| Date |
Text |
| 2007-08-06 12:45:17 | |
| | |
| | ** UNSAT ** |
| | |
| | |
| | 1) NOTE:PLEASE SEE ONCE THE ADDRESSING REVIEWER HAS |
| | ASSIGNED A SUITE/UNIT NUMBER, PLEASE BE SURE TO PLACE |
| | DESIGNATION ON TITLE BLOCKS. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 2) NOTE: PLEASE SEE THE ID PLANS ARE REQUIRED TO BE |
| | DATED WHEN SIGNING AND SEALING DOCUMENTS. |
| | PLEASE SEE FS 481.221. |
| | |
| | 3) NOTE: PLEASE KNOW THAT ALL PLANS SHALL BE SIGNED, |
| | WITH SIGNATURES AS ON FILE AND RECORD WITH THE CITY OF |
| | WEST PALM BEACH AND THIS JURISDICTION. |
| | FS 481.221/471.025 |
| | |
| | 4) NOTE: PLEASE SEE COMMENTS WHICH WERE MADE BY THE |
| | MECHANICAL REVIEWER ALSO WITH RESPECT TO THE BASE |
| | BUILDING DESIGN TEAM BEING REQUIRED TO REVIEW THE PLANS |
| | AS THIS BUILDING DOES NOT CONTAIN A CO AND ALL WORK |
| | BEING DONE ON A BUILDING WHICH IS UNDER THE |
| | RESPONSIBILITY OF ANOTHER DESIGN TEAM MUST BE |
| | REVIEWED. |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE BE SURE TO STAMP AS REVIEWED. PLEASE BE |
| | KNOW ANY ASSUMPTIONS MADE TO THE BASE BUILDING FOR LOAD |
| | CALCULATIONS AND ENERGY CALCULATIONS WILL BE REQUIRED |
| | TO BE REVISED ON BASE BUILDING AND INFORMATION SHOULD |
| | BE MAD AVAILABLE TO THE BASE BUILDING DESIGN TEAM. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | NEC 220/408/215 ETC |
| | FBC CHAPTER 13 AS NOTED ON MECHANICAL REVIEW. |
| | |
| | 6) NOTE: PLEASE VERIFY THE CORRIDOR BEING UNDER THE |
| | SCOPE OF WORK FOR THIS PERMIT OR NOT. PLEASE ALSO |
| | VERIFY WITH THE BASE BUILDING DESIGN TEAM AND OWNER FOR |
| | POSSIBLE OWNER REQUIRED ELECTRICAL ROOM/AREA. PLEASE |
| | SEE THAT THE TENANT/OCCUPANT DOES NOT CONTAIN ACCESS TO |
| | OVER CURRENT PROTECTION DEVICES AS REQUIRED. PLEASE SEE |
| | THIS WOULD AFFECT THE LOCATIONS AS THE BASE BUILDING |
| | HAD CONDITIONS DUE TO CONSTRUCTION BOARD OF APPEALS |
| | APPLICATION AND ITEMS GRANTED. |
| | PLEASE CORRELATE. |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | 240.24D. |
| | |
| | 7) NOTE: PLEASE BE SURE TO CORRELATE ALL ROOM AND AREA |
| | DESIGNATIONS ON PLANS. PLEASE SEE DESIGNATIONS AS |
| | PROVIDED ON THE ID PLANS ARE NOT THE SAME ON MEP. |
| | PLEASE SEE THE ELECTRICAL PLANS CONTAIN THE SAME |
| | NUMERICAL DESIGNATION USED IN MORE THAN ONE LOCATION. |
| | PLEASE SEE FOR EXAMPLE: ROOM/AREA 103. |
| | PLEASE ALSO SEE THE STORAGE ROOM WHICH IS BEING NOTED |
| | ON ALL PLANS WHEN IN FACTTHIS IS A SERVER. AND |
| | POSSIBLE IT ROOM. |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE THE ROOM NOTED AS STORAGE IS SHOWN |
| | WITH MULTIPLE CIRCUITS FOR WHAT APPEARS WILL BE AN IT |
| | ROOM. |
| | PLEASE PROVIDE MORE INFORMATION ON THIS ROOM AND ALL |
| | EQUIPMENT INTENDED TO BE INSTALLED. |
