| 2007-11-30 13:03:25 | |
| | |
| | |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW |
| | WHICH ARE STILL IN NEED OF ADDRESSING. |
| | PLEASE ALSO SEE NEW COMMENTS BASED ON SOME INFORMATION |
| | ONLY NOW SUBMITTED FOR REVIEW. |
| | |
| | |
| | 1) NOTE: PLEASE PROVIDE AND SUBMIT THE ORIGINAL PERMIT |
| | APPLICATION BACK WITH THE RESUBMITTED PLANS FOR THIS |
| | SCOPE OF WORK. PLEASE SEE THE PERMIT APPLICATION WHICH |
| | WAS SUBMITTED AND PLACED IN PACKAGE WAS FOR PERMIT |
| | #07070314 FOR SITE CLEARANCE AND DEMO/SITE WORK. |
| | |
| | 2) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #5 REQUESTED |
| | THE MANUFACTURES SPECS/CUT SHEETS FOR THE |
| | GENERATOR/FUEL TANK AND ATS TO BE SUBMITTED. THE SHEETS |
| | FOR THE GENERATOR WAS SUBMITTED HOWEVER NOT THE SHEETS |
| | FOR THE ATS. |
| | PLEASE ALSO SEE NO SPECS WERE SUBMITTED FOR FUEL TANK |
| | FOR REVIEW BY FIRE AND MECHANICAL. |
| | PLEASE KNOW THESE ARE REQUIRED AT THIS TIME. PLEASE SEE |
| | COMMENTS FROM OTHER TRADES SUCH AS MECHANICAL FOR |
| | POSSIBLE COMMENTS. |
| | PLEASE PROVIDE MINIMUM CLEARANCE INFORMATION FOR THE |
| | GENERATOR ON ALL SIDES OF UNIT. THE SIDE FACING THE |
| | CONDENSING UNITS SEEMS TO BE LESS THAN THE MINIMUMS |
| | WHICH THIS OFFICE HAS SEEN AS SET-FORTH FROM |
| | MANUFACTURE AND RECOMMENDED CLEARANCES. PLEASE KNOW ALL |
| | CLEARANCES PER NEC 110.26 SHALL ALSO BE REQUIRED. |
| | 110.3, 90.7, |
| | FBC 106.1.2 |
| | |
| | ** FN:BASED ON TANK PROVIDED AND SIZE OF GENERATOR |
| | WITH FUEL CONSUMPTION LISTED ON CUT SHEETS, THIS WILL |
| | NOT PROVIDE THE 72HRS AS STATED. AS THIS IS AN OPTIONAL |
| | STAND-BY SYSTEM, THE TIME IS NOT OF CONCERN HOWEVER |
| | RECORD PLANS SHOULD PROVIDE ALL INFORMATION. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS NOTE #6. PLEASE SUBMIT |
| | COMPLETED ENERGY CALCULATIONS WHICH MEET THE FBC AND |
| | CORRELATE WITH ALL ELECTRICAL DESIGNS FOR LIGHTING |
| | FIXTURESETC ON PLANS. |
| | PLEASE BE SURE ALL FIXTURES ON PLANS COORDINATE WITH |
| | THE INPUT DATA REPORTS FOR ALL INTERIOR AND EXTERIOR |
| | LIGHTING. |
| | PLEASE SEE SOME OF THE FOLLOWING EXAMPLES WHERE THESE |
| | DO NOT CORRELATE. |
| | THE INPUT DATA REPORT WILL BE NOTED AS IDR FOR THE REST |
| | OF THIS COMMENT. |
| | FOR EXAMPLE: PLEASE SEE THE FIRST ITEM ON THE IDR WHICH |
| | IS THE LOBBY LIGHTING WHICH INDICATES A 260W FIXTURE |
| | WHEREAS NEITHER THE PLANS NOR THE FIXTURE LEGEND HAS |
| | ANY 260W FIXTURE. |
| | FOR EXAMPLE: PLEASE SEE THE FIXTURE WS4 WHICH IS ON |
| | PLANS AND FIXTURE LEGEND HOWEVER THE IDR DOES NOT ANY |
| | OF THESE 75W FIXTURES. |
| | FOR EXAMPLE: PLEASE SEE THE EXTERIOR LIGHTING FIXTURES |
| | WD26 WHICH DO APPEAR TO BE ON THE IDR AND/OR WATTAGE |
| | DOES NOT CORRELATE. |
| | FOR EXAMPLE: PLEASE SEE THE TOTAL NUMBER OF *EXTERIOR |
| | LIGHTING FIXTURES* DO NOT CORRELATE WITH THE IDR.THIS |
| | SHOULD INCLUDE ALL LIGHTING FIXTURES EVEN IF THEY ARE |
| | THE 2ND FLOOR EXTERIOR LIGHTS. |
| | FOR EXAMPLE: THE TOTAL SQ FT AND ASSUMPTIONS REQUIRED |
| | FOR SHELL SPACE HAVE NOT AND ARE NOT INCLUDED. |
| | |
| | THESE ARE A FEW EXAMPLES AND NOT ALL ITEMS. PLEASE |
| | CORRELATE ALL REQUIRED INFORMATION AND ALL INFORMATION |
| | ON PLANS WITH THAT OF THE IDR, SUMMARY AND TOTALS ON |
| | THE METHOD *B* AS SUBMITTED. |
| | PLEASE SEE 13-101.1.6, 13-415.2, 13-415.1.B AND ALL |
| | SECTIONS AS GIVEN IN FIRST REVIEW; 13-4, 13-101.1, |
| | 13-414.2(2)(3)M 13-415.1.ABC.2, 13-415.1.ABC.1.4, |
| | 13-415.2.ABC.1.3 ETC. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS NOTE #9 WHICH REQUESTED TO |
| | SUBMIT COMPLETED PHOTO-METRICS FOR EGRESS PATHS |
| | INDICATING THE MINIMUM LIGHTING LEVELS FOR FLAT EGRESS |
| | SURFACES AS WELL AS BOTH STAIR AREAS. PLEASE SEE LS 101 |
| | 7.8.1.3, 7.9.2.2. |
| | PLEASE ALSO SEE THE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-33.004 AS THIS IS REQUIRED. |
| | THE RESPONSE ADDRESSED OTHER PARTS OF PREVIOUS NOTE |
| | HOWEVER THIS WAS NOT ADDRESSED AND NONE WERE SUBMITTED |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | ** PLEASE KNOW AS NO LIGHTING LEVELS WERE SUBMITTED |
| | NONE COULD BE REVIEWED AT THIS TIME. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS NOTE #17 WHICH MENTIONED |
| | FOR ALL A/C CU DISCONNECTS TO MEET 110.26. |
| | THE RESPONSE MENTIONS THIS WILL BE FIELD VERIFIED. THIS |
| | IS CORRECT HOWEVER THE PLANS ARE STILL REQUIRED TO SHOW |
| | MINIMUM CODE COMPLIANCE. |
| | PLEASE SEE UNIT LAYOUT ON E4.2 AS DISCONNECTS ARE STILL |
| | BE SHOWNON TWO WALLS BEHIND UNITS. |
| | ** THIS IS AN ITEM WHICH WOULD NORMALLY BE REDLINED IF |
| | THIS WAS OF THE *MINOR* COMMENTS HOWEVER AS PLANS ARE |
| | COMING BACK FOR OTHER CORRECTIONS PLEASE SHOW *MINIMUM* |
| | CODE COMPLIANCE AT THIS TIME. |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS NOTE #20 FOR MEANS OF |
| | DISCONNECT FOR FEEDERS AT THE MAIN BUILDING FOR THE |
| | FEEDERS FROM THE OUTSIDE MAIN. |
| | THE RESPONSE GIVES A LONG EXPLANATION WHICH GOES INTO |
| | CODES IN CHAPTER 7 WHICH ARE KNOWN TO THIS OFFICE. |
| | PLEASE KNOW THIS PROJECT LOCATION AND BUILDING DOES NOT |
| | MEET THE EXCEPTION FOR UNDER SINGLE MANAGEMENT AND |
| | QUALIFIED PERSONNEL AND DOCUMENTED SAFE DISCONNECTING |
| | PRACTICES. |
| | PLEASE SEE AS STATED ON PREVIOUS COMMENTS; PLEASE |
| | PROVIDE DISCONNECTING MEANS FOR FEEDERS AS REQUIRED PER |
