Plan Review Notes
Plan Review Notes For Permit 07070315
Permit Number 07070315
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-06 18:10:26DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1.ALL SHEETS. THE ADDRESS OF THE PROJECT SHALL BE
 INDICATED IN THE TITLE BLOCK OF EACH SHEET. SECTION
 106.1.1.
  
 2. SHTS 1 THRU 3 OF 3 & 1 THRU 7 OF 7. THE CERTIFICATE
 OF AUTHORIZATION NUMBER, (FIRM LICENSE NUMBER),IS
 REQUIRED IN THE TITLE BLOCK OF EACH SHEET AS WELL AS
 THE DATED SEAL, SIGNATURE, AND PRINTED NAME OF THE
 PERSON SEALING THE DOCUMENT. FAC 61G1-16.003,
 61G1-16.004(2)(6) AND FS 481.219, 481.2055.--IT
 APPEARS THAT THE PLANS HAVE BEEN SIGNED WITH A
 INITIALS, NOT A SIGNATURE. IF INDEED THIS IS THE LEGAL
 SIGNATURE OF THE ENGINEER, THEN A SIGNED, SEALED,
 LEGALLY NOTORIZED LETTER INDICATING THE LEGAL ADDRESS
 OF THE LANDSCAPE ARCHITECT SHALL BE SUBMITTED FOR OUR
 FILES.
  
 3. SHT 1 0F 1. THE CERTIFICATE OF AUTHORIZATION NUMBER,
 (FIRM LICENSE NUMBER),IS REQUIRED IN THE TITLE BLOCK
 OF EACH SHEET AS WELL AS THE DATED SEAL, SIGNATURE, AND
 PRINTED NAME OF THE PERSON SEALING THE DOCUMENT. FAC
 61G1-16.003, 61G1-16.004(2)(6) AND FS 481.219,
 481.2055.--THE SHEET HAS NOT BEEN SIGNED, SEALED &
 DATED ALSO. SECTION 106.1.
  
 4. SHT A-1.0 PER TABLE 403.1, MINIMUM FIXTURE
 REQUIREMENTS FOR THE FIRST FLOOR INCLUDE 4 W/C'S, 3
 LAVS & 2 DRINKING FOUNTAINS. PLEASE INDICATE MINIMUM
 FACILITIES.
  
 5. SHT A-2.0 PER TABLE 403.1, TWO DRINKING FOUNTAINS
 ARE REQUIRED. ONLY ONE IS SHOWN ON THE FLOOR PLAN.
 PLEASE INDICATE THE LOCATION OF TWO DRINKING FOUNTAINS
 ON THE FLOOR PLAN.
  
 6. SHT A-2.0 KEY NOTE #11 NOT FOUND. PLEASE INDICATE
 THE ROOM NUMBER KEY NOT CAN BE LOCATED. SECTION
 106.1.1.
  
 7. SHTS A-2.0, A-2.1, A-2.4, A-3.0 (DETAIL #2)AND SHT
 P1.2. PER SECTION 11-4.17.3 EXCEPTION NEW CONSTRUCTION
 (2), THE ACCESSIBLE W/C SHALL BE LOCATED IN THE CORNER
 DIAGONAL TO THE DOOR. THE W/C IN THE ACCESSIBLE STALL
 IN THE WOMENS TOILET ROOM (225) DOES NOT MEET THIS
 REQUIREMENT. PLEASE MOVE DOOR OR W/C TO COMPLY.
  
 8. SHT A-3.0 DETAIL #3 TOI.ET ROOMS SHALL BE
 ACCESSIBLE. SHOW COMPLIANCE WITH SECTION 11-4.22 AND
 ALL SUBSECTIONS.
  
 9. SHT A-3.0 DETAILS #5 & #6 SINKS SHALL BE ACCESSIBLE.
 SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.--THE GARBAGE DISPOSALS SHALL BE ADA
 COMPLIANT. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS
 WITH INSTALLATION INSTRUCTIONS. SECTION 106.1.2 MORE
 INFORMATION REQD.
  
 10. SHT A-9.0 DETAILS #2 & #5 THE FLUSH CONTROL FOR THE
 W/C SHALL BE TO THE WIDE SIDE OF THE W/C PER SECTION
 11-4.16.5. PLEASE SHOW ON DETAILS.
  
 11. SHT A-9.0 DETAIL #6 SINK SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
  
 12. SHT A-9.0 DETAIL #12 THE URINAL SHALL BE
 ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH SECTION
 11-4.18.4, MAX HEIGHT FOR FLUSH CONTROLS. (44").
  
 13. SHT A-9.0 DETAIL #12 THE LAVS SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH SECTIONS 11-4.19.4 EXPOSED
 PIPES & SURFACES, AND 11-4.19.5 FAUCETS.
  
 14. SHT A-9.1 DETAIL #3 SINK SHALL BE ACCESSIBLE.
 PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL
 SUBSECTIONS.
  
 15. SHTS S-1 THRU S-6 THE ENGINEER SHALL LEGIBLY
 INDICATE THEIR ADDRESS IN THE TITLE BLOCK. FAC
 61G15-23.002(2) & FS 471.025.
  
 16. ALL M, E, P & FP SHEETS. THE ENGINEER SHALL LEGIBLY
 INDICATE THEIR ADDRESS AND IF PRACTICING THROUGH A DULY
 AUTHORIZED ENGINEERING BUSINESS, THE ADDRESS OF THE
 ENGINEERING BUSINESS IS REQUIRED AS WELL. FAC
 61G15-23.002(2) & FS 471.025. AS SHOWN, THE ADDRESS OF
 THE ENGINEER IS SHOWN, BUT THE ADDRESS OF THE
 ENGINEERING BUSINESS, (INDICATED AS 797 ANDREWS AVE.,
 DELRAY BEACH ON THE FLORIDA STATE DBPR WEBSITE), IS NOT
 SHOWN IN THE TITLE BLOCKS. (SEE ATTACHED SHEET). PLEASE
 INCLUDE THE BUSINESS ADDRESS IN THE TITLE BLOCKS. IF
 THE ADDRESS IS DIFFERENT FROM THE DBPR WEBSITE, PLEASE
 UPDATE THE DBPR WEBSITE PRIOR TO RESUBMITTING FOR
 REVIEW AT THE CITY WPB.
  
 17. SHT P0.3 ABBREIVIATIONS RRW & RRWR ARE NOT
 INDICATED IN THE LIST OF ABBREIVIATIONS ON SHT P0.1.
 PLEASE CLARIFY WHAT THE ABBREIVIATIONS STAND FOR.
 SECTION 106.1.2.
  
 18. SHT P1.1 NOTE: 3" FROM RAIN WATER PIPING. REFER
 ARCHITECTURAL FOR CONT. & DETAILS. PLEASE INDICATE
 WHERE ON THE ARCHITECTURAL SHEETS THIS CAN BE FOUND.
 SECTION 106.1.2.
  
 19. SHT P1.1 KEYED NOTES #12 IS NOT INDICATED ON THE
 FLOOR PLAN. PLEASE INDICATE WHERE #12 CAN BE FOUND.--
 THE SANITARY RISER NEXT TO STAIR #2 IS NOT IDENTIFIED.
 PLEASE IDENTIFY THIS RISER. SECTION 106.1.1.
  
 20. SHT P1.1 FLOOR DRAIN IN THE ELEVATOR MACHINE ROOM.
 SECTION 301.6. PLEASE DELETE FROM FLOOR PLAN & SANITARY
 RISER DIAGRAM.
  
 21. SHT P1.2 VENT FROM EWC BY THE WATER HEATER DOES NOT
 CONNECT TO OR SHOW VTR. PLEASE CLARIFY. SECTIONS
 106.1.1 AND 901.2.1.
  
 22. SHT P5.1 DOMESTIC WATER RISER DIAGRAM FOR RRW &
 RRWR DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE
 RISER AND FLOOR PLAN. SECTION 106.1.1.
  
 23. SHT P5.1 DOMESTIC WATER RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. PIPING AT THE BAR SINK, THE
 JANITOR SINK. THE LINE TO THE HOSE BIBB THAT ALSO
 INDICATES A LINE THAT CONNECTS TO THE RRW LINE IS NOT
 SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 24. SHT P5.1 THE CHECK VALVE SHOWN BETWEEN THE DCW AND
 THE RRW IS NOT APPROVED. AN RPZV BACKFLOW IS REQUIRED
 FOR PROTECTION OF THE POTABLE WATER FROM A POSSIBLE
 CROSS CONNECTION. SECTION 608.13.2.
  
 25. SHT P5.1 THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN. FUTURE 4" LINE FOR TENANT 2 IS
 SHOWN ON THE 2ND FLOOR OF THE THE RISER DIAGRAM.--
 THE FLOOR DRAIN SHOWN ON THE FLOOR PLAN NEAR ROOM 105
 IS NOT SHOWN ON THE SANT. RISER DIAGRAM.--THE
 CLEANOUT SHOWN ON THE FLOOR PLAN DOWNSTREAM OF THE LAV
 IN THE WOMENS TOILET ROOM 2ND FLOOR IS NOT SHOWN ON THE
 RISER DIAGRAM.--ONLY ONE EWC IS INDICATED. THE EWC
 BY THE RECEPTION AREA IS NOT SHOWN ON THE RISER
 DIAGRAM.--RISER SHOWS AN EXTRA FLOOR DRAIN AND VENT
 UPSTREAM OF THE ONE SHOWN IN THE ELEVATOR MACHINE ROOM,
 (TO BE DELETED PER SECTION 301.6).--NOTE #3 AT THE
 TWO WAY CLEANOUT NEAR THE JUNCTION OF THE BUILDING
 DRAIN AND THE BUILDING SEWER DOES NOT REFLECT KEY NOTE
 #3. PLEASE CHECK THAT THE RISER DIAGRAM. CORRELATES
 WITH THE FLOOR PLAN. SECTION 106.1.1.
  
 26. SHT P5.1 KEY NOTE 11 PAN DRAIN NOT SHOWN. CORRELATE
 NOTE AND RISER DIAGRAM. SECTION 106.1.1.
  
 27. SHT P5.1 KEY NOTE 16. TWO PUMPS ARE SHOWN. PLEASE
 CLARIFY. SUBMIT A DETAIL FOR THE PIPING TO THE PUMPS AT
 THE CISTERN. SECTION 106.1.2.
  
 28. SUBMIT MANUF. SPECIFICATION SHEETS FOR ALL PUMPS.
 SHEETS SHALL SHOW A LISTING AND MANUF. INSTALLATION
 INSTRUCTIONS. SECTION 303.4.
  
 29. DURING A CONVERSATION WITH THE ELECTRICAL PLAN
 REVIEWER, IT WAS BROUGHT TO MY ATTENTION THAT THE HOUSE
 PANEL ON SHT E8.1 ONLY SHOWS ONE BOOSTER PUMP AND ONE
 RECIRCULATION PUMP. TWO OF EACH PUMP ARE SHOWN ON THE
 PLUMBING SHEET P5.1. PLEASE CLARIFY. SECTION 106.1.1.
  
 30. SHT P5.1 KEY NOTES 14 INDICATES A WATER FILTER.
 PLEASE EXPLAIN THE 2 VFD'S TO THE LEFT OF THE FILTER.
 SECTION 106.1.2 MORE INFORMATION REQUIRED.
  
 31. SHT P5.1 KEY NOTE 2 INDICATES A CLEANOUT 36" BELOW
 THE FINISH FLOOR. SECTION 708.4 REQUIRES THAT CLEANOUTS
 SHALL BE EXTENDED THROUGH AND SHALL TERMINATE FLUSH
 WITH THE FINISHED FLOOR. PLEASE CORRECT KEY NOTE.
  
 32. SUBMIT A CONDENSATE ISOMETRIC RISER DIAGRAM. SHOW
 ALL PIPE SIZES AND INDICATE VENTS. SECTION
 106.3.5.1.3(13).
  
 33. THE APPLICATION STATES "DESCRIBE PROJECT IN DETAIL"
 (FAILURE TO DO SO MAY RESULT IN DELAYS). IT APPEARS
 THAT THE SECOND FLOOR WILL BE BUILT OUT,BUT THE FIRST
 FLOOR WILL BE SHELL ONLY WITH THIS PERMIT. THIS IS NOT
 INDICATED ON THE PERMIT APPLICATION, (NEW BUILD).
 PLEASE INDICATE THE SCOPE OF WORK FOR THIS PERMIT AS
 REQUIRED ON THE APPLICATION.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved