Plan Review Notes
Plan Review Notes For Permit 07070315
Permit Number 07070315
Review Stop M
Sequence Number 2
Notes
Date Text
2007-11-28 16:34:45REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THE REVISED NOTE #13 INDICATES AN AUDIBLE AND
 VISIBLE SIGNAL WILL BE LOCATED AT THE RESPECTIVE
 THERMOSTATS. IS THIS IN ADDITION TO THE GENERAL ALARM
 SIGNAL AS INDICATED BY NOTE 9(D) ON PG E5.2? ALSO,
 PLEASE COORDINATE THIS NOTE WITH NOTE #17 ON PG FA 1.2,
 WHICHINDICATES A VISIBLE AND AUDIBLE ALARM WILL BE
 SENT TO THE FACP. THIS IS LOCATED AT THE 1ST FLOOR
 LOBBY AND DOES NOT APPEAR TO BE A CONSTANTLY ATTENDED
 LOCATION.
  
 2. OK
  
 3. M1.1: THERE IS STILL ONE 12X8 EXHAUST DUCT
 PENETRATION (ASSOCIATED WITH KEY NOTE #2, AS STATED IN
 PREVIOUS REVIEW) WHICH IS NOT SHOWN AS BEING PROTECTED
 BY A FIRE DAMPER. SHOW COMPLIANCE WITH FBC,M 607.6 AND
 607.8.
  
 4. OK
  
 5. THE DESIGN INTENT IS STILL UNCLEAR. ON M7.2, DETAIL
 9 SHOWS THE PIPES ENTERING A FIRE RATED CHASE. ON M7.1,
 DETAIL 9 SHOWS A THROUGH-PENETRATION FIRESTOP SYSTEM
 FOR CONCRETE, INDICATING THIS IS A FLOOR/CEILING
 PENETRATION. A FLOOR/CEILING THROUGH-PENETRATION SYSTEM
 IS NOT NEEDED IF THE PIPE IS IN A FIRE RATED CHASE.
 ALSO, THE SYSTEM SPECIFIED IN THE DETAIL IS NOT
 APPLICABLE TO THIS LOCATION FOR THE FOLLOWING REASONS:
 A) IT ONLY ALLOWS FOR ONE PIPE PER HOLE.
 B) IT IS ONLY LISTED FOR STEEL PIPE. COPPER IS NOT PART
 OF ITS LISTING.
 C) IF THIS IS NOT FOR THE FLOOR/CEILING, BUT FOR WHERE
 THE PIPES LEAVE THE FIRE RATED CHASE, IT WILL NOT WORK
 BECAUSE IT IS ONLY LISTED FOR USE IN CONCRETE, NOT A
 FRAMED WALL OR SHAFT ASSEMBLY.
 ALSO, THERE IS NO FIRE RATED CHASE SHOWN ON
 ARCHITECTURAL FLOOR PLANS AT THESE LOCATIONS, ONLY
 PARTITIONS TO GO 6 INCHES ABOVE THE CEILING ACCORDING
 TO THE WALL LEGEND ON THE A PAGES. THERE IS NO LISTED
 ASSEMBLY FOR A FIRE RATED CHASE IN THE ARCHITECTURAL
 DETAILS. PLEASE CLARIFY THE INTENT AND DEMONSTRATE
 COMPLIANCE WITH FBC 712.4.
  
 6. OK
  
 7. OK
  
 8. THE ?ASSEMBLY AND DIMENSIONAL INFORMATION? PACKAGE
 SUBMITTED FOR FIRE DAMPERS DOES NOT INCLUDE THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS. DETAIL 7 ON
 M7.1 DOES NOT CORRESPOND WITH RUSKIN INSTALLATION
 INSTRUCTIONS. OPTIONS:
 A) REMOVE THE CURRENT DETAIL FROM THE PLANS. PROVIDE A
 NOTE ON PLANS DEFERRING TO MANUFACTURER?S INSTALLATION
 INSTRUCTIONS. PROVIDE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS IN THE SUBMITTAL PACKAGE.
 B) INCLUDE THE MANUFACTURER?S INSTALLATION INSTRUCTION
 ON PLANS (IF ALLOWED BY MANUFACTURER, THIS IS NOT A
 RECOMMENDATION TO VIOLATE ANY COPYRIGHT.).
 SHOW COMPLIANCE WITH FBC, M 607.2.
  