| | THIS ROOM IS BEING FED WITH A SEPARATE AC SYSTEM. |
| | PLEASE SEE 645.10,645.4, 645.5 ETC. |
| | |
| | 9) NOTE: PLEASE SEE FBC CHAPTER 13 FOR ENERGY CODE |
| | COMPLIANCE NEEDS TO BE MET. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE MISSING CONTROLS FOR SEPARATE SPACES IN MANY |
| | ROOMS. |
| | PLEASE SEE THAT NO ENERGY CALCULATIONS/PERFORMANCE |
| | CALCULATIONS WERE SUBMITTED FOR REVIEW. 13-415.1.A, |
| | 13-415.B, 13-415.1.C, 13-415.2. |
| | PLEASE CORRELATE FIXTURE LEGEND FOR ALL FIXTURES ON |
| | PLANS WITH CALCULATIONS FOR TYPES, WATTAGE, METHOD OF |
| | CONTROL ETC. |
| | PLEASE PROVIDE SCHEDULING FOR PROPOSED SYSTEM. PLEASE |
| | KNOW A BASE TIME SHOULD BE SHOWN. |
| | PLEASE INDICATE LOCATIONS AS REQUIRED FOR ALL OVER RIDE |
| | DEVICES SO THE OCCUPANT CAN VISUALLY SEE THE LIGHTING |
| | WHICH IS BEING OVER RIDDEN. |
| | PLEASE PROVIDE ALL MAXIMUM TIMES ON OVER RIDES AND OVER |
| | RIDE DEVICES. |
| | PLEASE SUBMIT THE MANUFACTURES/SPEC CUT SHEETS ON THE |
| | PROPOSED SYSTEM. PLEASE BE SURE ALL DEVICES/SYSTEM |
| | CONTAINS A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY. (NRTL) |
| | 110.3, 90.7. |
| | PLEASE BE SURE ALL DOCUMENTS ARE SIGNED, DATED AND |
| | SEALED AS REQUIRED PER 13-103.1.1.1 AND OWNER/AGENT IS |
| | SIGNED. |
| | |
| | 10) NOTE: PLEASE SEE THE FIXTURE LEGEND AS PROVIDED ON |
| | THE ID PLANS NEEDS COORDINATION WITH THE LEGEND ON THE |
| | ELECTRICAL PLANS. |
| | FBC 106.1.2 |
| | |
| | 11) NOTE: PLEASE SEE THE PANEL 10HA SHOWS ON THE RISER |
| | AS CONTAINING SOME SORT OF FEED COMING FROM THIS PANEL |
| | TO PANEL 10LA, YET THIS DESIGNATION DOES NOT CORRELATE |
| | WITH EITHER PANEL OR OTHER INFORMATION. |
| | PLEASE SEE THE RISER WHICH SHOWS 10TA-1L? |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | |
| | 12) NOTE: PLEASE SEE THE TRANSFORMER SCHEDULE INDICATE |
| | THE FEEDERS ON THE SECONDARY SIDE OF THE TRANSFORMER AS |
| | 4/0 WHICH ARE NOT SUFFICIENT. PLEASE SEE 310.16, 240.4, |
| | 240.21 AS THE TAPPED CONDUCTORS ARE REQUIRED TO |
| | TERMINATE IN OVER CURRENT PROTECTION WHICH LIMITS THE |
| | LOAD ON THE TAPPED CONDUCTOR. |
| | |
| | 13) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION ON THE |
| | PANEL 10LA IS SHOWN AS 250AMPS WHICH IS TOO LARGE FOR |
| | THE CONDUCTORS AS NOTED ABOVE IN NOTE #13, HOWEVER THE |
| | PANEL MENTIONS THIS CONTAINS FEED-THRU LUGS TO FEED |
| | PANEL 10LB, YET PANEL 10LB IS A 225AMP RATED PANEL. |
| | THIS DOES NOT MEET THE NEC AS THE RATING OF THE PANEL |
| | MUST MEET THE MINIMUM RATING FOR THE OCP WHICH IS |
| | 250AMPS AS SHOWN ON PANEL 10LA MAIN. |
| | 240.4, 310.16, 408.36, 240.30, 240.20 ETC. |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| | AT THIS TIME. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |