| Date |
Text |
| 2007-09-06 18:10:26 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1.ALL SHEETS. THE ADDRESS OF THE PROJECT SHALL BE |
| | INDICATED IN THE TITLE BLOCK OF EACH SHEET. SECTION |
| | 106.1.1. |
| | |
| | 2. SHTS 1 THRU 3 OF 3 & 1 THRU 7 OF 7. THE CERTIFICATE |
| | OF AUTHORIZATION NUMBER, (FIRM LICENSE NUMBER),IS |
| | REQUIRED IN THE TITLE BLOCK OF EACH SHEET AS WELL AS |
| | THE DATED SEAL, SIGNATURE, AND PRINTED NAME OF THE |
| | PERSON SEALING THE DOCUMENT. FAC 61G1-16.003, |
| | 61G1-16.004(2)(6) AND FS 481.219, 481.2055.--IT |
| | APPEARS THAT THE PLANS HAVE BEEN SIGNED WITH A |
| | INITIALS, NOT A SIGNATURE. IF INDEED THIS IS THE LEGAL |
| | SIGNATURE OF THE ENGINEER, THEN A SIGNED, SEALED, |
| | LEGALLY NOTORIZED LETTER INDICATING THE LEGAL ADDRESS |
| | OF THE LANDSCAPE ARCHITECT SHALL BE SUBMITTED FOR OUR |
| | FILES. |
| | |
| | 3. SHT 1 0F 1. THE CERTIFICATE OF AUTHORIZATION NUMBER, |
| | (FIRM LICENSE NUMBER),IS REQUIRED IN THE TITLE BLOCK |
| | OF EACH SHEET AS WELL AS THE DATED SEAL, SIGNATURE, AND |
| | PRINTED NAME OF THE PERSON SEALING THE DOCUMENT. FAC |
| | 61G1-16.003, 61G1-16.004(2)(6) AND FS 481.219, |
| | 481.2055.--THE SHEET HAS NOT BEEN SIGNED, SEALED & |
| | DATED ALSO. SECTION 106.1. |
| | |
| | 4. SHT A-1.0 PER TABLE 403.1, MINIMUM FIXTURE |
| | REQUIREMENTS FOR THE FIRST FLOOR INCLUDE 4 W/C'S, 3 |
| | LAVS & 2 DRINKING FOUNTAINS. PLEASE INDICATE MINIMUM |
| | FACILITIES. |
| | |
| | 5. SHT A-2.0 PER TABLE 403.1, TWO DRINKING FOUNTAINS |
| | ARE REQUIRED. ONLY ONE IS SHOWN ON THE FLOOR PLAN. |
| | PLEASE INDICATE THE LOCATION OF TWO DRINKING FOUNTAINS |
| | ON THE FLOOR PLAN. |
| | |
| | 6. SHT A-2.0 KEY NOTE #11 NOT FOUND. PLEASE INDICATE |
| | THE ROOM NUMBER KEY NOT CAN BE LOCATED. SECTION |
| | 106.1.1. |
| | |
| | 7. SHTS A-2.0, A-2.1, A-2.4, A-3.0 (DETAIL #2)AND SHT |
| | P1.2. PER SECTION 11-4.17.3 EXCEPTION NEW CONSTRUCTION |
| | (2), THE ACCESSIBLE W/C SHALL BE LOCATED IN THE CORNER |
| | DIAGONAL TO THE DOOR. THE W/C IN THE ACCESSIBLE STALL |
| | IN THE WOMENS TOILET ROOM (225) DOES NOT MEET THIS |
| | REQUIREMENT. PLEASE MOVE DOOR OR W/C TO COMPLY. |
| | |
| | 8. SHT A-3.0 DETAIL #3 TOI.ET ROOMS SHALL BE |
| | ACCESSIBLE. SHOW COMPLIANCE WITH SECTION 11-4.22 AND |
| | ALL SUBSECTIONS. |
| | |
| | 9. SHT A-3.0 DETAILS #5 & #6 SINKS SHALL BE ACCESSIBLE. |
| | SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS.--THE GARBAGE DISPOSALS SHALL BE ADA |
| | COMPLIANT. PLEASE SUBMIT MANUF. SPECIFICATION SHEETS |
| | WITH INSTALLATION INSTRUCTIONS. SECTION 106.1.2 MORE |
| | INFORMATION REQD. |
| | |
| | 10. SHT A-9.0 DETAILS #2 & #5 THE FLUSH CONTROL FOR THE |
| | W/C SHALL BE TO THE WIDE SIDE OF THE W/C PER SECTION |
| | 11-4.16.5. PLEASE SHOW ON DETAILS. |
| | |
| | 11. SHT A-9.0 DETAIL #6 SINK SHALL BE ACCESSIBLE. |
| | PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. |
