Plan Review Notes
Plan Review Notes For Permit 07070315
Permit Number 07070315
Review Stop E
Sequence Number 2
Notes
Date Text
2007-11-30 13:03:25 
  
  
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL IN NEED OF ADDRESSING.
 PLEASE ALSO SEE NEW COMMENTS BASED ON SOME INFORMATION
 ONLY NOW SUBMITTED FOR REVIEW.
  
  
 1) NOTE: PLEASE PROVIDE AND SUBMIT THE ORIGINAL PERMIT
 APPLICATION BACK WITH THE RESUBMITTED PLANS FOR THIS
 SCOPE OF WORK. PLEASE SEE THE PERMIT APPLICATION WHICH
 WAS SUBMITTED AND PLACED IN PACKAGE WAS FOR PERMIT
 #07070314 FOR SITE CLEARANCE AND DEMO/SITE WORK.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #5 REQUESTED
 THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 GENERATOR/FUEL TANK AND ATS TO BE SUBMITTED. THE SHEETS
 FOR THE GENERATOR WAS SUBMITTED HOWEVER NOT THE SHEETS
 FOR THE ATS.
 PLEASE ALSO SEE NO SPECS WERE SUBMITTED FOR FUEL TANK
 FOR REVIEW BY FIRE AND MECHANICAL.
 PLEASE KNOW THESE ARE REQUIRED AT THIS TIME. PLEASE SEE
 COMMENTS FROM OTHER TRADES SUCH AS MECHANICAL FOR
 POSSIBLE COMMENTS.
 PLEASE PROVIDE MINIMUM CLEARANCE INFORMATION FOR THE
 GENERATOR ON ALL SIDES OF UNIT. THE SIDE FACING THE
 CONDENSING UNITS SEEMS TO BE LESS THAN THE MINIMUMS
 WHICH THIS OFFICE HAS SEEN AS SET-FORTH FROM
 MANUFACTURE AND RECOMMENDED CLEARANCES. PLEASE KNOW ALL
 CLEARANCES PER NEC 110.26 SHALL ALSO BE REQUIRED.
 110.3, 90.7,
 FBC 106.1.2
  
 ** FN:BASED ON TANK PROVIDED AND SIZE OF GENERATOR
 WITH FUEL CONSUMPTION LISTED ON CUT SHEETS, THIS WILL
 NOT PROVIDE THE 72HRS AS STATED. AS THIS IS AN OPTIONAL
 STAND-BY SYSTEM, THE TIME IS NOT OF CONCERN HOWEVER
 RECORD PLANS SHOULD PROVIDE ALL INFORMATION.
  
 3) NOTE: PLEASE SEE PREVIOUS NOTE #6. PLEASE SUBMIT
 COMPLETED ENERGY CALCULATIONS WHICH MEET THE FBC AND
 CORRELATE WITH ALL ELECTRICAL DESIGNS FOR LIGHTING
 FIXTURESETC ON PLANS.
 PLEASE BE SURE ALL FIXTURES ON PLANS COORDINATE WITH
 THE INPUT DATA REPORTS FOR ALL INTERIOR AND EXTERIOR
 LIGHTING.
 PLEASE SEE SOME OF THE FOLLOWING EXAMPLES WHERE THESE
 DO NOT CORRELATE.
 THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR THE REST
 OF THIS COMMENT.
 FOR EXAMPLE: PLEASE SEE THE FIRST ITEM ON THE IDR WHICH
 IS THE LOBBY LIGHTING WHICH INDICATES A 260W FIXTURE
 WHEREAS NEITHER THE PLANS NOR THE FIXTURE LEGEND HAS
 ANY 260W FIXTURE.
 FOR EXAMPLE: PLEASE SEE THE FIXTURE WS4 WHICH IS ON
 PLANS AND FIXTURE LEGEND HOWEVER THE IDR DOES NOT ANY
 OF THESE 75W FIXTURES.
 FOR EXAMPLE: PLEASE SEE THE EXTERIOR LIGHTING FIXTURES
 WD26 WHICH DO APPEAR TO BE ON THE IDR AND/OR WATTAGE
 DOES NOT CORRELATE.
 FOR EXAMPLE: PLEASE SEE THE TOTAL NUMBER OF *EXTERIOR
 LIGHTING FIXTURES* DO NOT CORRELATE WITH THE IDR.THIS
 SHOULD INCLUDE ALL LIGHTING FIXTURES EVEN IF THEY ARE
 THE 2ND FLOOR EXTERIOR LIGHTS.
 FOR EXAMPLE: THE TOTAL SQ FT AND ASSUMPTIONS REQUIRED
 FOR SHELL SPACE HAVE NOT AND ARE NOT INCLUDED.
  
 THESE ARE A FEW EXAMPLES AND NOT ALL ITEMS. PLEASE
 CORRELATE ALL REQUIRED INFORMATION AND ALL INFORMATION
 ON PLANS WITH THAT OF THE IDR, SUMMARY AND TOTALS ON
 THE METHOD *B* AS SUBMITTED.
 PLEASE SEE 13-101.1.6, 13-415.2, 13-415.1.B AND ALL
 SECTIONS AS GIVEN IN FIRST REVIEW; 13-4, 13-101.1,
 13-414.2(2)(3)M 13-415.1.ABC.2, 13-415.1.ABC.1.4,
 13-415.2.ABC.1.3 ETC.
  
 4) NOTE: PLEASE SEE PREVIOUS NOTE #9 WHICH REQUESTED TO
 SUBMIT COMPLETED PHOTO-METRICS FOR EGRESS PATHS
 INDICATING THE MINIMUM LIGHTING LEVELS FOR FLAT EGRESS
 SURFACES AS WELL AS BOTH STAIR AREAS. PLEASE SEE LS 101
 7.8.1.3, 7.9.2.2.
 PLEASE ALSO SEE THE FLORIDA ADMINISTRATIVE CODE
 61G15-33.004 AS THIS IS REQUIRED.
 THE RESPONSE ADDRESSED OTHER PARTS OF PREVIOUS NOTE
 HOWEVER THIS WAS NOT ADDRESSED AND NONE WERE SUBMITTED
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
 ** PLEASE KNOW AS NO LIGHTING LEVELS WERE SUBMITTED
 NONE COULD BE REVIEWED AT THIS TIME.
  
 5) NOTE: PLEASE SEE PREVIOUS NOTE #17 WHICH MENTIONED
 FOR ALL A/C CU DISCONNECTS TO MEET 110.26.
 THE RESPONSE MENTIONS THIS WILL BE FIELD VERIFIED. THIS
 IS CORRECT HOWEVER THE PLANS ARE STILL REQUIRED TO SHOW
 MINIMUM CODE COMPLIANCE.
 PLEASE SEE UNIT LAYOUT ON E4.2 AS DISCONNECTS ARE STILL
 BE SHOWNON TWO WALLS BEHIND UNITS.
 ** THIS IS AN ITEM WHICH WOULD NORMALLY BE REDLINED IF
 THIS WAS OF THE *MINOR* COMMENTS HOWEVER AS PLANS ARE
 COMING BACK FOR OTHER CORRECTIONS PLEASE SHOW *MINIMUM*
 CODE COMPLIANCE AT THIS TIME.
  
 6) NOTE: PLEASE SEE PREVIOUS NOTE #20 FOR MEANS OF
 DISCONNECT FOR FEEDERS AT THE MAIN BUILDING FOR THE
 FEEDERS FROM THE OUTSIDE MAIN.
 THE RESPONSE GIVES A LONG EXPLANATION WHICH GOES INTO
 CODES IN CHAPTER 7 WHICH ARE KNOWN TO THIS OFFICE.
 PLEASE KNOW THIS PROJECT LOCATION AND BUILDING DOES NOT
 MEET THE EXCEPTION FOR UNDER SINGLE MANAGEMENT AND
 QUALIFIED PERSONNEL AND DOCUMENTED SAFE DISCONNECTING
 PRACTICES.
 PLEASE SEE AS STATED ON PREVIOUS COMMENTS; PLEASE
 PROVIDE DISCONNECTING MEANS FOR FEEDERS AS REQUIRED PER
 225.31-225.39.
 THE SECTIONS GIVEN IN THE RESPONSE LETTER FOR THE
 GENERATOR WHICH REFLECTS FEEDERS FROM *OUTDOOR
 GENERATOR* SETS FOR 700 AND 701 DO NOT APPLY AS THE
 SYSTEM AS SHOWN ON PLANS IS THAT OF 702. THE SECTION
 702.11 IN THE 2005 NEC WAS REVISED TO INCLUDE THE
 SECTION WHICH WAS PREVIOUSLY IN 700 AND 701 FOR OUTDOOR
 GENERATORS, HOWEVER WHEN SPEAKING OF 702.11 THIS
 SECTION REQUIRES THE DISCONNECTING MEANS TO BE *
 READILY ACCESSIBLE* AND *WITHIN SIGHT*. PLEASE SEE NEC
 100 FOR DEFINITIONS OF BOTH. THE GENERATOR IS WITHIN
 SIGHT(50FT) HOWEVER THE DISCONNECT MEANS DOES NOT
 MEET READILY ACCESSIBLE BASED ON PLANS AND INFORMATION
 SUBMITTED.
 IN EITHER CASE AS STATED ABOVE THE DISCONNECTING MEANS
 (W/OUT OCP) FOR THE FEEDERS IS STILL REQUIRED.
  
 7) NOTE: PLEASE SEE PREVIOUS NOTE #21 FOR GROUNDING
 ELECTRODE SYSTEM. RESPONSE MENTIONS TO SEE DETAILS ON
 5.1 AND 7.1 HOWEVER EITHER SHEET DOES NOT PROVIDE THE
 INFORMATION NEEDED. WHERE IS THE GROUNDING ELECTRODE
 SYSTEM SHOWN FOR THE MAIN SERVICE LOCATION. RISER SHOWS
 THAT THERE WILL BE ONE, BUT GROUND RODS, HOW MANY,
 SIZE, WHAT TYPE ETC IS NOT SHOWN
 MAIN BUILDING DETAIL DOES SHOW TO CONCRETE ENCASED
 ELECTRODE BUT IT IS ONLY BEING ASSUMED THAT THIS IS THE
 FOOTER STEEL AS REQUIRED.
 (DETAIL ON E7.1 MENTIONS THERE WILL BE A GROUND LOOP)
 PLEASE PROVIDE MORE INFORMATION OR SHOW DETAIL FOR MAIN
 SERVICE GE-SYSTEM PER 250.50,-250.56
  
 8) NOTE: PLEASE SEE PREVIOUS NOTE #23 WHICH SPOKE OF
 THE REQUIRED DEDICATED CIRCUITS FOR ELEVATOR MACHINE
 ROOMS/PIT HOIST-WAY CIRCUITS.
 THE RESPONSE MENTIONS THAT CIRCUIT HP-16 WAS ALREADY
 PROVIDED. THIS IS TRUE, THIS CIRCUIT WAS PROVIDE
 HOWEVER AS STATED ON PREVIOUS COMMENT, THIS MAY NOT
 FEED ANY OTHER LOCATIONS EXCEPT THE AREA IN WHICH IS
 STATED IN THE CODE.
 PLEASE ALSO SEE THE RESPONSE MENTIONS THAT IT IS THE
 CONTRACTORS RESPONSIBILITY TO NOT CONNECT ON THE LOAD
 SIDE OF THE GFI. THE PREVIOUS REVIEW COMMENT DID NOT
 SAY ANYTHING ABOUT ANY CONNECTIONS TO THE LOAD SIDE OF
 THE GFI NOT DID THE COMMENT GIVE A SECTION IN THE CODE
 WHICH STATES THIS.
 PLEASE SEE THE PLANS. PLEASE SEE SPECIFICALLY SHEET
 E4.1, DETAIL #2 E4.1 WHICH SHOWS CIRCUIT HP1-16 FEEDING
 BOTH THE ELEVATOR ROOM GFI RECEPTACLES AND ALSO THE
 ELEVATOR PIT GFI RECEPTACLES. THESE ARE NOT PERMITTED
 AND PLEASE ADJUST CIRCUIT(S).
 PLEASE SEE SPECIFICALLY SHEET E4.1 WHICH SHOWS CIRCUIT
 HP1-13 FEEDING BOTH THE MAIN ELECTRICAL ROOM LIGHTING
 ON FIRST FLOOR AS WELL AS THE LIGHTING IN PIT.
 ONCE AGAIN THIS IS NOT PERMITTED AND REQUIRES DEDICATED
 CIRCUITS.
 PLEASE SEE 620.23 AND 620.24.
  
 9) NOTE: PLEASE SEE PREVIOUS NOTE #26. PLEASE PROVIDE
 METER CAN SIZES ON BUILDING. PLEASE VERIFY THE 600AMP
 METER CAN AS SHOWN.
 PLEASE SEE NOTE #26 FROM PREVIOUS REVIEW IS COPIED FOR
 SAME CLARIFICATION.
 PLEASE PROVIDE NOTE FOR *FLOATING NEUTRAL KIT REQUIRED
 * AT THE METERS AT THE BUILDING. 250.6, 250.24
 ***************************
 26) NOTE: PLEASE INDICATE THE SIZE/AMERAGE OF THE METER
 CANS ON THE RISER. PLEASE SEE THE METER WHICH IS SHOWN
 ONE E-4.2 FOR MAIN IS NOT INCLUDED ON RISER DIAGRAM
 SHEET E-5.1.
 PLEASE COORDINATE AND ADJUST PLANS AND SHOW SIZES OF
 EQUIPMENT.
 FBC 106.1.2, 106.3.5.1.2
 ************************
  
 10) NOTE: PLEASE SEE PREVIOUS NOTE #27. PLEASE SHOW AND
 INDICATES FEEDERS FROM GUTTER TO METERS, METERS TO
 MAINS AT THE BUILDING.
 PLEASE INDICATE
 ** PREVIOUS REVIEW NOTE **
 27) NOTE: PLEASE INDICATE THE SIZE OF FEEDERS FROM
 WIRE-WAY TO METERS TO MAINS ON E5.1.
 310.16, 215.5, 240.4
 FBC 106.1.2, 106.3.5.1.2
  
 11) NOTE: PLEASE SEE PREVIOUS NOTE #28.
 THE RESPONSE MENTIONS THIS BREAKER IS 1200AMPS JUST
 LIKE THE SERVICE. THIS IS OK, HOWEVER THE PLANS ARE
 STILL REQUIRED TO SHOW AND INDICATE THE SIZE OF THE OCP
 DEVICE AT UNIT.
 AS THE RESPONSE LETTER IS NOT PART OF THE RECORD SET
 OF PLANS AND IS NOT PART OF THE DESIGN PLANS THE PLANS
 ARE REQUIRED TO CHANGE.
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE TO INDICATE THE OVER CURRENT PROTECTION
 ON THE GENERATOR. PLEASE SEE E5.1 AS AT THIS TIME THE
 CONDUCTORS FROM THE GENERATOR CAN NOT BE VERIFIED PER
 445.13, 310.16 AND 240.4.
  
 12) NOTE: PLEASE SEE NOTICE TO FLORIDA STATUTES
 553.80(2)(B) HAS BEEN ATTACHED WITH RESPECT TO REPEAT
 COMMENTS FOR CODE COMPLIANCE.
 THIS NOTICE STAND FOR ALL TRADES AND IS NOT ONLY FOR
 ELECTRICAL.
 PLEASE KNOW ONE SET OF ELECTRICAL AND MECHANICAL PLANS
 ARE BEING RETAINED BY THIS OFFICE ALONG WITH ONE SET OF
 ENERGY CALCULATIONS.
 ** THIS NOTICE TO FS 553.80 IS ONLY A NOTICE GIVEN AT
 THIS TIME.
  
 *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-11-28 15:36:1911/27/07
  
 ELECTRICAL REVIEW TO COMMENCE ONCE ONE SET OF PLANS
 BECOME AVAILABLE FROM OTHER TRADES CURRENTLY REVIEWING
 PLANS.