 9. THE PRESCRIPTIVE FASTENING METHOD LISTED IN FBC, M
 301.13.1 IS ONLY APPLICABLE FOR GROUP R-3 OCCUPANCIES.
 IT IS NOT APPLICABLE TO THIS PROJECT. IN ANY OTHER
 OCCUPANCY, ENGINEERING IS REQUIRED BASED ON THE WIND
 SPEED AND WIND LOAD CALCULATIONS IN ACCORDANCE WITH FBC
 CH.16. OPTIONS:
 A) PROVIDE WIND LOAD CALCULATIONS FOR OUTDOOR EQUIPMENT
 WITH FASTENER DETAILS FOR BUILDING PLAN REVIEW. NOTE:
 DETAIL 3 ON M7.2 SHOWS INBED OR EXPANSION ANCHOR BOLTS
 TO BE USED ON CONDENSERS BUT KEY NOTES CALL FOR STRAPS
 AND TAPCONS.
 B) CHECK WITH EQUIPMENT MANUFACTURER. MANY
 MANUFACTURERS HAVE THEIR INSTALLATION INSTRUCTIONS
 TESTED AND CERTIFIED TO MEET WIND LOADS ALREADY. IF
 THIS IS THE CASE, MANUFACTURER?S INSTRUCTIONS MAY BE
 USED. A DETAIL MAY BE PROVIDED WHICH CORRESPONDS WITH
 THOSE INSTRUCTIONS AND A NOTE WHICH DEFERS TO
 INSTRUCTIONS MAY BE USED. IF THIS METHOD IS USED,
 PROVIDE DOCUMENTATION WHICH VERIFIES THAT THE
 MANUFACTURER?S INSTRUCTIONS HAVE BEEN TESTED AND MEET
 WIND LOADS FOR THIS AREA.
  
 10. OK
  
 11. ENERGY CALCULATIONS: METHOD B HAS BEEN SUBMITTED.
 HOWEVER, IT APPEARS THAT ONLY THE SPACES BEING
 BUILT-OUT ARE INCLUDED IN THE CALCULATIONS. AS STATED
 IN FBC 13-101.1.6, ?ALL ASSUMPTIONS MADE ABOUT FEATURES
 NOT INSTALLED UNTIL LATER THAT ARE NOT ON THE BUILDING
 PLANS SHALL BE LISTED AND APPENDED TO THE COMPLIANCE
 FORM SUBMITTED TO THE BUILDING DEPARTMENT.? NO
 ASSUMPTIONS ABOUT FEATURES TO BE INSTALLED IN THE
 UNFINISHED AREA COULD BE FOUND APPENDED TO THE
 CALCULATIONS. ALSO, THE PROJECT SUMMARY PAGE INDICATES
 THAT ONLY THE FINISHED AREAS WERE COUNTED IN THE
 CALCULATIONS. COOLING LOAD CALCULATIONS, A/C EQUIPMENT
 AND LIGHTING ASSUMPTIONS SHALL BE PROVIDED WITH THE
 COMPLIANCE FORM FOR ALL UNFINISHED AREAS OF THE
 BUILDING AND BE INCLUDED IN THE CALCULATIONS IN
 ACCORDANCE WITH THIS SECTION. ENERGY CALCULATIONS CAN
 NOT BE REVIEWED AT THIS TIME.
  
 12. OK
  
 13. OK
  
 14. RESPONSE INDICATES THAT THE GENERATOR IS NOT
 RELATED TO THE MECHANICAL DISCIPLINE. PLEASE SEE FBC, M
 915.1, WHICH STATES ?THE INSTALLATION OF LIQUID-FUELED
 STATIONARY INTERNAL COMBUSTION ENGINES AND GAS
 TURBINES, INCLUDING FUEL STORAGE AND PIPING, SHALL MEET
 THE REQUIREMENTS OF NFPA 37.? THIS CLEARLY MAKES DIESEL
 POWERED GENERATORS AND THEIR FUEL STORAGE SYSTEMS
 SUBJECT TO THE MECHANICAL CODE. THE MECHANICAL CODE
 REFERENCES NFPA 37, WHICH IS THE STANDARD BY WHICH THE
 GENERATOR INSTALLATION AND ITS FUEL STORAGE SYSTEM WILL
 BE REVIEWED BY THE MECHANICAL REVIEWER. NO INFORMATION
 HAS BEEN PROVIDED REGARDING DIESEL FUEL STORAGE FOR
 THIS GENERATOR. ALSO, IF THE DIESEL TANK EXCEEDS 550
 GALLONS; THE TANK, ITS INSTALLATION METHOD AND LOCATION
 MUST BE FIRST APPROVED BY PALM BEACH COUNTY DERM BEFORE
 SUBMITTAL TO THIS AHJ FOR PERMIT. CONTACT INFORMATION
 FOR PBC DERM WAS PROVIDED TO THE DESIGN TEAM DURING OUR
 MEETING IN THIS OFFICE.
  