| Date |
Text |
| 2007-12-10 17:01:56 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: THE COMMENT NUMBER SHALL |
| | REMAIN THE SAME TO AVOID CONFUSION. |
| | |
| | 1.OK |
| | |
| | 2. SHTS 1 THRU 3 OF 3 & 1 THRU 7 OF 7. THE CERTIFICATE |
| | OF AUTHORIZATION NUMBER, (FIRM LICENSE NUMBER),IS |
| | REQUIRED IN THE TITLE BLOCK OF EACH SHEET AS WELL AS |
| | THE DATED SEAL, SIGNATURE, AND PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT. FAC 61G1-16.003, |
| | 61G1-16.004(2)(6) AND FS 481.219, 481.2055.--IT |
| | APPEARS THAT THE PLANS HAVE BEEN SIGNED WITH A |
| | INITIALS, NOT A SIGNATURE. IF INDEED THIS IS THE LEGAL |
| | SIGNATURE OF THE ENGINEER, THEN A SIGNED, SEALED, |
| | LEGALLY NOTORIZED LETTER INDICATING THE LEGAL ADDRESS |
| | OF THE LANDSCAPE ARCHITECT SHALL BE SUBMITTED FOR OUR |
| | FILES. |
| | ****RESPONSE NOTED, BUT SHT 7 OF 7 STILL SHOWS |
| | INITIALS, AND NO LETTER HAS BEEN SUBMITTED. --THE |
| | LICENSE FOR THE DESIGN PROFESSIONAL IS SHOWN IN |
| | DELINQUENT STATUS ON THE FLORIDA STATE DBPR WEBSITE. |
| | (SEE ATTACHED SHEET). PLEASE HAVE THE STATUS UPDATED |
| | PRIOR TO RESUBMITTING. |
| | |
| | 3. SHT 1 0F 1. THE CERTIFICATE OF AUTHORIZATION NUMBER, |
| | (FIRM LICENSE NUMBER),IS REQUIRED IN THE TITLE BLOCK |
| | OF EACH SHEET AS WELL AS THE DATED SEAL, SIGNATURE, AND |
| | PRINTED NAME OF THE PERSON SEALING THE DOCUMENT. FAC |
| | 61G1-16.003, 61G1-16.004(2)(6) AND FS 481.219, |
| | 481.2055.--THE SHEET HAS NOT BEEN SIGNED, SEALED & |
| | DATED ALSO. SECTION 106.1. |
| | ****RESPONSE NOTED, AND COMMENT IS OK,BUT THE LICENSE |
| | FOR THE DESIGN PROFESSIONAL IS SHOWN IN DELINQUENT |
| | STATUS ON THE FLORIDA STATE DBPR WEBSITE. (SEE ATTACHED |
| | SHEET). PLEASE HAVE THE STATUS UPDATED PRIOR TO |
| | RESUBMITTING. |
| | |
| | 4. SHT A-1.0 PER TABLE 403.1, MINIMUM FIXTURE |
| | REQUIREMENTS FOR THE FIRST FLOOR INCLUDE 4 W/C'S, 3 |
| | LAVS & 2 DRINKING FOUNTAINS. PLEASE INDICATE MINIMUM |
| | FACILITIES. |
| | ****RESPONSE NOTED, BUT ONLY 3 W/C'S ARE SHOWN. 4 W/C'S |
| | REQUIRED. |
| | |
| | 5. OK |
| | 6. OK |
| | 7. OK |
| | |
| | 8. SHT A-3.0 DETAIL #3 TOI.ET ROOMS SHALL BE |
| | ACCESSIBLE. SHOW COMPLIANCE WITH SECTION 11-4.22 AND |
| | ALL SUBSECTIONS. |
| | ****RESPONSE NOTED, BUT NOT ADDRESSED. NO GRAB BARS |
| | SHOWN, NO CLEAR FLOOR SPACE SHOWN, STILL INDICATESAS |
| | ADAPTABLE. PLEASE SHOW THE TOILET ROOMS AS ACCESSIBLE. |
| | SECTION 11-4.1.3(11). |
| | |
| | 9. SHT A-3.0 DETAILS #5 & #6 SINKS SHALL BE ACCESSIBLE. |
| | SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS.--THE GARBAGE DISPOSALS SHALL BE ADA |
| | COMPLIANT. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS |
| | WITH INSTALLATION INSTRUCTIONS. SECTION 106.1.2 MORE |
| | INFORMATION REQD. |
| | ****RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. NO |
| | CLEAR FLOOR SPACE SHOWN ON THE FLOOR PLAN, DIMENSIONS |
| | AT TOE KICK NOT APPROVED. MAX 6" FROM WALL REQUIRED, |
| | ONE DETAIL SHOWS 1'1" AND THE OTHER INDICATES 8-1/4". |
| | PLEASE SHOW COMPLIANCE WITH FIG. 11-31.--ONLY ONE |
| | COPY OF THE GARBAGE DISPOSAL FOUND, AND IT IS NOT |
| | APPROVED. NO ADA APPROVAL IS SHOWN ON THE MANUF. |
| | SPECIFICATION SHEET. |
| | |
| | 10. OK |
| | |
| | 11. SHT A-9.0 DETAIL #6 SINK SHALL BE ACCESSIBLE. |
| | PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. |
| | ****RESPONSE NOTED, BUT COMPLIANCE SHALL BE SHOWN FOR |
| | THE FOLLOWING: |
| | A. 11-4.24.4 SINK DEPTH |
| | B. 11-4.24.5 CLEAR FLOOR SPACE |
| | C. 11-4.24.7 FAUCETS |
| | |
| | 12. OK |
| | 13. OK |
| | |
| | 14. SHT A-9.1 DETAIL #3 SINK SHALL BE ACCESSIBLE. |
| | PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. |
| | ****RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. SHOW |
| | COMPLIANCE WITH THE FOLLOWING: |
| | A. 11-4.24.4 SINK DEPTH |
| | B. 11-4.24.5 CLEAR FLOOR SPACE |
| | C. 11-4.24.7 FAUCETS |
| | |
| | 15. OK |
| | 16. OK |
| | 17. OK |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | |
| | 22. SHT P5.1 DOMESTIC WATER RISER DIAGRAM FOR RRW & |
| | RRWR DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE |
| | RISER AND FLOOR PLAN. SECTION 106.1.1. ****RESPONSE |
| | NOTED, BUT COMMENT NOT ADDRESSED COMPLETLY. RISER STILL |
| | DOES NOT REFLECT THE FLOOR PLAN IN SOME AREAS. |
| | |
| | 23. OK |
| | 24. OK (INDICATED AS A BALLCOCK STYLE FLOAT VALVE. IF |
| | THERE IS AN AIR GAP, NO BACKFLOW IS REQUIRED). |
| | |
| | 25. SHT P5.1 THE SANITARY RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. FUTURE 4" LINE FOR TENANT 2 IS |
| | SHOWN ON THE 2ND FLOOR OF THE THE RISER DIAGRAM.-- |
| | THE FLOOR DRAIN SHOWN ON THE FLOOR PLAN NEAR ROOM 105 |
| | IS NOT SHOWN ON THE SANT. RISER DIAGRAM.--THE |
| | CLEANOUT SHOWN ON THE FLOOR PLAN DOWNSTREAM OF THE LAV |
| | IN THE WOMENS TOILET ROOM 2ND FLOOR IS NOT SHOWN ON THE |
| | RISER DIAGRAM.--ONLY ONE EWC IS INDICATED. THE EWC |
| | BY THE RECEPTION AREA IS NOT SHOWN ON THE RISER |
| | DIAGRAM.--RISER SHOWS AN EXTRA FLOOR DRAIN AND VENT |
| | UPSTREAM OF THE ONE SHOWN IN THE ELEVATOR MACHINE ROOM, |
| | (TO BE DELETED PER SECTION 301.6).--NOTE #3 AT THE |
| | TWO WAY CLEANOUT NEAR THE JUNCTION OF THE BUILDING |
| | DRAIN AND THE BUILDING SEWER DOES NOT REFLECT KEY NOTE |
| | #3. PLEASE CHECK THAT THE RISER DIAGRAM. CORRELATES |
| | WITH THE FLOOR PLAN. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE VENT FOR THE FLOOR DRAIN BY |
| | THE ELECTRICAL ROOM APPEARS TO OFFSET BELOW THE SLAB. |
| | PER SECTION 905.4 THE VENT SHALL RISE VERTICALLY A |
| | MINIMUM 6" ABOVE THE FLOOD RIM LEVEL PRIOR TO |
| | OFFSETTING HORIZONTALLY.--THE 4" BRANCH LINE FOR |
| | THE FUTURE TENANT IS SHOWN DOWNSTREAM OF THE SECOND |
| | FLOOR RISER ON THE FLOOR PLAN, BUT UPSTREAM OF THE |
| | RISER ON THE ISOMETRIC RISER DIAGRAM. PLEASE CORRELATE. |
| | |
| | |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | 29. OK |
| | 30. OK |
| | 31. OK |
| | 32. OK |
| | |
| | 33. THE APPLICATION STATES "DESCRIBE PROJECT IN DETAIL" |
| | (FAILURE TO DO SO MAY RESULT IN DELAYS). IT APPEARS |
| | THAT THE SECOND FLOOR WILL BE BUILT OUT,BUT THE FIRST |
| | FLOOR WILL BE SHELL ONLY WITH THIS PERMIT. THIS IS NOT |
| | INDICATED ON THE PERMIT APPLICATION, (NEW BUILD). |
| | PLEASE INDICATE THE SCOPE OF WORK FOR THIS PERMIT AS |
| | REQUIRED ON THE APPLICATION. |
| | ****RESPONSE NOTED, WILL CHECK WHEN THE APPLICATION IS |
| | RETURNED. |
| | |
| | **********NEW COMMENT********** |
| | |
| | 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| | PROFESSIONAL & FS 553.80(2)(B). THIS IS GIVEN AS A |
| | NOTICE ONLY AT THIS TIME. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | ****RESPONSE NOTED. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |