| 2007-09-01 14:02:33 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. INTERIOR DESIGN DOCUMENTS PREPARED BY A REGISTERED |
| | INTERIOR DESIGNER SHALL CONTAIN A STATEMENT THAT THE |
| | DOCUMENT IS NOT AN ARCHITECTURAL OR ENGINEERING STUDY, |
| | DRAWING, SPECIFICATION OR DESIGN AND IS NOT TO BE USED |
| | FOR CONSTRUCTION OF ANY LOAD BEARING COLUMNS, |
| | LOAD-BEARING FRAMING OR WALLS OF STRUCTIURES, OR |
| | ISSUANCE OF ANY BUILDING PERMIT, EXCEPT AS OTHERWISE |
| | PROVIDED BY LAW.FS 481.2131. PLEASE SHOW COMPLIANCE. |
| | |
| | 2. INDICATE WHICH CODES PLANS WERE DESIGNED TO AND |
| | OCCUPANCY CLASSIFICATION ON THE PLANS. SECTIONS 106.1.1 |
| | & 106.3.5.1.1(2)(7). |
| | |
| | 3. ALL SHEETS REQUIRE THE ADDRESS AND TENANT SPACE IN |
| | THE TITLE BLOCK PER SECTION 106.1.1. FLORIDA |
| | ADMINISTRATIVE CODE. AFTER SUITE NUMBER IS ASSIGNED |
| | PLEASE INDICATE ADDRESS & SUITE NUMBER IN TITLE BLOCK. |
| | |
| | 4. THE BASE BUILDING HAS NOT RECIEVED A CERTIFICATE OF |
| | OCCUPANCY AT THIS TIME. THE BUILDING OFFICIAL HAS |
| | DETERMINED THAT ALL PLANS SHALL BE REVIEWED BY THE |
| | DESIGNERS OF THE BASE BUILDING FOR ALL TENANT |
| | BUILDOUTS. PLANS SHALL BE STAMPED AS REVIEWED BY BASE |
| | BUILDING DESIGN TEAM PRIOR TO RESUBMITTING FOR REVIEW |
| | AT THE CITY WPB. (SEE COMMENTS BY MECHANICAL REVIEW, |
| | (1), ELECTRICAL REVIEW, (4), AND BUILDING (2)).-- |
| | SINCE THE BUILD-OUT G.C. IS A DIFFERENT COMPANY FROM |
| | THE BASE BUILDING G.C., A LETTER IS REQUIRED FROM THE |
| | DEVELOPER, SIGNED BY THE BASE BUILD G.C. AND THE SHELL |
| | G.C., STATING THAT ALL PARTIES UNDERSTAND THAT NO |
| | DISPUTE OVER WORK SCOPE OR RESPONSIBILITY CAN COME |
| | BEFORE THE REQUIREMENT FOR COMPLIANCE WITH FLORIDA |
| | BUILDING CODE. |
| | |
| | 5. SHTS ID-1 THRU ID-15 SHALL HAVE THE SIGNATURE AND |
| | DATE THE SEAL AND SIGNATURE WERE AFFIXED TO PLANS. IT |
| | APPEARS THAT INITIALS HAVE BEEN USED IN PLACE OF |
| | SIGNATURE WHEN SEALING THE PLANS. IF THIS INDEED THE |
| | LEGAL SIGNATURE OF THE INTERIOR DESIGNER, THEN A |
| | SIGNED, SEALED, NOTORIZED LETTER INDICATING THE |
| | INTERIOR DESIGNER'S LEGAL SIGNATURE SHALL BE SUBMITTED |
| | FOR OUR FILES. FAC 61G1-16.003,61G1-16.004(5) & |
| | 481.2055. |
| | |
| | 6. SHT ID-1A IF TOILET STALLS ARE PROVIDED, THAN AT |
| | LEAST ONE SHALL BE A STANDARD TOILET STALL COMPLYING |
| | WITH SECTION 11-4.17 EXCEPTION: NEW CONSTRUCTION(1) AND |
| | SHALL CONTAIN AN ACCESSIBLE LAVATORY WITH IT. (SEE FIG. |
| | 11-30(E). |
| | |
| | 7. SHT ID-2 WHITE OUT OR HAND WRITTEN CHANGES ARE NOT |
| | APPROVED ON SIGNED, SEALED PLANS. SECTION 106.1.3. |
| | |
| | 8. SHT ID-3 FLOOR FINISH SCHEDULE. MORE INFORMATION |
| | REQUIRED. PER SECTION 1210.1 THE FLOOR SHALL HAVE A |
| | "SMOOTH, HARD, NONABSORBENT" SURFACE. PLEASE SUBMIT THE |
| | MANUF. SPECIFICATION FOR THE MEDIUM SATURNIA INDICATED |
| | ON THE SCHEDULE TO VERIFY COMPLIANCE. SECTION 106.1.2. |
| | |
| | 9. SHT ID-3B WALLS WITHIN 2FT OF THE WATER CLOSETS |
| | SHALL HAVE A "SMOOTH, HARD, NONABSORBENT" SURFACE UP TO |
| | 4FT ABOVE THE FLOOR. PLEASE INDICATE COMPLIANCE WITH |
| | SECTION 1210.2. |
| | |
| | 10. SUBMIT A DETAIL FOR THE TOILET ROOM FIXTURES |
| | SHOWING COMPLIANCE WITH SECTIONS 11-4.16, 11-4.17, |
| | 11-4.19 & 11-4.21 WITH ALL SUBSECTIONS. SHOW THE CLEAR |
| | FLOOR SPACE FOR ALL ACCESSIBLE FIXTURES ON THE FLOOR |
| | PLAN AS WELL AS THE TURNING AREA IN BOTH TOILET ROOMS. |
| | SUBMIT ELEVATIONS TO SHOW COMPLIANCE FOR ALL OTHER |
| | REQUIREMENTS. |
| | |
| | 11. PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. |
| | PLEASE SHOW THE LOCATION AND SUBMIT A DETAIL SHOWING |
| | COMPLIANCE WITH SECTION 11-5.15 AND ALL SUBSECTIONS AS |
| | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 12. THE SINK IN THE BREAKROOM, (ROOM #112), SHALL BE |
| | ACCESSIBLE. PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE |
| | WITH SECTION 11-4.24 AND ALL SUBSECTIONS. ELEVATION |
| | A1/ID-14 INDICATES CABINET DOORS. THE DOORS ARE NOT |
| | APPROVED IN THE CLEAR FLOOR SPACE AND SHALL BE DELETED |
| | FROM DETAIL. FORWARD APPROACH IS REQUIRED. SHOW CLEAR |
| | FLOOR SPACE ON THE FLOOR PLAN AND OTHER REQUIREMENTS ON |
| | THE ELEVATION. (NOTE: THE GARBAGE DISPOSAL SHALL BE ADA |
| | APPROVED. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS |
| | SHOWING APPROVAL). |
| | |
| | 13. WHEN RESUBMITTING PLANS, PLEASE INDICATE THE |
| | REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | SUBMIT ONE COPY OF SHEETS REMOVED FOR COMPARISON. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 14. SHT P31 SHOWS NO PLUMBING INFORMATION. PLEASE |
| | CLARIFY. THERE SEEMS TO BE ELECTRIC OR MECHANICAL |
| | INFORMATION THAT SHOULD BE TRANSFERED TO THE RESPECTIVE |
| | ELECTRIC OR MECHANICAL SHEETS. SECTION 106.1.1. |
| | |