Plan Review Notes
Plan Review Notes For Permit 07070352
Permit Number 07070352
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-06 12:45:17 
  
 ** UNSAT **
  
  
 1) NOTE:PLEASE SEE ONCE THE ADDRESSING REVIEWER HAS
 ASSIGNED A SUITE/UNIT NUMBER, PLEASE BE SURE TO PLACE
 DESIGNATION ON TITLE BLOCKS.
 FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE: PLEASE SEE THE ID PLANS ARE REQUIRED TO BE
 DATED WHEN SIGNING AND SEALING DOCUMENTS.
 PLEASE SEE FS 481.221.
  
 3) NOTE: PLEASE KNOW THAT ALL PLANS SHALL BE SIGNED,
 WITH SIGNATURES AS ON FILE AND RECORD WITH THE CITY OF
 WEST PALM BEACH AND THIS JURISDICTION.
 FS 481.221/471.025
  
 4) NOTE: PLEASE SEE COMMENTS WHICH WERE MADE BY THE
 MECHANICAL REVIEWER ALSO WITH RESPECT TO THE BASE
 BUILDING DESIGN TEAM BEING REQUIRED TO REVIEW THE PLANS
 AS THIS BUILDING DOES NOT CONTAIN A CO AND ALL WORK
 BEING DONE ON A BUILDING WHICH IS UNDER THE
 RESPONSIBILITY OF ANOTHER DESIGN TEAM MUST BE
 REVIEWED.
 FBC 106.1.2
  
 5) NOTE: PLEASE BE SURE TO STAMP AS REVIEWED. PLEASE BE
 KNOW ANY ASSUMPTIONS MADE TO THE BASE BUILDING FOR LOAD
 CALCULATIONS AND ENERGY CALCULATIONS WILL BE REQUIRED
 TO BE REVISED ON BASE BUILDING AND INFORMATION SHOULD
 BE MAD AVAILABLE TO THE BASE BUILDING DESIGN TEAM.
 FBC 106.1.2, 106.3.5.1.2
 NEC 220/408/215 ETC
 FBC CHAPTER 13 AS NOTED ON MECHANICAL REVIEW.
  
 6) NOTE: PLEASE VERIFY THE CORRIDOR BEING UNDER THE
 SCOPE OF WORK FOR THIS PERMIT OR NOT. PLEASE ALSO
 VERIFY WITH THE BASE BUILDING DESIGN TEAM AND OWNER FOR
 POSSIBLE OWNER REQUIRED ELECTRICAL ROOM/AREA. PLEASE
 SEE THAT THE TENANT/OCCUPANT DOES NOT CONTAIN ACCESS TO
 OVER CURRENT PROTECTION DEVICES AS REQUIRED. PLEASE SEE
 THIS WOULD AFFECT THE LOCATIONS AS THE BASE BUILDING
 HAD CONDITIONS DUE TO CONSTRUCTION BOARD OF APPEALS
 APPLICATION AND ITEMS GRANTED.
 PLEASE CORRELATE.
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
 240.24D.
  
 7) NOTE: PLEASE BE SURE TO CORRELATE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. PLEASE SEE DESIGNATIONS AS
 PROVIDED ON THE ID PLANS ARE NOT THE SAME ON MEP.
 PLEASE SEE THE ELECTRICAL PLANS CONTAIN THE SAME
 NUMERICAL DESIGNATION USED IN MORE THAN ONE LOCATION.
 PLEASE SEE FOR EXAMPLE: ROOM/AREA 103.
 PLEASE ALSO SEE THE STORAGE ROOM WHICH IS BEING NOTED
 ON ALL PLANS WHEN IN FACTTHIS IS A SERVER. AND
 POSSIBLE IT ROOM.
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE THE ROOM NOTED AS STORAGE IS SHOWN
 WITH MULTIPLE CIRCUITS FOR WHAT APPEARS WILL BE AN IT
 ROOM.
 PLEASE PROVIDE MORE INFORMATION ON THIS ROOM AND ALL
 EQUIPMENT INTENDED TO BE INSTALLED.
 THIS ROOM IS BEING FED WITH A SEPARATE AC SYSTEM.
 PLEASE SEE 645.10,645.4, 645.5 ETC.
  
