| 2007-11-29 08:13:06 | GOODRICH LLC CITY PL. TOWER SUITE # 1000 |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07070352 |
| | ADD: 525 OKEECHOBEE BLVD # 1000 |
| | CONT: DAVIS GENERAL CONTRACTING CORP |
| | TEL: (561) 820-1400 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) NOTE OF REFRENECE ONLY, BASED ON THE DETERMINATION |
| | OF THE BUILDING OFFICIAL, APPLICATION FOR TENANT |
| | IMPROVEMENT PRIOR TO C.O. WILL REQUIRE SHOP DRAWING |
| | REVIEW BY THE BASE BUILDING DESIGN TEAM, THE DESIGNER |
| | OF RECORD. PLEASE HAVE THE BASE BUILDING DESIGNERS OF |
| | RECORD REVIEW YOUR PLANS AND IF FOUND SUFFICIENT AFFIX |
| | THEIR SHOP DRAWING STAMP ON YOUR DOCUMENTS. |
| | NOTE ALSO THAT A TENANT CAN NOT ACHIEVE A CERTIFICATE |
| | OF OCCUPANCY BEFORE THE SHELL BUILDING HAS RECEIVED |
| | THEIR CERTIFICATE OF COMPLETION. FBC 106.1.2* |
| | ADMINISTRATIVE CODE. |
| | |
| | 3)NOTE OF REFRENECE ONLY, PLEASE NOTE AT THIS TIME |
| | THIS BUILDING HAS NOT RECEIVED A CERTIFICATE OF |
| | COMPLETION, AND THE ENERGY CALCULATIONS ARE BASED ON A |
| | SHELL BUILDING AND ARE BASED ON 13-101.1.6. UNLESS THE |
| | BUILDING IS COMPLETED AS PER ALL ASSUMPTIONS MADE IN |
| | THE ORIGINAL CODE COMPLIANCE SUBMITTAL, REVISED CODE |
| | SUBMITTALS USING METHOD A, B OR C SHALL BE SUBMITTED |
| | WHEN THE COMPLETION OF THE BUILDING (OR PART) OF A |
| | BUILDING IS PERMITTED. |
| | |
| | 4-6A) COMPLIED. |
| | |
| | 6B) 2ND REQUEST,SHEET ID-1A ALSO INDICATES THE TENANT |
| | SEPERATION WALLS TO BE EXISTING DEMISSING WALL.THE |
| | BASE SHELL BUILDING PLAN DOESN'T INDICATE ANY SUCH WALL |
| | IN THE MOST RECENT SET OF REVISIONS SHEET A1.07 |
| | REVISION# 15 DATED 6/13/07. SECTION 708.1(5) REQUIRES |
| | FIRE PARTITIONS BETWEEN TENANTS. 708.3 FIRE RESISTANCE |
| | RATING WILL REQUIRE A 1-HOUR FIRE RATING. |
| | FLORIDA STATE STATUTE 481.2131 INTERIOR DESIGNER CAN |
| | NOT DESIGN PLANS OR PORTIONS OF THAT EFFECT FIRE-RATED |
| | SEPERATIONS BETWEEN INTERIOR SPACES, THE FIRM IS |
| | WORKING OUT OF THE SCOPE OF THEIR LOCENSE. SEE |
| | ATTACHMENT 481.2131. A FLORIDA LICENSED ARCHITECT WILL |
| | NEED TO DESIGN ALL COMPONENTS THAT WILL REQUIRE FIRE |
| | RATED WALLS, CEILINGS AS WELL AS THE PENETRATIONS |
| | THROUGH SUCH RATED ASSEMBLIES. |
| | SHEET 1D-1A NOW INDICATE A RATED CEILING IN THE IT OR |
| | SERVER ROOM & THE ELECTRIC ROOM 127 BUT NO ASSEMBLY HAS |
| | BEEN CALLED OUT, AGAIN WORKING OUT OF THE SCOPE OF |
| | LICENSURE FL SS 481.2131. |
| | THIS PERMIT IS A STAND ALONE PERMIT AND THE WORK TO BE |
| | COMPLETED UNDER THIS PERMIT, EVEN IF THE DEMISSING |
| | WALLS, FIRE RATED WALLS AND CEILINGS OF THE SERVER ROOM |
| | AND ELECTRIC ROOM WERE TO BE COMPLETED UNDER THE BASE |
| | BUILDING PERMIT, THE THROUGH PENETRATIONS OF THE |
| | VARIOUS TRADES WILL NEED DETAILS INDICATING AS TO WHAT |
| | SYSTEMS TO BE USED AND OR UL LISTINGS WHICH WOULD AGAIN |
| | FALL INTO THE WORK TO BE COMPLETED BY THE TRADES THAT |
| | ARE COVERED UNDER THIS PERMIT. 712.4.1. THROUGH |
| | PENETRATIONS, HORIZONTAL AND VERTICAL. |
| | |
| | 6C) PLEASE NOTE ELECTRICAL COMMENT ABOUT TRANSFORMER |
| | ABOVE RATED CEILING IN THE ELECTRIC ROOM 127. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 7) COMPLIED. |
| | |
| | 8) RECONFIGURATION OF TENANT SPACE, CLOSET 133 IS |
| | MISSING THE DOOR IDENTIFICATION MARKER BUT THE DOOR IS |
| | MISSING 18" CLEARENCE ON THE LATCH SIDE OF THE DOOR. |
| | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM |
| | MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC |
| | OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE |
| | FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES |
| | SHALL BE CLEAR & LEVEL. |
| | |
| | 9-13) COMPLIED. |
| | |
| | 14) 2ND REQUEST,ON THE INTERIOR ELEVATION SHEETS |
| | QUITE A FEW WALLS INDICATE THE USE OF UPHOLSTERED |
| | PANELS, SUBMITTED DOCUMENT FOR THE FOAM IS A TEST THAT |
| | PASSES CAL 117 NOT THE TEST REQUIRED UNDER SECTION |
| | 803.6.1.1 OR 803.1.2. |
| | |
| | |
| | THE TEST REFERED TO IS NOT CAL 117 BUT NFPA 265. WHEN |
| | RESEARCHING CAL 117 TEST CRITERIA THIS IS NOT SO CLEAR |
| | SINCE INFORMATION FOUND ON THE WEB FOR THIS TEST IS A |
| | DRAFT FORM, BUT THE TEST INDICATES THAT TWO PROPOSALS |
| | ONE A B5 SECOND FLAME TEST, AND THE SECOND PROPOSAL A |
| | 10 SECOND FLAME TEST BUT THE KW OF FIRE OR HEAT APPLIED |
| | IS NOT PROVIDED. IN ONE AREA OF THE REPORT IT SUGESTED |
| | THAT OF A BURNIUNG CIGARETTE.THE PAS FAIL CRITERIA |
| | WAS ALSO A AREA OF QUESTION SINCE THIS IS A DRAFT FORM |
| | DOCUMENT. |
| | |
| | THE TEST LISTED IN SECTIONS 803.6.1.1 AND 603.6.1.2 |
| | REFERENCE NFPA 265 AND THE RESULTS IT TAKES TO PASS |
| | THIS TEST BY USING METHOD A OR THE MORE RESTRICTIVE |
| | METHOD B. IN EITHER CASE THE FABRIC, FOAM AND |
| | "ADHESIVE" ARE TO BE TESTED.BELOW IS THE TEST |
| | CRITERIA TO BE MET WHICH IS MORE RESTRICTIVE THAN THE |
| | CAL 117 SUBMITTED. |
| | |
| | NFPA 265:9.1 METHOD A 9.2. |
| | METHOD B PROTOCOL SPECIFIED IN 1.4.1 SHALL BE USED. |
| | 9.2 PROCEDURE. |
| | THE TEST PROCEDURE SHALL BE AS FOLLOWS: |
| | (1)ESTABLISH AN INITIAL VOLUMETRIC FLOW RATE OF |
| | AT LEAST 0.47 M3/S (1000 STANDARD FT3/MIN) THROUGH THE |
| | DUCT, AND INCREASE THE VOLUME FLOW RATE TO 3.4 M3/S |
| | (7000 STANDARD FT3/MIN) AS REQUIRED TO KEEP THE OXYGEN |
| | CONTENT ABOVE 14 PERCENT AND TO CAPTURE ALL EFFLUENTS |
| | FROM THE BURN ROOM. |
| | (2)TURN ON ALL SAMPLING AND RECORDING DEVICES, |
| | AND ESTABLISH STEADY-STATE BASELINE READINGS FOR AT |
| | LEAST 2 MINUTES. |
| | (3)IGNITE THE GAS BURNER AND PROCEED AS FOLLOWS: |
| | |
| | (A)START THE TIMER ONCE BURNER IGNITION HAS BEEN |
| | OBSERVED, AND INCREASE GAS FLOW RATE TO PROVIDE A |
| | BURNER RATE OF HEAT RELEASE EQUAL TO THE REQUIRED HEAT |
| | OUTPUT FOR THE INITIAL PERIOD. THIS RATE SHALL BE 40 KW |
| | ? 1 KW FOR 5 MINUTES ? 10 SECONDS. |
| | (B)CONTINUE THE EXPOSURE AT THAT SAME LEVEL FOR 5 |
| | MINUTES. |
| | (C)WITHIN 10 SECONDS AFTER THE 5-MINUTE INITIAL |
| | EXPOSURE, INCREASE THE GAS FLOW RATE TO PROVIDE A RATE |
| | OF HEAT RELEASE BY THE BURNER EQUAL TO THE FINAL HEAT |
| | OUTPUT FOR A 10-MINUTE PERIOD. THIS RATE SHALL BE 150 |
| | KW ? 5 KW. |