| | |
| | 12. SHT A-9.0 DETAIL #12 THE URINAL SHALL BE |
| | ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH SECTION |
| | 11-4.18.4, MAX HEIGHT FOR FLUSH CONTROLS. (44"). |
| | |
| | 13. SHT A-9.0 DETAIL #12 THE LAVS SHALL BE ACCESSIBLE. |
| | PLEASE SHOW COMPLIANCE WITH SECTIONS 11-4.19.4 EXPOSED |
| | PIPES & SURFACES, AND 11-4.19.5 FAUCETS. |
| | |
| | 14. SHT A-9.1 DETAIL #3 SINK SHALL BE ACCESSIBLE. |
| | PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24 AND ALL |
| | SUBSECTIONS. |
| | |
| | 15. SHTS S-1 THRU S-6 THE ENGINEER SHALL LEGIBLY |
| | INDICATE THEIR ADDRESS IN THE TITLE BLOCK. FAC |
| | 61G15-23.002(2) & FS 471.025. |
| | |
| | 16. ALL M, E, P & FP SHEETS. THE ENGINEER SHALL LEGIBLY |
| | INDICATE THEIR ADDRESS AND IF PRACTICING THROUGH A DULY |
| | AUTHORIZED ENGINEERING BUSINESS, THE ADDRESS OF THE |
| | ENGINEERING BUSINESS IS REQUIRED AS WELL. FAC |
| | 61G15-23.002(2) & FS 471.025. AS SHOWN, THE ADDRESS OF |
| | THE ENGINEER IS SHOWN, BUT THE ADDRESS OF THE |
| | ENGINEERING BUSINESS, (INDICATED AS 797 ANDREWS AVE., |
| | DELRAY BEACH ON THE FLORIDA STATE DBPR WEBSITE), IS NOT |
| | SHOWN IN THE TITLE BLOCKS. (SEE ATTACHED SHEET). PLEASE |
| | INCLUDE THE BUSINESS ADDRESS IN THE TITLE BLOCKS. IF |
| | THE ADDRESS IS DIFFERENT FROM THE DBPR WEBSITE, PLEASE |
| | UPDATE THE DBPR WEBSITE PRIOR TO RESUBMITTING FOR |
| | REVIEW AT THE CITY WPB. |
| | |
| | 17. SHT P0.3 ABBREIVIATIONS RRW & RRWR ARE NOT |
| | INDICATED IN THE LIST OF ABBREIVIATIONS ON SHT P0.1. |
| | PLEASE CLARIFY WHAT THE ABBREIVIATIONS STAND FOR. |
| | SECTION 106.1.2. |
| | |
| | 18. SHT P1.1 NOTE: 3" FROM RAIN WATER PIPING. REFER |
| | ARCHITECTURAL FOR CONT. & DETAILS. PLEASE INDICATE |
| | WHERE ON THE ARCHITECTURAL SHEETS THIS CAN BE FOUND. |
| | SECTION 106.1.2. |
| | |
| | 19. SHT P1.1 KEYED NOTES #12 IS NOT INDICATED ON THE |
| | FLOOR PLAN. PLEASE INDICATE WHERE #12 CAN BE FOUND.-- |
| | THE SANITARY RISER NEXT TO STAIR #2 IS NOT IDENTIFIED. |
| | PLEASE IDENTIFY THIS RISER. SECTION 106.1.1. |
| | |
| | 20. SHT P1.1 FLOOR DRAIN IN THE ELEVATOR MACHINE ROOM. |
| | SECTION 301.6. PLEASE DELETE FROM FLOOR PLAN & SANITARY |
| | RISER DIAGRAM. |
| | |
| | 21. SHT P1.2 VENT FROM EWC BY THE WATER HEATER DOES NOT |
| | CONNECT TO OR SHOW VTR. PLEASE CLARIFY. SECTIONS |
| | 106.1.1 AND 901.2.1. |
| | |
| | 22. SHT P5.1 DOMESTIC WATER RISER DIAGRAM FOR RRW & |
| | RRWR DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE |
| | RISER AND FLOOR PLAN. SECTION 106.1.1. |
| | |
| | 23. SHT P5.1 DOMESTIC WATER RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. PIPING AT THE BAR SINK, THE |
| | JANITOR SINK. THE LINE TO THE HOSE BIBB THAT ALSO |
| | INDICATES A LINE THAT CONNECTS TO THE RRW LINE IS NOT |
| | SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 24. SHT P5.1 THE CHECK VALVE SHOWN BETWEEN THE DCW AND |
| | THE RRW IS NOT APPROVED. AN RPZV BACKFLOW IS REQUIRED |
| | FOR PROTECTION OF THE POTABLE WATER FROM A POSSIBLE |
| | CROSS CONNECTION. SECTION 608.13.2. |
| | |
| | 25. SHT P5.1 THE SANITARY RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN. FUTURE 4" LINE FOR TENANT 2 IS |
| | SHOWN ON THE 2ND FLOOR OF THE THE RISER DIAGRAM.-- |
| | THE FLOOR DRAIN SHOWN ON THE FLOOR PLAN NEAR ROOM 105 |
| | IS NOT SHOWN ON THE SANT. RISER DIAGRAM.--THE |
| | CLEANOUT SHOWN ON THE FLOOR PLAN DOWNSTREAM OF THE LAV |
| | IN THE WOMENS TOILET ROOM 2ND FLOOR IS NOT SHOWN ON THE |
| | RISER DIAGRAM.--ONLY ONE EWC IS INDICATED. THE EWC |
| | BY THE RECEPTION AREA IS NOT SHOWN ON THE RISER |
| | DIAGRAM.--RISER SHOWS AN EXTRA FLOOR DRAIN AND VENT |
| | UPSTREAM OF THE ONE SHOWN IN THE ELEVATOR MACHINE ROOM, |
| | (TO BE DELETED PER SECTION 301.6).--NOTE #3 AT THE |
| | TWO WAY CLEANOUT NEAR THE JUNCTION OF THE BUILDING |
| | DRAIN AND THE BUILDING SEWER DOES NOT REFLECT KEY NOTE |
| | #3. PLEASE CHECK THAT THE RISER DIAGRAM. CORRELATES |
| | WITH THE FLOOR PLAN. SECTION 106.1.1. |
| | |
| | 26. SHT P5.1 KEY NOTE 11 PAN DRAIN NOT SHOWN. CORRELATE |
| | NOTE AND RISER DIAGRAM. SECTION 106.1.1. |
| | |
| | 27. SHT P5.1 KEY NOTE 16. TWO PUMPS ARE SHOWN. PLEASE |
| | CLARIFY. SUBMIT A DETAIL FOR THE PIPING TO THE PUMPS AT |
| | THE CISTERN. SECTION 106.1.2. |
| | |
| | 28. SUBMIT MANUF. SPECIFICATION SHEETS FOR ALL PUMPS. |
| | SHEETS SHALL SHOW A LISTING AND MANUF. INSTALLATION |
| | INSTRUCTIONS. SECTION 303.4. |
| | |
| | 29. DURING A CONVERSATION WITH THE ELECTRICAL PLAN |
| | REVIEWER, IT WAS BROUGHT TO MY ATTENTION THAT THE HOUSE |
| | PANEL ON SHT E8.1 ONLY SHOWS ONE BOOSTER PUMP AND ONE |
| | RECIRCULATION PUMP. TWO OF EACH PUMP ARE SHOWN ON THE |
| | PLUMBING SHEET P5.1. PLEASE CLARIFY. SECTION 106.1.1. |
| | |
| | 30. SHT P5.1 KEY NOTES 14 INDICATES A WATER FILTER. |
| | PLEASE EXPLAIN THE 2 VFD'S TO THE LEFT OF THE FILTER. |
| | SECTION 106.1.2 MORE INFORMATION REQUIRED. |
| | |
| | 31. SHT P5.1 KEY NOTE 2 INDICATES A CLEANOUT 36" BELOW |
| | THE FINISH FLOOR. SECTION 708.4 REQUIRES THAT CLEANOUTS |
| | SHALL BE EXTENDED THROUGH AND SHALL TERMINATE FLUSH |
| | WITH THE FINISHED FLOOR. PLEASE CORRECT KEY NOTE. |
| | |
| | 32. SUBMIT A CONDENSATE ISOMETRIC RISER DIAGRAM. SHOW |
| | ALL PIPE SIZES AND INDICATE VENTS. SECTION |
| | 106.3.5.1.3(13). |
| | |
| | 33. THE APPLICATION STATES "DESCRIBE PROJECT IN DETAIL" |
| | (FAILURE TO DO SO MAY RESULT IN DELAYS). IT APPEARS |
| | THAT THE SECOND FLOOR WILL BE BUILT OUT,BUT THE FIRST |
| | FLOOR WILL BE SHELL ONLY WITH THIS PERMIT. THIS IS NOT |
| | INDICATED ON THE PERMIT APPLICATION, (NEW BUILD). |
| | PLEASE INDICATE THE SCOPE OF WORK FOR THIS PERMIT AS |
| | REQUIRED ON THE APPLICATION. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |