING THAT ALL PARTIES UNDERSTAND THAT NO
 DISPUTE OVER WORK SCOPE OR RESPONSIBILITY CAN COME
 BEFORE THE REQUIREMENT FOR COMPLIANCE WITH FLORIDA
 BUILDING CODE.
 ****RESPONSE NOTED, BUT THE LETTER REQUESTED FROM THE
 DEVELOPER, SIGNED BY THE GENERAL CONTRACTORS HAS NOT
 BEEN SUBMITTED.
  
 5. SHTS ID-1 THRU ID-15 SHALL HAVE THE SIGNATURE AND
 DATE THE SEAL AND SIGNATURE WERE AFFIXED TO PLANS. IT
 APPEARS THAT INITIALS HAVE BEEN USED IN PLACE OF
 SIGNATURE WHEN SEALING THE PLANS. IF THIS INDEED THE
 LEGAL SIGNATURE OF THE INTERIOR DESIGNER, THEN A
 SIGNED, SEALED, NOTORIZED LETTER INDICATING THE
 INTERIOR DESIGNER'S LEGAL SIGNATURE SHALL BE SUBMITTED
 FOR OUR FILES. FAC 61G1-16.003,61G1-16.004(5) &
 481.2055.
 ****RESPONSE NOTED, BUT THE DATE THAT THE SIGNATURE AND
 SEAL WERE AFFIXED ON THE PLANS HAS NOT BEEN INDICATED
 AS REQUIRED.
  
 6. OK
 7. OK
 8. OK
 9. OK
  
 10. SUBMIT A DETAIL FOR THE TOILET ROOM FIXTURES
 SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17,
 11-4.19 & 11-4.21 WITH ALL SUBSECTIONS. SHOW THE CLEAR
 FLOOR SPACE FOR ALL ACCESSIBLE FIXTURES ON THE FLOOR
 PLAN AS WELL AS THE TURNING AREA IN BOTH TOILET ROOMS.
 SUBMIT ELEVATIONS TO SHOW COMPLIANCE FOR ALL OTHER
 REQUIREMENTS.
 ****RESPONSE NOTED, BUT COMPLIANCE FOR THE FOLLOWING IS
 NOT SHOWN:
 ___FOR THE W/C'S
 A. 11-4.16.2 CLEAR FLOOR SPACE
 B. 11-4.16.4 GRAB BARS (42" REQD ON SIDE)
 THE LAV FAUCET SHOWN ON THE PLAN IS A KOHLER MODEL
 PK272, BUT THE ATTACHED SPECIFICATION BOOK INDICATES
 THE FAUCET AS A KOHLER MODEL K-394, (APPROVED), PLEASE
 CLARIFY AND CORRELATE.
  
 11. OK
  
 12. THE SINK IN THE BREAKROOM, (ROOM #112), SHALL BE
 ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE
 WITH SECTION 11-4.24 AND ALL SUBSECTIONS. ELEVATION
 A1/ID-14 INDICATES CABINET DOORS. THE DOORS ARE NOT
 APPROVED IN THE CLEAR FLOOR SPACE AND SHALL BE DELETED
 FROM DETAIL. FORWARD APPROACH IS REQUIRED. SHOW CLEAR
 FLOOR SPACE ON THE FLOOR PLAN AND OTHER REQUIREMENTS ON
 THE ELEVATION. (NOTE: THE GARBAGE DISPOSAL SHALL BE ADA
 APPROVED. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS
 SHOWING APPROVAL).
 ****RESPONSE NOTED, BUT COMPLIANCE NOT SHOWN FOR
 SECTION 11-4.24.7 FAUCET, AND THE GARBAGE DISPOSAL
 SEPCIFICATION SHEETS HAS NOT BEEN SUBMITTED.
  
 13. OK
  
 14. DELETED - OK
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]