| 2007-09-14 11:11:44 | *****DENIED***** |
| | |
| | (UNLESS OTHERWISE NOTED, THIS TENANT SPACE IMPROVEMENT |
| | SHALL BE CLASSIFIED AS A NEW BUSINESS OCCUPANCY) |
| | |
| | |
| | 01.THE NUMERICAL ADDRESS OF THE PROJECT SITE |
| | (INCLUDING THE SUITE NUMBER) SHALL BE IN THE TITLE |
| | BLOCK OF EACH SUBMITTED PLAN SHEET.PROJECT SITE |
| | LOCATION NEEDED ON COVER PAGE OF HYDRAULIC CALCULATION |
| | SHEETS ALSO. |
| | |
| | 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT |
| | OR MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 05.THE PROJECTED SCOPE OF WORK SHALL NOT INTERFERE OR |
| | HINDER ACCESS TO OR EGRESS FROM THE TENANT SPACE, OTHER |
| | TENANT SPACES ON THE TENTH FLOOR, OR THE BUILDING. |
| | |
| | 06.PROVIDE OCCUPANT LOAD AS IN NUMBER OF PERSONS FOR |
| | WHOM MEANS OF EGRESS ARE REQUIRED BASED UPON THE |
| | CHARACTERISTIC OF THE USE OF THE TENANT SPACE. |
| | |
| | 07.SPECIFY THE WALL AND CEILING FINISH MATERIAL FOR |
| | THE EXITS, AISLE CORRIDORS, AND ALL OTHER SPACES IN |
| | TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 08.DOORS THAT LEAD INTO THE EXIT CORRIDOR SHALL BE |
| | SELF CLOSING OR AUTOMATIC CLOSING.ALL FIRE RATED |
| | DOORS TO COMPLY WITH NFPA 80. |
| | |
| | 09.PROVIDE A LIFE SAFETY PLAN SHEET WHICH ILLUSTATES |
| | TRAVEL DISTANCE TO THE EXITS.EXIT LIGHTS, EMERGENCY |
| | LIGHTS, AND LOCATION OF FIRE EXTINGUISHER MAY ALSO BE |
| | INCLUDED ON THIS PLAN SHEET. |
| | |
| | 10.ON SHEET E2.1, EXPLAIN RATIONALE FOR EXIT LIGHTS |
| | DIRECTING PATRONS IN CORRIDOR 123 AND 125. |
| | |
| | 11. SHOW THE LOCATION OF THE 2A:10BC FIRE |
| | EXINGUISHER(S) WHICH SATISFIES THE 75' TRAVEL |
| | DISTANCE. |
| | |
| | 12.NO EXIT LIGHTS OR EMERGENCY LIGHTING SHOWN ON SHEET |
| | ID-6. CORRELATE WITH SHEET E3.1. |
| | |
| | 13. THE 2002 EDITION OF NFPA 72 SHALL BE REFERENCED. |
| | (SEE NOTE #2 AND #12 ON SHEET FA0.1. |
| | |
| | 14.AMEND NOTE #17 ON SHEET FA0.1 TO REFLECT LOCAL |
| | REQUIREMENT:DELETE "SUPERVISORY SIGNAL ONLY"INSERT |
| | "GENERAL FIRE ALARM". |
| | |
| | 15.EXPLAIN THE DIFFERENCE/RATIONALE IN FIRE ALARM |
| | DEVICES LOCATED IN THE TWO CONFERENCE ROOMS (108 AND |
| | 117) ONE BEING COMBINATION AUDIBLE/VISUAL AND THE OTHER |
| | ONLY VISUAL. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDIACTING WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |