Plan Review Notes
Plan Review Notes For Permit 07070315
Permit Number 07070315
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-15 11:15:06*****DENIED*****
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 03.THE RELOCATED FIRE HYDRANTS SHALL BE INSTALLED,
 COMPLETED, AND IN SERVICE PRIOR TO CONSTRUCTION WORK,
  
 04.LANDSCAPING SHALL NOT INTERFERE OR HINDER ACCESS
 TO FIRE PROTECTION EQUIPMENT AND DEVICES.
  
 05.NFPA 101, LIFE SAFETY CODE, 2003 EDITION AND THE
 FLORIDA FIRE PREVENTION CODE 2004 SHALL BE REFERENCED.
 THESE REFERENCES ARE INCORRECTLY SHOWN AS ONE LISTED ON
 THE LIFE SAFETY SHEETS.
  
 06.ON THE LIFE SAFETY SHEETS (LS-1 & LS-2), CLASS "D"
 FINISHES FOR ROOMS AND ENCLOSED SPACES IS LISTED.AS
 PER 38.3.3.2.2 , CLASS A, B, OR C SHALL BE LISTED IN
 THESE OTHER AREAS.
  
 07.ON SHEET LS-2, REFERENCE IS INCORRECTLY MADE TO
 1ST FLOOR - LIFE SAFETY.
  
 08.ON SHEET LS-2, PLEASE EXPLAIN RATIONALE FOR ONLY
 SHOWING TRAVEL DISTANCE TO ONLY 1 OF THE 2 STAIRWELLS.
  
 09.SPECIFY THE INTERIOR FLOOR FINISH FOR THE EXIT
 ENCLOSURES IN TERMS OF CLASS I OR CLASS II.
  
 10.PLEASE PROVIDE FLAME SPREAD DETAILS ON THE FABRIC
 OF THE PARKING CANOPY.
  
 11.HOW WILL THE INSTALLATION OF THE CARD ACCESS
 SYSTEM (CARD READERS) IMPACT ANY EXITING FROM THE EXIT
 STAIRWAYS?PLEASE BE ADVISED THAT SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED FOR CARD ACCESS SYSTEM.
  
 12.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE
 NUMERICAL ADDRESS ON THE BUILDING TO BE VISIBLE FROM
 IBIS BOULEVARD.AS PER WEST PALM BEACH CODE, THE
 NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS
 THAN 1" IN WIDTH.
  
 13.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW THE
 LOCATION OF THE KNOX BOX.FOR APPLICATIONS, CONTACT
 WEST PALM BEACH FIRE PREVENTION BUREAU AT
 561-804-4724.
  
 14.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE STAIR
 HANDRAILS/GUARD RAILS.
  
 15.SHOW/VERIFY THAT THE HEADROOM ON STAIRS SHALL NOT
 BE LESS THAN 80" AND SHALL BE MEASURED VERTICALLY ABOVE
 A PLANE PARELLEL TO AND TANGENT WITH THE MOST FORWARD
 PROJECTION OF THE STAIR DETAIL.
  
 16.NO TAMPER SWITCH (TS) AND FLOW SWITCH (FS) SHOWN
 ON THE FA1.1 SHEET.
  
 17.FIRE DEPARTMENT CONNECTION (FDC) SHALL BE EQUIPPED
 WITH KNOX LOCKING CAPS.FOR APPLICATIONS, CONTACT
 WEST PALM BEACH FIRE PREVENTION BUREAU AT
 561-804-4724.
  
 18.ELECTRONIC SWITCHES, CHAIN AND LOCK SHALL BE
 REQUIRED ON THE FIRE LINE BACKFLOW DEVICE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722