| 2007-10-15 11:15:06 | *****DENIED***** |
| | |
| | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 02.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE |
| | TITLE BLOCK OF EACH SUBMITTED PLAN SHEET. |
| | |
| | 03.THE RELOCATED FIRE HYDRANTS SHALL BE INSTALLED, |
| | COMPLETED, AND IN SERVICE PRIOR TO CONSTRUCTION WORK, |
| | |
| | 04.LANDSCAPING SHALL NOT INTERFERE OR HINDER ACCESS |
| | TO FIRE PROTECTION EQUIPMENT AND DEVICES. |
| | |
| | 05.NFPA 101, LIFE SAFETY CODE, 2003 EDITION AND THE |
| | FLORIDA FIRE PREVENTION CODE 2004 SHALL BE REFERENCED. |
| | THESE REFERENCES ARE INCORRECTLY SHOWN AS ONE LISTED ON |
| | THE LIFE SAFETY SHEETS. |
| | |
| | 06.ON THE LIFE SAFETY SHEETS (LS-1 & LS-2), CLASS "D" |
| | FINISHES FOR ROOMS AND ENCLOSED SPACES IS LISTED.AS |
| | PER 38.3.3.2.2 , CLASS A, B, OR C SHALL BE LISTED IN |
| | THESE OTHER AREAS. |
| | |
| | 07.ON SHEET LS-2, REFERENCE IS INCORRECTLY MADE TO |
| | 1ST FLOOR - LIFE SAFETY. |
| | |
| | 08.ON SHEET LS-2, PLEASE EXPLAIN RATIONALE FOR ONLY |
| | SHOWING TRAVEL DISTANCE TO ONLY 1 OF THE 2 STAIRWELLS. |
| | |
| | 09.SPECIFY THE INTERIOR FLOOR FINISH FOR THE EXIT |
| | ENCLOSURES IN TERMS OF CLASS I OR CLASS II. |
| | |
| | 10.PLEASE PROVIDE FLAME SPREAD DETAILS ON THE FABRIC |
| | OF THE PARKING CANOPY. |
| | |
| | 11.HOW WILL THE INSTALLATION OF THE CARD ACCESS |
| | SYSTEM (CARD READERS) IMPACT ANY EXITING FROM THE EXIT |
| | STAIRWAYS?PLEASE BE ADVISED THAT SEPARATE PLANS AND |
| | PERMIT WILL BE REQUIRED FOR CARD ACCESS SYSTEM. |
| | |
| | 12.ON THE APPROPIATE EXTERIOR ELEVATION, POST THE |
| | NUMERICAL ADDRESS ON THE BUILDING TO BE VISIBLE FROM |
| | IBIS BOULEVARD.AS PER WEST PALM BEACH CODE, THE |
| | NUMBERS SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS |
| | THAN 1" IN WIDTH. |
| | |
| | 13.ON THE APPROPIATE EXTERIOR ELEVATION, SHOW THE |
| | LOCATION OF THE KNOX BOX.FOR APPLICATIONS, CONTACT |
| | WEST PALM BEACH FIRE PREVENTION BUREAU AT |
| | 561-804-4724. |
| | |
| | 14.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE STAIR |
| | HANDRAILS/GUARD RAILS. |
| | |
| | 15.SHOW/VERIFY THAT THE HEADROOM ON STAIRS SHALL NOT |
| | BE LESS THAN 80" AND SHALL BE MEASURED VERTICALLY ABOVE |
| | A PLANE PARELLEL TO AND TANGENT WITH THE MOST FORWARD |
| | PROJECTION OF THE STAIR DETAIL. |
| | |
| | 16.NO TAMPER SWITCH (TS) AND FLOW SWITCH (FS) SHOWN |
| | ON THE FA1.1 SHEET. |
| | |
| | 17.FIRE DEPARTMENT CONNECTION (FDC) SHALL BE EQUIPPED |
| | WITH KNOX LOCKING CAPS.FOR APPLICATIONS, CONTACT |
| | WEST PALM BEACH FIRE PREVENTION BUREAU AT |
| | 561-804-4724. |
| | |
| | 18.ELECTRONIC SWITCHES, CHAIN AND LOCK SHALL BE |
| | REQUIRED ON THE FIRE LINE BACKFLOW DEVICE. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS |
| | ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |