Plan Review Notes
Plan Review Notes For Permit 07070315
Permit Number 07070315
Review Stop P
Sequence Number 2
Notes
Date Text
2007-12-10 17:01:56DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW: THE COMMENT NUMBER SHALL
 REMAIN THE SAME TO AVOID CONFUSION.
  
 1.OK
  
 2. SHTS 1 THRU 3 OF 3 & 1 THRU 7 OF 7. THE CERTIFICATE
 OF AUTHORIZATION NUMBER, (FIRM LICENSE NUMBER),IS
 REQUIRED IN THE TITLE BLOCK OF EACH SHEET AS WELL AS
 THE DATED SEAL, SIGNATURE, AND PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT. FAC 61G1-16.003,
 61G1-16.004(2)(6) AND FS 481.219, 481.2055.--IT
 APPEARS THAT THE PLANS HAVE BEEN SIGNED WITH A
 INITIALS, NOT A SIGNATURE. IF INDEED THIS IS THE LEGAL
 SIGNATURE OF THE ENGINEER, THEN A SIGNED, SEALED,
 LEGALLY NOTORIZED LETTER INDICATING THE LEGAL ADDRESS
 OF THE LANDSCAPE ARCHITECT SHALL BE SUBMITTED FOR OUR
 FILES.
 ****RESPONSE NOTED, BUT SHT 7 OF 7 STILL SHOWS
 INITIALS, AND NO LETTER HAS BEEN SUBMITTED. --THE
 LICENSE FOR THE DESIGN PROFESSIONAL IS SHOWN IN
 DELINQUENT STATUS ON THE FLORIDA STATE DBPR WEBSITE.
 (SEE ATTACHED SHEET). PLEASE HAVE THE STATUS UPDATED
 PRIOR TO RESUBMITTING.
  
 3. SHT 1 0F 1. THE CERTIFICATE OF AUTHORIZATION NUMBER,
 (FIRM LICENSE NUMBER),IS REQUIRED IN THE TITLE BLOCK
 OF EACH SHEET AS WELL AS THE DATED SEAL, SIGNATURE, AND
 PRINTED NAME OF THE PERSON SEALING THE DOCUMENT. FAC
 61G1-16.003, 61G1-16.004(2)(6) AND FS 481.219,
 481.2055.--THE SHEET HAS NOT BEEN SIGNED, SEALED &
 DATED ALSO. SECTION 106.1.
 ****RESPONSE NOTED, AND COMMENT IS OK,BUT THE LICENSE
 FOR THE DESIGN PROFESSIONAL IS SHOWN IN DELINQUENT
 STATUS ON THE FLORIDA STATE DBPR WEBSITE. (SEE ATTACHED
 SHEET). PLEASE HAVE THE STATUS UPDATED PRIOR TO
 RESUBMITTING.
  
 4. SHT A-1.0 PER TABLE 403.1, MINIMUM FIXTURE
 REQUIREMENTS FOR THE FIRST FLOOR INCLUDE 4 W/C'S, 3
 LAVS & 2 DRINKING FOUNTAINS. PLEASE INDICATE MINIMUM
 FACILITIES.
 ****RESPONSE NOTED, BUT ONLY 3 W/C'S ARE SHOWN. 4 W/C'S
 REQUIRED.
  
 5. OK
 6. OK
 7. OK
  
 8. SHT A-3.0 DETAIL #3 TOI.ET ROOMS SHALL BE
 ACCESSIBLE. SHOW COMPLIANCE WITH SECTION 11-4.22 AND
 ALL SUBSECTIONS.
 ****RESPONSE NOTED, BUT NOT ADDRESSED. NO GRAB BARS
 SHOWN, NO CLEAR FLOOR SPACE SHOWN, STILL INDICATESAS
 ADAPTABLE. PLEASE SHOW THE TOILET ROOMS AS ACCESSIBLE.
 SECTION 11-4.1.3(11).
  
 9. SHT A-3.0 DETAILS #5 & #6 SINKS SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.--THE GARBAGE DISPOSALS SHALL BE ADA
 COMPLIANT. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS
 WITH INSTALLATION INSTRUCTIONS. SECTION 106.1.2 MORE
 INFORMATION REQD.
 ****RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. NO
 CLEAR FLOOR SPACE SHOWN ON THE FLOOR PLAN, DIMENSIONS
 AT TOE KICK NOT APPROVED. MAX 6" FROM WALL REQUIRED,
 ONE DETAIL SHOWS 1'1" AND THE OTHER INDICATES 8-1/4".
 PLEASE SHOW COMPLIANCE WITH FIG. 11-31.--ONLY ONE
 COPY OF THE GARBAGE DISPOSAL FOUND, AND IT IS NOT
 APPROVED. NO ADA APPROVAL IS SHOWN ON THE MANUF.
 SPECIFICATION SHEET.
  