| | (D)CONTINUE THE EXPOSURE AT THAT SAME LEVEL FOR |
| | 10 MINUTES ? 10 SECONDS. |
| | (4)PROVIDE VISUAL DOCUMENTATION IN ACCORDANCE |
| | WITH 7.1.4. |
| | (5)PROVIDE A VOICE OR WRITTEN RECORD OF THE FIRE, |
| | WHICH WILL PROVIDE THE TIMES OF ALL SIGNIFICANT EVENTS, |
| | SUCH AS TIMES OF IGNITION, ESCAPE OF FLAMES THROUGH THE |
| | DOORWAY, AND FLASHOVER. |
| | (6)SHUT OFF THE IGNITION BURNER 15 MINUTES AFTER |
| | START OF THE TEST, AND TERMINATE THE TEST AT THAT TIME |
| | UNLESS SAFETY CONSIDERATIONS DICTATE AN EARLIER |
| | TERMINATION. |
| | (7)DOCUMENT DAMAGE AFTER THE TEST, USING WORDS, |
| | PICTURES, AND DRAWINGS. |
| | |
| | |
| | METHOD B: |
| | 1.4.1 THE SAMPLE SHALL BE TESTED BY USING A CORNER TEST |
| | EXPOSURE WITH THE SPECIMENS MOUNTED ON THREE FULLY |
| | LINED WALLS OF THE TEST COMPARTMENT (METHOD B). |
| | 1.4.1.1 THESE TEST METHODS SHALL USE A GAS BURNER TO |
| | PRODUCE A DIFFUSION FLAME TO EXPOSE THE WALLS IN THE |
| | CORNER OF A ROOM 2.4 M3.7 M2.4 M (8 FT12 FT8 |
| | FT). |
| | 1.4.1.2 THE BURNER SHALL PRODUCE A PRESCRIBED RATE OF |
| | HEAT OUTPUT OF 40 KW FOR 5 MINUTES FOLLOWED BY 150 KW |
| | FOR 10 MINUTES, FOR A TOTAL EXPOSURE PERIOD OF 15 |
| | MINUTES. |
| | 1.4.1.3 THE CONTRIBUTION OF THE TEXTILE WALL COVERING |
| | TO FIRE GROWTH SHALL BE MEASURED BY CONSTANT MONITORING |
| | OF THE INCIDENT HEAT FLUX ON THE CENTER OF THE FLOOR, |
| | THE TEMPERATURE OF THE GASES IN THE UPPER PART OF THE |
| | ROOM, THE RATE OF HEAT RELEASE, THE SMOKE RELEASE, AND |
| | THE TIME TO FLASHOVER. |
| | 1.4.1.4 THE TEST SHALL BE CONDUCTED WHILE PROVIDING |
| | NATURAL VENTILATION TO THE ROOM, THROUGH A SINGLE |
| | DOORWAY OF 0.8 M2.0 M (30 IN.80 IN.). |
| | 1.4.1.5 THE COMBUSTION PRODUCTS SHALL BE COLLECTED IN A |
| | HOOD FEEDING INTO A CHAMBER THAT IS CONNECTED TO AN |
| | EXHAUST DUCT IN WHICH MEASUREMENTS OF THE GAS VELOCITY, |
| | TEMPERATURE, AND CONCENTRATIONS OF SELECTED GASES ARE |
| | MADE. |
| | 1.4.2 FLASHOVER SHALL BE CONSIDERED TO HAVE OCCURRED |
| | WHEN ANY TWO OF THE FOLLOWING CONDITIONS HAVE BEEN |
| | ATTAINED: |
| | (1)THE HEAT RELEASE RATE EXCEEDS 1 MW. |
| | (2)THE HEAT FLUX AT FLOOR EXCEEDS 20 KW/M2. |
| | (3)THE AVERAGE UPPER LAYER TEMPERATURE EXCEEDS |
| | 600?C (1112?F). |
| | (4)FLAMES EXIT THE DOORWAY. |
| | (5)AUTOIGNITION OF PAPER TARGET ON FLOOR OCCURS. |
| | |
| | |
| | TEXTILE WALL COVERINGS. TEXTILE WALL COVERINGS SHALL |
| | HAVE A CLASS A FLAME SPREAD INDEX IN ACCORDANCE WITH |
| | ASTM E 84 AND BE PROTECTED BY AUTOMATIC SPRINKLERS |
| | INSTALLED IN ACCORDANCE WITH SECTION 903.3.1.1 OR |
| | 903.3.1.2 OR THE COVERING SHALL MEET THE CRITERIA OF |
| | SECTION 803.6.1.1 OR 803.6.1.2 WHEN TESTED IN THE |
| | MANNER INTENDED FOR USE IN ACCORDANCE WITH NFPA 265 |
| | USING THE PRODUCT MOUNTING SYSTEM, INCLUDING ADHESIVE. |
| | |
| | 15) COMPLIED. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |
| | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO |
| | THE PUBLIC UPON REQUEST. YOUR E-MAILCOMMUNICATIONS ARE |
| | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
| | |
| | |