Plan Review Notes
Plan Review Notes For Permit 07070352
Permit Number 07070352
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-09-14 11:11:44*****DENIED*****
  
 (UNLESS OTHERWISE NOTED, THIS TENANT SPACE IMPROVEMENT
 SHALL BE CLASSIFIED AS A NEW BUSINESS OCCUPANCY)
  
  
 01.THE NUMERICAL ADDRESS OF THE PROJECT SITE
 (INCLUDING THE SUITE NUMBER) SHALL BE IN THE TITLE
 BLOCK OF EACH SUBMITTED PLAN SHEET.PROJECT SITE
 LOCATION NEEDED ON COVER PAGE OF HYDRAULIC CALCULATION
 SHEETS ALSO.
  
 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT
 OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 05.THE PROJECTED SCOPE OF WORK SHALL NOT INTERFERE OR
 HINDER ACCESS TO OR EGRESS FROM THE TENANT SPACE, OTHER
 TENANT SPACES ON THE TENTH FLOOR, OR THE BUILDING.
  
 06.PROVIDE OCCUPANT LOAD AS IN NUMBER OF PERSONS FOR
 WHOM MEANS OF EGRESS ARE REQUIRED BASED UPON THE
 CHARACTERISTIC OF THE USE OF THE TENANT SPACE.
  
 07.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR
 THE EXITS, AISLE CORRIDORS, AND ALL OTHER SPACES IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 08.DOORS THAT LEAD INTO THE EXIT CORRIDOR SHALL BE
 SELF CLOSING OR AUTOMATIC CLOSING.ALL FIRE RATED
 DOORS TO COMPLY WITH NFPA 80.
  
 09.PROVIDE A LIFE SAFETY PLAN SHEET WHICH ILLUSTATES
 TRAVEL DISTANCE TO THE EXITS.EXIT LIGHTS, EMERGENCY
 LIGHTS, AND LOCATION OF FIRE EXTINGUISHER MAY ALSO BE
 INCLUDED ON THIS PLAN SHEET.
  
 10.ON SHEET E2.1, EXPLAIN RATIONALE FOR EXIT LIGHTS
 DIRECTING PATRONS IN CORRIDOR 123 AND 125.
  
 11. SHOW THE LOCATION OF THE 2A:10BC FIRE
 EXINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL
 DISTANCE.
  
 12.NO EXIT LIGHTS OR EMERGENCY LIGHTING SHOWN ON SHEET
 ID-6. CORRELATE WITH SHEET E3.1.
  
 13. THE 2002 EDITION OF NFPA 72 SHALL BE REFERENCED.
 (SEE NOTE #2 AND #12 ON SHEET FA0.1.
  
 14.AMEND NOTE #17 ON SHEET FA0.1 TO REFLECT LOCAL
 REQUIREMENT:DELETE "SUPERVISORY SIGNAL ONLY"INSERT
 "GENERAL FIRE ALARM".
  
 15.EXPLAIN THE DIFFERENCE/RATIONALE IN FIRE ALARM
 DEVICES LOCATED IN THE TWO CONFERENCE ROOMS (108 AND
 117) ONE BEING COMBINATION AUDIBLE/VISUAL AND THE OTHER
 ONLY VISUAL.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDIACTING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  