 9) NOTE: PLEASE SEE FBC CHAPTER 13 FOR ENERGY CODE
 COMPLIANCE NEEDS TO BE MET.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE MISSING CONTROLS FOR SEPARATE SPACES IN MANY
 ROOMS.
 PLEASE SEE THAT NO ENERGY CALCULATIONS/PERFORMANCE
 CALCULATIONS WERE SUBMITTED FOR REVIEW. 13-415.1.A,
 13-415.B, 13-415.1.C, 13-415.2.
 PLEASE CORRELATE FIXTURE LEGEND FOR ALL FIXTURES ON
 PLANS WITH CALCULATIONS FOR TYPES, WATTAGE, METHOD OF
 CONTROL ETC.
 PLEASE PROVIDE SCHEDULING FOR PROPOSED SYSTEM. PLEASE
 KNOW A BASE TIME SHOULD BE SHOWN.
 PLEASE INDICATE LOCATIONS AS REQUIRED FOR ALL OVER RIDE
 DEVICES SO THE OCCUPANT CAN VISUALLY SEE THE LIGHTING
 WHICH IS BEING OVER RIDDEN.
 PLEASE PROVIDE ALL MAXIMUM TIMES ON OVER RIDES AND OVER
 RIDE DEVICES.
 PLEASE SUBMIT THE MANUFACTURES/SPEC CUT SHEETS ON THE
 PROPOSED SYSTEM. PLEASE BE SURE ALL DEVICES/SYSTEM
 CONTAINS A LISTING FROM A NATIONALLY RECOGNIZED TESTING
 LABORATORY. (NRTL)
 110.3, 90.7.
 PLEASE BE SURE ALL DOCUMENTS ARE SIGNED, DATED AND
 SEALED AS REQUIRED PER 13-103.1.1.1 AND OWNER/AGENT IS
 SIGNED.
  
 10) NOTE: PLEASE SEE THE FIXTURE LEGEND AS PROVIDED ON
 THE ID PLANS NEEDS COORDINATION WITH THE LEGEND ON THE
 ELECTRICAL PLANS.
 FBC 106.1.2
  
 11) NOTE: PLEASE SEE THE PANEL 10HA SHOWS ON THE RISER
 AS CONTAINING SOME SORT OF FEED COMING FROM THIS PANEL
 TO PANEL 10LA, YET THIS DESIGNATION DOES NOT CORRELATE
 WITH EITHER PANEL OR OTHER INFORMATION.
 PLEASE SEE THE RISER WHICH SHOWS 10TA-1L?
 FBC 106.1.2 FOR COORDINATION.
  
  
 12) NOTE: PLEASE SEE THE TRANSFORMER SCHEDULE INDICATE
 THE FEEDERS ON THE SECONDARY SIDE OF THE TRANSFORMER AS
 4/0 WHICH ARE NOT SUFFICIENT. PLEASE SEE 310.16, 240.4,
 240.21 AS THE TAPPED CONDUCTORS ARE REQUIRED TO
 TERMINATE IN OVER CURRENT PROTECTION WHICH LIMITS THE
 LOAD ON THE TAPPED CONDUCTOR.
  
 13) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION ON THE
 PANEL 10LA IS SHOWN AS 250AMPS WHICH IS TOO LARGE FOR
 THE CONDUCTORS AS NOTED ABOVE IN NOTE #13, HOWEVER THE
 PANEL MENTIONS THIS CONTAINS FEED-THRU LUGS TO FEED
 PANEL 10LB, YET PANEL 10LB IS A 225AMP RATED PANEL.
 THIS DOES NOT MEET THE NEC AS THE RATING OF THE PANEL
 MUST MEET THE MINIMUM RATING FOR THE OCP WHICH IS
 250AMPS AS SHOWN ON PANEL 10LA MAIN.
 240.4, 310.16, 408.36, 240.30, 240.20 ETC.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  