 10. OK
  
 11. SHT A-9.0 DETAIL #6 SINK SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
 ****RESPONSE NOTED, BUT COMPLIANCE SHALL BE SHOWN FOR
 THE FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE
 C. 11-4.24.7 FAUCETS
  
 12. OK
 13. OK
  
 14. SHT A-9.1 DETAIL #3 SINK SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
 ****RESPONSE NOTED, BUT NOT COMPLETLY ADDRESSED. SHOW
 COMPLIANCE WITH THE FOLLOWING:
 A. 11-4.24.4 SINK DEPTH
 B. 11-4.24.5 CLEAR FLOOR SPACE
 C. 11-4.24.7 FAUCETS
  
 15. OK
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
  
 22. SHT P5.1 DOMESTIC WATER RISER DIAGRAM FOR RRW &
 RRWR DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE
 RISER AND FLOOR PLAN. SECTION 106.1.1. ****RESPONSE
 NOTED, BUT COMMENT NOT ADDRESSED COMPLETLY. RISER STILL
 DOES NOT REFLECT THE FLOOR PLAN IN SOME AREAS.
  
 23. OK
 24. OK (INDICATED AS A BALLCOCK STYLE FLOAT VALVE. IF
 THERE IS AN AIR GAP, NO BACKFLOW IS REQUIRED).
  
 25. SHT P5.1 THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. FUTURE 4" LINE FOR TENANT 2 IS
 SHOWN ON THE 2ND FLOOR OF THE THE RISER DIAGRAM.--
 THE FLOOR DRAIN SHOWN ON THE FLOOR PLAN NEAR ROOM 105
 IS NOT SHOWN ON THE SANT. RISER DIAGRAM.--THE
 CLEANOUT SHOWN ON THE FLOOR PLAN DOWNSTREAM OF THE LAV
 IN THE WOMENS TOILET ROOM 2ND FLOOR IS NOT SHOWN ON THE
 RISER DIAGRAM.--ONLY ONE EWC IS INDICATED. THE EWC
 BY THE RECEPTION AREA IS NOT SHOWN ON THE RISER
 DIAGRAM.--RISER SHOWS AN EXTRA FLOOR DRAIN AND VENT
 UPSTREAM OF THE ONE SHOWN IN THE ELEVATOR MACHINE ROOM,
 (TO BE DELETED PER SECTION 301.6).--NOTE #3 AT THE
 TWO WAY CLEANOUT NEAR THE JUNCTION OF THE BUILDING
 DRAIN AND THE BUILDING SEWER DOES NOT REFLECT KEY NOTE
 #3. PLEASE CHECK THAT THE RISER DIAGRAM. CORRELATES
 WITH THE FLOOR PLAN. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE VENT FOR THE FLOOR DRAIN BY
 THE ELECTRICAL ROOM APPEARS TO OFFSET BELOW THE SLAB.
 PER SECTION 905.4 THE VENT SHALL RISE VERTICALLY A
 MINIMUM 6" ABOVE THE FLOOD RIM LEVEL PRIOR TO
 OFFSETTING HORIZONTALLY.--THE 4" BRANCH LINE FOR
 THE FUTURE TENANT IS SHOWN DOWNSTREAM OF THE SECOND
 FLOOR RISER ON THE FLOOR PLAN, BUT UPSTREAM OF THE
 RISER ON THE ISOMETRIC RISER DIAGRAM. PLEASE CORRELATE.
  
  
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
  
 33. THE APPLICATION STATES "DESCRIBE PROJECT IN DETAIL"
 (FAILURE TO DO SO MAY RESULT IN DELAYS). IT APPEARS
 THAT THE SECOND FLOOR WILL BE BUILT OUT,BUT THE FIRST
 FLOOR WILL BE SHELL ONLY WITH THIS PERMIT. THIS IS NOT
 INDICATED ON THE PERMIT APPLICATION, (NEW BUILD).
 PLEASE INDICATE THE SCOPE OF WORK FOR THIS PERMIT AS
 REQUIRED ON THE APPLICATION.
 ****RESPONSE NOTED, WILL CHECK WHEN THE APPLICATION IS
 RETURNED.
  
 **********NEW COMMENT**********
  
 1B. SEE ATTACHED SHEET CONCERNING THE DESIGN
 PROFESSIONAL & FS 553.80(2)(B). THIS IS GIVEN AS A
 NOTICE ONLY AT THIS TIME.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 ****RESPONSE NOTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved