Plan Review Notes
Plan Review Notes For Permit 07070352
Permit Number 07070352
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-15 21:18:02GOODRICH LLC CITY PL. TOWER SUITE # 1000
 BUILDING PLAN REVIEW
 PERMIT: 07070352
 ADD: 525 OKEECHOBEE BLVD # 1000
 CONT: DAVIS GENERAL CONTRACTING CORP
 TEL: (561) 820-1400
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) BASED ON THE DETERMINATION OF THE BUILDING OFFICIAL,
 APPLICATION FOR TENANT IMPROVEMENT PRIOR TO C.O. WILL
 REQUIRE SHOP DRAWING REVIEW BY THE BASE BUILDING DESIGN
 TEAM, THE DESIGNER OF RECORD. PLEASE HAVE THE BASE
 BUILDING DESIGNERS OF RECORD REVIEW YOUR PLANS AND IF
 FOUND SUFFICIENT AFFIX THEIR SHOP DRAWING STAMP ON YOUR
 DOCUMENTS.
 NOTE ALSO THAT A TENANT CAN NOT ACHIEVE A CERTIFICATE
 OF OCCUPANCY BEFORE THE SHELL BUILDING HAS RECEIVED
 THEIR CERTIFICATE OF COMPLETION. FBC 106.1.2*
 ADMINISTRATIVE CODE.
  
 3)PLEASE NOTE AT THIS TIME THIS BUILDING HAS NOT
 RECEIVED A CERTIFICATE OF COMPLETION, AND THE ENERGY
 CALCULATIONS ARE BASED ON A SHELL BUILDING AND ARE
 BASED ON 13-101.1.6. UNLESS THE BUILDING IS COMPLETED
 AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL CODE
 COMPLIANCE SUBMITTAL, REVISED CODE SUBMITTALS USING
 METHOD A, B OR C SHALL BE SUBMITTED WHEN THE COMPLETION
 OF THE BUILDING (OR PART) OF A BUILDING IS PERMITTED.
  
 4)PLEASE CONTACT LILI URSA AT 822-1239 FOR SUITE
 NUMBER ASSIGNMENT PLEASE PROVIDE THIS INFORMATION IN
 THE TITLE BLOCK, SEE FLORIDA ADMINISTRATIVE CODES
 61G1-15.004 AND 61G15-23.002.
  
 5) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY, TO BE LISTED IN THE PLAN:
 A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
  
 6A) SHEET ID-1A WALL TYPE "A" IS INDICATED AS AN
 EXISTING CMU DEMISING WALL, PLEASE COORDINATE WITH THE
 BASE BUILDING DESIGNER. ADDITIONAL INFORMATION
 REQUIRED, FBC ADMINISTRATIVE CODE 106.1.2*. THE SHELL
 BUILDING PLAN SHEET A1.06 & A2.06 BOTH INDICATE THIS
 WALL TO BE A DRYWALL AND METAL STUD WALL.
  
 6B) SHEET ID-1A ALSO INDICATES THE TENANT SEPERATION
 WALLS TO BE EXISTING CMU DEMISSING WALL.THE BASE
 SHELL BUILDING PLAN DOESN'T INDICATE ANY SUCH WALL.
 708.1(5) REQUIRES FIRE PARTITIONS BETWEEN TENANTS.
 708.3 FIRE RESISTANCE RATING WILL REQUIRE A 1-HOUR FIRE
 RATING.
 FLORIDA STATE STATUTE 481.2131 INTERIOR DESIGNER CAN
 NOT DESIGN PLANS OR PORTIONS OF THAT EFFECT FIRE-RATED
 SEPERATIONS BETWEEN INTERIOR SPACES, THE FIRM IS
 WORKING OUT OF THE SCOPE OF THEIR LOCENSE. SEE
 ATTACHMENT 481.2131.
  
 7) SHEET ID-1A DOOR# 002IS INDICATED TO BE A SINGLE
 2'-8" DOOR CUT IN HALF, CLOSETS THAT AREDEEPER THAN
 2'-0" WILL REQUIRE A MINIMUM CLEAR WIDE OF 32" WHEN THE
 DOOR OR DOORS ARE OPEN 90 DEGREES TO THE OPENING. SEE
 11-4.13.5
 11-4.13.5 CLEAR WIDTH.
 DOORWAYS SHALL HAVE A MINIMUM CLEAR OPENING OF 32
 INCHES (813 MM) WITH THE DOOR OPEN 90 DEGREES, MEASURED
 BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE STOP [SEE
 FIGURE 24 (A), FIGURE 24 (B), FIGURE 24 (C), AND FIGURE
 24 (D)]. OPENINGS MORE THAN 24 INCHES (610 MM) IN DEPTH
 SHALL COMPLY WITH SECTIONS 11-4.2.1 AND 11-4.3.3 [SEE
 FIGURE 24 (E)].
 EXCEPTION: DOORS NOT REQUIRING FULL USER PASSAGE, SUCH
 AS SHALLOW CLOSETS, MAY HAVE THE CLEAR OPENING REDUCED
 TO 20"MINIMUM.
  
 8) SHEET ID-1A DOORS 023 AND 024 ARE BOTH CLOSET DOORS
 THAT OPEN TO A CLOSET DEEPER THAN 24" REQUIRING A CLEAR
 32" OPENING.
 SEE 11-4.13.5 CLEAR WIDTH.
  
 9) DOORS 16-19 ARE INDICATED AS 28" DOORS THAT LEAD TO
 THE INDIVIDUAL WATER CLOSET STALLS.PLEASE SEE 11-4.13.5
 AND 11-4.17.5
 DOORS. TOLIET STALL DOORS INCLUDING DOOR HARDWARE,
 SHALL COMPLY WITH SECTION 11-4.13.. DOORS SHALL BE SELF
 CLOSING.
 11-4.17.3 EXCEPTION: NEW CONSTRUCTION.
 (1)THE STANDARD ACCESSIBLE RESTROOM STALL SHALL
 CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF
 SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30 (A) AND FIGURE 30 (E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
 (2)THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN
 THE CORNER, DIAGONAL TO THE DOOR.
  
 10) IN BOTH THE WOMEN'S AND MEN'S RESTROOMS THERE ARE
 NO HANDICAPPED STALLS. 11-4.1.3(11)TOILET FACILITIES.
 IF TOILET ROOMS ARE PROVIDED, THEN EACH PUBLIC AND
 COMMON USE TOILET ROOM SHALL COMPLY WITH SECTION
 11-4.22 .
 EXCEPTION: NEW CONSTRUCTION.
 (1)THE STANDARD ACCESSIBLE RESTROOM STALL SHALL
 CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF
 SUCH LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17
 INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL
 MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO
 OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION
 11-4.17 [SEE FIGURE 30 (A) AND FIGURE 30 (E)] AND TO
 COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH
 LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED
 FIXTURE COUNT FOR THE BUILDING.
 (2)THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN
 THE CORNER, DIAGONAL TO THE DOOR.
  
 11) SHEET ID-14 DETAIL A1 BREAK ROOM# 112 SINKS:
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE MOUNTED WITH
 THE COUNTER NO HIGHER THAN 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30"
 WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT
 LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM)
 COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN
 FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR
 FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL
 EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE
 SINK.
  
 12)SHEET ID-14 DETAIL A11 & A15 BOTH ARE OF RESTROOM
 VANITIES AND LAVATORIES.11-4.19.2 HEIGHT AND
 CLEARANCES.
 LAVATORIES SHALL BE MOUNTED WITH THE RIM OR COUNTER
 SURFACE NO HIGHER THAN 34 INCHES (865 MM) ABOVE THE
 FINISH FLOOR. PROVIDE A CLEARANCE OF AT LEAST 29 INCHES
 (735 MM) ABOVE THE FINISH FLOOR TO THE BOTTOM OF THE
 APRON. KNEE AND TOE CLEARANCE SHALL COMPLY WITH FIGURE
 31 .
  
 11-4.19.3 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE 30 INCHES BY 48 INCHES (760 MM BY
 1219 MM) COMPLYING WITH SECTION 11-4.2.4 SHALL BE
 PROVIDED IN FRONT OF A LAVATORY TO ALLOW FORWARD
 APPROACH. SUCH CLEAR FLOOR SPACE SHALL ADJOIN OR
 OVERLAP AN ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM
 OF 19 INCHES (485 MM) UNDERNEATH THE LAVATORY (SEE
 FIGURE 32 ).
  
 11-4.19.4 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES UNDER LAVATORIES SHALL BE
 INSULATED OR OTHERWISE CONFIGURED TO PROTECT AGAINST
 CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE SURFACES
 UNDER LAVATORIES.
  
 13)TABLE 803.3 MINIMUM INTERIOR FINISH
 CLASSIFICATION; PROVIDE INFORMATION BASED ON INTERIOR
 FINISH REQUIREMENTS BASED ON OCCUPANCY.
  
 14) ON THE INTERIOR ELEVATION SHEETS QUITE A FEW WALLS
 INDICATE THE USE OF UPHOLSTERED PANELS, PLEASE PROVIDE
 ADDITIONAL INFORMATION 106.1.2.HOW WILL THE FABRIC BE
 MOUNTED? 803.6.1 TEXTILE WALL COVERINGS.
 TEXTILE WALL COVERINGS SHALL HAVE A CLASS A FLAME
 SPREAD INDEX IN ACCORDANCE WITH ASTM E 84 AND BE
 PROTECTED BY AUTOMATIC SPRINKLERS INSTALLED IN
 ACCORDANCE WITH SECTION 903.3.1.1 OR 903.3.1.2 OR THE
 COVERING SHALL MEET THE CRITERIA OF SECTION 803.6.1.1
 OR 803.6.1.2 WHEN TESTED IN THE MANNER INTENDED FOR USE
 IN ACCORDANCE WITH NFPA 265 USING THE PRODUCT MOUNTING
 SYSTEM, INCLUDING ADHESIVE.
  
 15) THE MILLWORK LEGEND INDICATES CATALOG NUMBERS FOR
 TRIM BUT DOESN'T IDENTIFY AS TO WHAT TYPE OF MATERIALS
 THE TRIM WILL BE MADE OF? 106.1.2* ADDITIONAL
 INFORMATION REQUIRED.805.5 TRIM .
 MATERIAL USED AS INTERIOR TRIM SHALL HAVE A MINIMUM
 CLASS C FLAME SPREAD INDEX AND SMOKE-DEVELOPED INDEX.
 COMBUSTIBLE TRIM , EXCLUDING HANDRAILS AND GUARDRAILS,
 SHALL NOT EXCEED 10 PERCENT OF THE AGGREGATE WALL OR
 CEILING AREA IN WHICH IT IS LOCATED.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.