2007-08-08 18:20:10REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 AMENDMENTS FBC
 CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M0.2 MECHANICAL EQUIPMENT NOTE #13: DUCT SMOKE
 DETECTORS SHALL BE CONNECTED TO THE FIRE ALARM SYSTEM
 PER FBC,M 606.4.1. EITHER A SUPERVISORY SIGNAL AT A
 CONSTANTLY ATTENDED LOCATION OR ACTIVATION OF THE
 BUILDING'S ALARM NOTIFICATION DEVICES IS ACCEPTABBLE
 UNDER THIS CODE. HOWEVER, THE DESIGNER SHOULD CHECK
 WITH THE WEST PALM BEACH FIRE PREVENTION BUREAU (FIRE
 MARSHAL'S OFFICE) TO DETERMINE THEIR REQUIREMENTS FOR
 NOTIFICATION UPON ACTIVATION OF THE DETECTORS.
  
 2. M0.3: PROVIDE INFORMATION FROM EQUIPMENT
 MANUFACTURER SHOWING REQUIRED CLEARANCES OF OUTDOOR
 EQUIPMENT FOR SERVICE, MAINTENANCE AND REQUIRED AIRFLOW
 FOR EFFICIENT OPERATION. FBC 106.1.2
  
 3. M1.1: KEYED NOTES 2 AND 4, ONLY TWO OF THE FIVE 2ND
 FLOOR DUCT PENETRATIONS SHOW FIRE DAMPERS. FIRE DAMPERS
 ARE REQUIRED AT ALL DUCT PENETRATIONS OF 2ND FLOOR SLAB
 PER FBC,M 607.6. THE SPECIFIC LOCATION OF EACH FIRE
 DAMPER SHALL BE SHOWN AND PROPERLY IDENTIFIED ON PLANS
 BY THE DESIGNER. FBC,M 607.8
  
 4. M1.1: REFRIGERANT LINES THROUGH 1ST FLOOR SLAB
 APPEAR TO PASS THROUGH STRUCTURAL FOOTERS IN TWO
 LOCATIONS. PROVIDE DETAIL SHOWING SIZE AND NUMBER OF
 SLEEVES GOING THROUGH THE FOOTERS FOR STRUCTURAL
 REVIEW. FBC 106.1.2
  
 5. M1.2: REFRIGERANT LINES FROM 1ST FLOOR ARE SHOWN IN
 2 REFIRGERANT CHASES. THE CHASES ARE NOT SHOWN AS FIRE
 RATED ON ARCHITECTURAL PLANS. THESE PENETRATIONS SHALL
 BE PROTECTED IN A FIRE RESISTANCE RATED ASSEMBLY PER
 FBC 712.4.1.1 OR PROTECTED BY AN APPROVED THROUGH
 PENETRATION FIRESTOP SYSTEM PER FBC 712.4.1.2. PROVIDE
 DETAIL AND TYPE OF ASSEMBLY TO BE USED.
  
 6.PROVIDE SUBMITTALS/INSTRUCTIONS FOR TITUS BYPASS
 TERMINALS.
  
 7. M1.2: KEY NOTE #9, THE 12X12 DUCT FROM 1ST FLOOR TO
 ROOF NEAR 2AHU-10 APPEARS TO PASS THROUGH THE 18X12
 RETURN DUCT. THESE DUCTS DO NOT LOOK LIKE THEY ARE
 INTENDED TO BE CONNECTED, BUT THAT'S HOW THEY APPEAR ON
 FLOOR PLAN. PLEASE CLARIFY.
  
 8. M7.1 DETAIL 7: FIRE DAMPERS LOCATED WITHIN AIR
 DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN ACCORDANCE
 WITH THE REQUIREMENTS OF THIS SECTION, AND THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS AND LISTING
 PER FBC,M 607.2. IF THIS DETAIL IS NOT FROM THE
 MANUFACTURER, IT IS NOT ACCEPTABLE AND THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS MUST BE
 PROVIDED.
  
 9. M7.2 DETAIL 3: SHOW CONDENSING UNIT ATTACHMENT TO BE
 DESIGNED FOR THE 140 MPH WIND ZONE PER FBC,M 301.13 AND
 FBC CH.16
  
 10. ENERGY CALCULATIONS: PROJECT SUMMARY INDICATES MAX
 TONNAGE AT 3.4. THE LARGEST SYSTEM SHOWN ON PLANS IS 5
 TONS. ALSO, THE OWNER'S NAME AND THE ADDRESS OF THE
 PROJECT ARE MISSING. PLEASE CORRECT.
  
 11. ENERGY CALCULATIONS: FORM 400A HAS BEEN USED FOR
 THIS BUILDING. HOWEVER, EITHER METHOD B OR C SHALL BE
 USED. PLEASE SEE THE FOLLOWING REQUIREMENTS FOR ENERGY
 CALCULATIONS FOR SHELL BUILDINGS:
 "NONRESIDENTIAL BUILDINGS THAT ARE PERMITTED PRIOR TO
 DESIGN COMPLETION OR WHICH WILL BE FINISHED IN SECTIONS
 AT A TIME AFTER CONSTRUCTION OF THE SHELL SHALL COMPLY
 WITH EITHER METHOD B OR C OF SUBCHAPTER 13-4 OF THE
 CODE PRIOR TO GRANTING OF A PERMIT TO BUILD. ALL
 ASSUMPTIONS MADE ABOUT FEATURES NOT INSTALLED UNTIL
 LATER THAT ARE NOT ON THE BUILDING PLANS SHALL BE
 LISTED AND APPENDED TO THE COMPLIANCE FORM SUBMITTED TO
 THE BUILDING DEPARTMENT. UNLESS THE BUILDING IS
 COMPLETED AS PER ALL ASSUMPTIONS MADE IN THE ORIGINAL
 CODE COMPLIANCE SUBMITTAL, A REVISED CODE SUBMITTAL(S)
 USING METHODS A, B OR C SHALL BE SUBMITTED WHEN
 COMPLETION OF THE BUILDING (OR PART OF THE BUILDING) IS
 PERMITTED." FBC 13-101.1.6
  
 12. PROVIDE AN AIR BALANCE SCHEDULE FOR THE SPACES
 BEING CONDITIONED TO ASSURE THAT THE BUILDING IS
 PRESSURIZED WITH RESPECT TO THE OUTDOORS. FBC
 13-409.1.ABC.2
  
 13. PROVIDE SHUTOFF DAMPER CONTROLS THAT WILL
 AUTOMATICALLY SHUT WHEN SYSTEMS OR SPACES SERVED ARE
 NOT IN USE. FBC 13-409.1.ABC.3.3
  
 14. PROVIDE ALL RELEVANT SUBMITTAL DATA FOR THE
 PROPOSED GENERATOR, INCLUDING INFORMATION ON FUEL
 STORAGE TANK TO BE USED.
 NOTE: GENERATORS ARE TO BE INSTALLED IN CONPLIANCE WITH
 NFPA 37-02. FUEL GAS PERMIT AND PBC DERM APPROVAL MAY
 BE REQUIRED.
  