| | 225.31-225.39. |
| | THE SECTIONS GIVEN IN THE RESPONSE LETTER FOR THE |
| | GENERATOR WHICH REFLECTS FEEDERS FROM *OUTDOOR |
| | GENERATOR* SETS FOR 700 AND 701 DO NOT APPLY AS THE |
| | SYSTEM AS SHOWN ON PLANS IS THAT OF 702. THE SECTION |
| | 702.11 IN THE 2005 NEC WAS REVISED TO INCLUDE THE |
| | SECTION WHICH WAS PREVIOUSLY IN 700 AND 701 FOR OUTDOOR |
| | GENERATORS, HOWEVER WHEN SPEAKING OF 702.11 THIS |
| | SECTION REQUIRES THE DISCONNECTING MEANS TO BE * |
| | READILY ACCESSIBLE* AND *WITHIN SIGHT*. PLEASE SEE NEC |
| | 100 FOR DEFINITIONS OF BOTH. THE GENERATOR IS WITHIN |
| | SIGHT(50FT) HOWEVER THE DISCONNECT MEANS DOES NOT |
| | MEET READILY ACCESSIBLE BASED ON PLANS AND INFORMATION |
| | SUBMITTED. |
| | IN EITHER CASE AS STATED ABOVE THE DISCONNECTING MEANS |
| | (W/OUT OCP) FOR THE FEEDERS IS STILL REQUIRED. |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS NOTE #21 FOR GROUNDING |
| | ELECTRODE SYSTEM. RESPONSE MENTIONS TO SEE DETAILS ON |
| | 5.1 AND 7.1 HOWEVER EITHER SHEET DOES NOT PROVIDE THE |
| | INFORMATION NEEDED. WHERE IS THE GROUNDING ELECTRODE |
| | SYSTEM SHOWN FOR THE MAIN SERVICE LOCATION. RISER SHOWS |
| | THAT THERE WILL BE ONE, BUT GROUND RODS, HOW MANY, |
| | SIZE, WHAT TYPE ETC IS NOT SHOWN |
| | MAIN BUILDING DETAIL DOES SHOW TO CONCRETE ENCASED |
| | ELECTRODE BUT IT IS ONLY BEING ASSUMED THAT THIS IS THE |
| | FOOTER STEEL AS REQUIRED. |
| | (DETAIL ON E7.1 MENTIONS THERE WILL BE A GROUND LOOP) |
| | PLEASE PROVIDE MORE INFORMATION OR SHOW DETAIL FOR MAIN |
| | SERVICE GE-SYSTEM PER 250.50,-250.56 |
| | |
| | 8) NOTE: PLEASE SEE PREVIOUS NOTE #23 WHICH SPOKE OF |
| | THE REQUIRED DEDICATED CIRCUITS FOR ELEVATOR MACHINE |
| | ROOMS/PIT HOIST-WAY CIRCUITS. |
| | THE RESPONSE MENTIONS THAT CIRCUIT HP-16 WAS ALREADY |
| | PROVIDED. THIS IS TRUE, THIS CIRCUIT WAS PROVIDE |
| | HOWEVER AS STATED ON PREVIOUS COMMENT, THIS MAY NOT |
| | FEED ANY OTHER LOCATIONS EXCEPT THE AREA IN WHICH IS |
| | STATED IN THE CODE. |
| | PLEASE ALSO SEE THE RESPONSE MENTIONS THAT IT IS THE |
| | CONTRACTORS RESPONSIBILITY TO NOT CONNECT ON THE LOAD |
| | SIDE OF THE GFI. THE PREVIOUS REVIEW COMMENT DID NOT |
| | SAY ANYTHING ABOUT ANY CONNECTIONS TO THE LOAD SIDE OF |
| | THE GFI NOT DID THE COMMENT GIVE A SECTION IN THE CODE |
| | WHICH STATES THIS. |
| | PLEASE SEE THE PLANS. PLEASE SEE SPECIFICALLY SHEET |
| | E4.1, DETAIL #2 E4.1 WHICH SHOWS CIRCUIT HP1-16 FEEDING |
| | BOTH THE ELEVATOR ROOM GFI RECEPTACLES AND ALSO THE |
| | ELEVATOR PIT GFI RECEPTACLES. THESE ARE NOT PERMITTED |
| | AND PLEASE ADJUST CIRCUIT(S). |
| | PLEASE SEE SPECIFICALLY SHEET E4.1 WHICH SHOWS CIRCUIT |
| | HP1-13 FEEDING BOTH THE MAIN ELECTRICAL ROOM LIGHTING |
| | ON FIRST FLOOR AS WELL AS THE LIGHTING IN PIT. |
| | ONCE AGAIN THIS IS NOT PERMITTED AND REQUIRES DEDICATED |
| | CIRCUITS. |
| | PLEASE SEE 620.23 AND 620.24. |
| | |
| | 9) NOTE: PLEASE SEE PREVIOUS NOTE #26. PLEASE PROVIDE |
| | METER CAN SIZES ON BUILDING. PLEASE VERIFY THE 600AMP |
| | METER CAN AS SHOWN. |
| | PLEASE SEE NOTE #26 FROM PREVIOUS REVIEW IS COPIED FOR |
| | SAME CLARIFICATION. |
| | PLEASE PROVIDE NOTE FOR *FLOATING NEUTRAL KIT REQUIRED |
| | * AT THE METERS AT THE BUILDING. 250.6, 250.24 |
| | *************************** |
| | 26) NOTE: PLEASE INDICATE THE SIZE/AMERAGE OF THE METER |
| | CANS ON THE RISER. PLEASE SEE THE METER WHICH IS SHOWN |
| | ONE E-4.2 FOR MAIN IS NOT INCLUDED ON RISER DIAGRAM |
| | SHEET E-5.1. |
| | PLEASE COORDINATE AND ADJUST PLANS AND SHOW SIZES OF |
| | EQUIPMENT. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | ************************ |
| | |
| | 10) NOTE: PLEASE SEE PREVIOUS NOTE #27. PLEASE SHOW AND |
| | INDICATES FEEDERS FROM GUTTER TO METERS, METERS TO |
| | MAINS AT THE BUILDING. |
| | PLEASE INDICATE |
| | ** PREVIOUS REVIEW NOTE ** |
| | 27) NOTE: PLEASE INDICATE THE SIZE OF FEEDERS FROM |
| | WIRE-WAY TO METERS TO MAINS ON E5.1. |
| | 310.16, 215.5, 240.4 |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 11) NOTE: PLEASE SEE PREVIOUS NOTE #28. |
| | THE RESPONSE MENTIONS THIS BREAKER IS 1200AMPS JUST |
| | LIKE THE SERVICE. THIS IS OK, HOWEVER THE PLANS ARE |
| | STILL REQUIRED TO SHOW AND INDICATE THE SIZE OF THE OCP |
| | DEVICE AT UNIT. |
| | AS THE RESPONSE LETTER IS NOT PART OF THE RECORD SET |
| | OF PLANS AND IS NOT PART OF THE DESIGN PLANS THE PLANS |
| | ARE REQUIRED TO CHANGE. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE TO INDICATE THE OVER CURRENT PROTECTION |
| | ON THE GENERATOR. PLEASE SEE E5.1 AS AT THIS TIME THE |
| | CONDUCTORS FROM THE GENERATOR CAN NOT BE VERIFIED PER |
| | 445.13, 310.16 AND 240.4. |
| | |
| | 12) NOTE: PLEASE SEE NOTICE TO FLORIDA STATUTES |
| | 553.80(2)(B) HAS BEEN ATTACHED WITH RESPECT TO REPEAT |
| | COMMENTS FOR CODE COMPLIANCE. |
| | THIS NOTICE STAND FOR ALL TRADES AND IS NOT ONLY FOR |
| | ELECTRICAL. |
| | PLEASE KNOW ONE SET OF ELECTRICAL AND MECHANICAL PLANS |
| | ARE BEING RETAINED BY THIS OFFICE ALONG WITH ONE SET OF |
| | ENERGY CALCULATIONS. |
| | ** THIS NOTICE TO FS 553.80 IS ONLY A NOTICE GIVEN AT |
| | THIS TIME. |
| | |
| | *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-11-28 15:36:19 | 11/27/07 |
| | |
| | ELECTRICAL REVIEW TO COMMENCE ONCE ONE SET OF PLANS |
| | BECOME AVAILABLE FROM OTHER TRADES CURRENTLY REVIEWING |
| | PLANS. |