| 2007-11-21 14:32:57 | ***FAILED**** PLEASE PROVIDE THE FOLLOWING: |
| | |
| | 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI). |
| | PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR |
| | NOI. |
| | YOU CAN GET NOI INFO FROM |
| | WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/ |
| | NOTICE OF INTENT DEP FORM 62-621.300(4)(B), |
| | EFFECTIVE MAY 1, 2003 |
| | |
| | COUND NOT FIND IN YOUR PACKAGE. PLEASE MAKE A SEPARATE |
| | PACKAGE FOR ENGINEERING REVIEW, SO, I GET IT WITHOUT |
| | LOST. |
| | |
| | 2. FIRST FLOOR ELEVATION, CENTER LINE OF ROAD , |
| | SIDEWALK ELEVATION MUST MEET FLOOD ZONE AREA, & 5,10, |
| | 25, 100 YEAR FLOOD CRITERIATO DETERMINE THE FIRST |
| | FLOOR ELEVATION, PLEASE SHOW IN YOUR STORM WATER CALS |
| | THAT HOW DID YOU DETERMINE THE FIRST FLOOR ELEVATION? |
| | FIRST FLOOR ELEVATION MUST BE HIGHER THAN MAXIMUM CROWN |
| | OF THE ROAD BY ATLEAST 1 FOOT. |
| | 3. PLEASE SHOW DETAIL OF THE CONTROL STRUCTURESWITH |
| | ELEVATIONS, NOTCHES, BLEEDING ELEVATION, ETC ON |
| | DRAWINGS,PLEASE PROVIDE CALCULATION FOR EXFILTRATION |
| | TRENCHES IN WATER QUALITY CALS.PLEASE SHOW DRY |
| | DETENTION/WET DETENTION AREAS IN STORM WATER CALS. |
| | AFTER CONTROL STRUCTURE WHERE DOES STORM WATER GOES?? |
| | 4. PLEASE RESUBMIT A COPY OF SFWMD PERMIT,, & PROVIDE |
| | STORM WATER QUALITY CALCULATIONS. PLEASE RESUBMIT |
| | GEO-TECH REPORT WITH STORM WATER CALS. ALSOSTORM |
| | WATER CALS MUST BE APPROVED FROM 100045TH STREET |
| | ENGINEERING SERVICES. |
| | 5. WATER & SEWER PLANS MUST BE APPROVED FROM 45TH |
| | STREET (MANNY G.), UTILITY DEPT BEFORE WE APPROVED. |
| | |
| | PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR |
| | PERMITTING PROCESS |
| | |
| | RASIK CHOKSHI805-6723 |