| 2007-11-28 11:33:41 | ** DENIED2ND REVIEW ** |
| | |
| | ** PLEASE KNOW THERE ARE STILL SOME COMMENTS FROM |
| | PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING ALONG |
| | WITH NEW COMMENTS DUE TO ITEMS NOW REVISED ON PLANS |
| | WHICH WERE NOT ON ORIGINAL PLANS. |
| | |
| | 1) NOTE: PLEASE SEE THE PERMIT APPLICATION PACKAGE WAS |
| | SUBMITTED BACK WITH RESPONSES FROM THE INTERIOR DESIGN |
| | TEAM WHICH MENTIONS TO SEE RESPONSES TO THE MEP NOTES |
| | FROM OTHER DESIGN PROFESSIONALS; HOWEVER NO RESPONSE |
| | LETTERS FROM ANY OTHER TRADE DESIGNERS WERE LOCATED |
| | WITH PACKAGE BROUGHT BACK. |
| | (PACKAGE CONTAINED: |
| | 1) LETTER/RESPONSE FROM STH FOR BASE BUILDING REVIEW. |
| | |
| | 2) 3-BOOKETS FOR RESPONSES FROM LISA ERDMANN AND |
| | ASSOCIATES. |
| | |
| | 3) ORIGINAL PERMIT APPLICATION WITH NOTES FROM TRADES. |
| | |
| | ** PLEASE KNOW RESPONSES FROM MEP DESIGNERS ARE NOT |
| | REQUIRED HOWEVER DO HELP TO EXPEDITE THE REVIEW PROCESS |
| | ON HOW COMMENTS WERE ADDRESSED OR RESPONSE ON |
| | COMMENTS. |
| | |
| | |
| | 2) NOTE: PLEASE SEE THAT THE FOLLOWING CODES SHALL BE |
| | STATED ON PLANS. PLEASE SEE THIS COMMENT IS FOR THE ID |
| | COVER SHEETS AS IT REFLECTS A 2003 NFPA-70. |
| | PLEASE KNOW THIS SHOULD BE 2005. |
| | IF THIS SHEET DOES NOT NEED TO BE REVISED FOR OTHER |
| | TRADES OR FOR OTHER COMMENTS, THERE WILL BE NO NEED TO |
| | RE-PRINT SHEET ONLY FOR THIS. IT COULD BE REDLINED. |
| | |
| | 2) NOTE: PLEASE SEE ELECTRICAL PLANS INDICATES THE |
| | TRANSFORMER AS CEILING MOUNTED HOWEVER THE ID PLANS |
| | SPECIFICALLY CALL FOR A 1HR RATED CEILING TO BE |
| | INSTALLED IN THIS SAME ROOM. |
| | THIS WAS GONE OVER IN THE MEETING PREVIOUSLY HELD |
| | BEFORE PLANS WERE RESUBMITTED THAT THE CODE |
| | SPECIFICALLY 450.13 A AND B DOES NOT PERMIT THIS SIZE |
| | OF TRANSFORMER ABOVE CEILING. THE COMMENT IN THE |
| | MEETING WAS THAT THERE WOULD BE NO CEILING INSTALLED IN |
| | THE ELECTRICAL ROOM 127 AND THE 1HR RATED WALLS WERE |
| | GOING TO GO UP TO THE DECK. |
| | PLEASE ADJUST. |
| | |
| | 3) NOTE: PLEASE SEE POSSIBLE COMMENTS FROM MECHANICAL |
| | REVIEW FOR RATED CEILING IN SERVER ROOM 104. ** THIS IS |
| | ONLY NOTED FOR INFORMATIONAL PURPOSE. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS COMMENTS WITH RESPECT TO |
| | COMPLETED SYSTEM FOR LIGHTING CONTROLS PER FBC CHAPTER |
| | 13, 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE THERE ARE CIRCUITS ON PLANS WHICH ARE NOTED |
| | TO LIGHTING CONTACTOR EITHER LCA OR LCB, HOWEVER |
| | NEITHER LIGHTING CONTACTOR CONTAINS THESE CIRCUITS. |
| | PLEASE SEE FOR EXAMPLE ONE FROM EACH: 10LA-27 AND |
| | 10HA-1 |
| | PLEASE ALSO SEE 13-415.1.ABC.1.3 FOR ACCENT/TASK |
| | LIGHTING. |
| | PLEASE COORDINATE AND ADJUST. |
| | |
| | 5) NOTE: PLEASE COMPLETE LIGHTING PERFORMANCE |
| | CALCULATIONS WHICH CONFORM TO THE FBC. PLEASE SEE THE |
| | LIGHTING POWER DENSITIES SUBMITTED ON E6.1REFLECT |
| | 13-415.2.B.1 WHICH IS FOR SPACE BY SPACE HOWEVER NO |
| | SPACE BY SPACE CALCULATIONS WERE SUBMITTED. THE FIGURE |
| | SUBMITTED SHOWS ALL AS *OFFICE* ONLY AT 1.1 SQ FT. |
| | PLEASE KNOW THE LIGHTING ON PLANS AND FIXTURES SHOWN ON |
| | FIXTURE LEGEND ON E0.1 ARE NOT COMPLETE AT THIS TIME. |
| | PLEASE IDENTIFY ALL FIXTURES ON FIXTURE LEGEND. FOR |
| | EXAMPLE: FIXTURE *J* ON PLANS, NOT ON FIXTURE LEGEND. |
| | FOR EXAMPLE: PLEASE SEE THE FIXTURE COUNT SHALL INCLUDE |
| | ALL FIXTURES, WATTAGES FOR THE MAXIMUM LPD AS ALLOWED. |
| | PLEASE KNOW AS THE FIXTURE LEGEND WILL NEED TO BE |
| | ADJUSTED AND SPACE BY SPACE WAS NOT SUBMITTED, A |
| | COMPLETE REVIEW OF ALL FIXTURES COULD NOT BE DONE AT |
| | THIS TIME. |
| | PLEASE BE SURE TO COORDINATE ALL. |
| | |
| | 6) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT CODE COMPLIANT COMMENTS. THIS IS ONLY A NOTICE |
| | GIVEN AT THIS TIME. |
| | PLEASE KNOW ONE COPY OF EACH ELECTRICAL HAS BEEN |
| | RETAINED BY THIS OFFICE. |
| | |
| | *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |