| Date |
Text |
| 2007-08-08 12:29:46 | 2007-08-07 12:29:46 |
| | |
| | |
| | ** DENIED ** |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES AT |
| | A MINIMUM ARE STATED ON PLANS FOR MINIMUM DESIGN. THIS |
| | IS REQUIRED ON ARCHITECTURAL TITLE/COVER SHEET AS WELL |
| | AS ELECTRICAL PLANS. |
| | PLEASE SEE NOTE ON ELECTRICAL PLANS WHICH MENTIONS |
| | LOCAL CODE PER PALM BEACH COUNTY JURISDICTION. PLEASE |
| | KNOW THIS JOB AS APPLIED IS LOCATION IN THE CITY OF |
| | WEST PALM BEACH. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 (NEC) |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY |
| | REQUIRE OTHER CODES. |
| | |
| | 2) NOTE: PLEASE SEE THAT ONCE THE ADDRESS OF THE |
| | PROJECT IS CONFIRMED ALONG WITH TENANT SUITE/UNIT |
| | NUMBERS FROM THE ADDRESSING REVIEWER, PLEASE BE SURE TO |
| | COMPLETE TITLE BLOCK WITH ALL INFORMATION AS |
| | DETERMINED. |
| | FLORIDA ADMINISTRATIVE CODE61G1-16.004, 61G15-23.002 |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 3) NOTE: PLEASE SEE THE PERMIT APPLICATION REQUESTS FOR |
| | THE PROJECT TO BE DESCRIBED IN DETAIL, HOWEVER THE |
| | APPLICATION ONLY STATES *NEW BUILD*? PLEASE SEE THE SQ |
| | FT ON PERMIT APPLICATION DOES NOT MATCH WITH THE ENERGY |
| | CALCULATIONS ETC. |
| | PLEASE COORDINATE AND SEE POSSIBLE COMMENTS FROM OTHER |
| | TRADES. |
| | |
| | 4) NOTE: PLEASE SEE THAT THE LANDSCAPE LIGHTING PLANS |
| | ARE REQUIRED TO BE SIGNED, DATED AND SEALED BY THE |
| | DESIGNER OF RECORD. PLEASE SEE SHEET 1 OF 1. FLORIDA |
| | STATUTES 481.221 |
| | PLEASE SEE OTHER LANDSCAPE PLANS WHICH WERE NOT DATED |
| | WHEN SIGNED AND SEALED AS REQUIRED PER ABOVE FLORIDA |
| | STATUTES. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. |
| | |
| | 5) NOTE: PLEASE SEE PLANS INDICATE A NEW GENERATOR, |
| | FUEL TANK AND ATS. PLEASE SUBMIT MANUFACTURES SPECS/CUT |
| | SHEETS FOR THESE ITEMS. PLEASE KNOW AS THE PLANS SEEM |
| | TO INDICATE A BI-FUEL UNIT, PLEASE OBTAIN THE LISTING |
| | AND INFORMATION ON THIS UNIT. IT IS KNOWN TO THIS |
| | OFFICE THAT THE GAS COMBUSTION CHAMBER AND ACCESSORIES |
| | ARE ADDED TO EQUIPMENT AFTER EQUIPMENT. IT IS ALSO THE |
| | UNDERSTANDING OF THIS OFFICE THAT THE EPA CERTIFICATION |
| | IS LOST ALONG WITH LISTING FROM THE MANUFACTURE AS THE |
| | DIESEL UNITS ARE MADE TO A LISTED STANDARD. PLEASE KNOW |
| | IF THESE ITEMS ARE ADDED AS AN AFTER MARKET CONVERSION, |
| | THE UNIT WILL BE REQUIRED TO BE RE-LISTED, AND |
| | CERTIFICATION FROM EPA WILL BE REQUIRED. |
| | PLEASE SUPPLY MORE INFORMATION ON UNIT AND |
| | SPECIFICATIONS AS REQUESTED. PLEASE SEE POSSIBLE |
| | COMMENTS FROM OTHER TRADES. |
| | NEC 110.3, 90.7. |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 6) NOTE: PLEASE SUBMIT CORRECTED AND COMPLETE ENERGY |
| | CALCULATIONS WITH COORDINATION WITH THE ELECTRICAL |
| | PLANS SUBMITTED. |
| | PLEASE SEE THE INPUT DATA REPORT AS THIS DOES NOT |
| | CORRELATE WITH PLANS FOR LUMINARIES TYPE, LUMINARIES |
| | WATTAGE, THE NUMBER OF LUMINARIES, METHOD OF CONTROLS, |
| | AREAS ETC. |
| | PLEASE SEE PAGE #2 FOR EXAMPLE OF THE INPUT DATA REPORT |
| | WHICH ONLY INDICATES A TOTAL OF TWO LUMINARIES WHEN THE |
| | PLANS IN FACT INDICATE A FAR GREAT NUMBER. |
| | PLEASE SEE THE ENERGY CALCULATIONS DO NOT INDICATE ANY |
| | LIGHTING ENTERED FOR EXTERIOR LIGHTING?? HOW IS THIS |
| | POSSIBLE WHEN THE PLANS INDICATE NUMEROUS FIXTURES FOR |
| | EXTERIOR LIGHTING? |
| | PLEASE SEE 13-4, 13-101.1, 13-414.2(2)(3)M |
| | 13-415.1.ABC.2, 13-415.1.ABC.1.4, 13-415.2.ABC.1.3 |
| | ETC. |
| | PLEASE COORDINATE ALL FIXTURES, CONTROLS, AREAS, |
| | WATTAGE AND INFORMATION ON PLANS WITH THE ENERGY |
| | CALCULATIONS. |
| | PLEASE BE SURE TO UPDATE THE PROJECT ADDRESS |
| | INFORMATION ON THE CALCULATIONS COVER SHEET. PLEASE |
| | KNOW THAT AT THIS TIME THERE SEVERAL AREAS WHICH NEED |
| | TO BE ADDRESSED AND CHANGED AND REVISED CALCULATIONS |
| | MAY VERY WELL CONTAIN NEW COMMENTS AS THERE ARE ITEMS |
| | NOT YET SUBMITTED FOR REVIEW. |
| | ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| | SUCH AS MECHANICAL REVIEW WHICH MAY AFFECT ENERGY |
| | CALCULATIONS AND METHOD USED. |
| | |
| | 7) NOTE: PLEASE SEE THAT LIGHTING CONTROLS FOR FBC |
| | CHAPTER 13 NEED SOME CLARIFICATION. PLEASE SEE THERE |
| | ARE AREAS ON PLANS WHICH DO NOT CONTAIN ANY OVER RIDE |
| | DEVICES ON PLANS. PLEASE SEE *COMMON AREAS* FOR EXAMPLE |
| | ON SHEET E1.2, WHICH ONLY CONTAIN STANDARD SWITCHES. |
| | PLEASE PROVIDE SCHEDULING FOR SYSTEM(S). A BASE TIME ON |
| | PLANS SHALL BE INDICATED. |
| | PLEASE PROVIDE MAXIMUM TIMES FOR ALL OVER RIDE DEVICES. |
| | THIS WOULD INCLUDE TIMERS, OCCUPANCY SENSOR DEVICES |
| | ETC. |
| | 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | 8) NOTE: PLEASE KNOW AS REQUIRED PER LIFE SAFETY CODE |
| | AND THE FIRE MARSHALS OFFICE, THE FIRST FLOOR TENANT |
| | SPACES WHICH ARE NOT GOING TO BE BUILT AT THIS TIME |
| | WILL STILL REQUIRE SOME TYPE OF NORMAL LIGHTING WITH |
| | AUTOMATIC SHUT OFF CONTROLS. |
| | THIS CAN BE A MINIMUM OF FIXTURES. |
| | PLEASE SEE LS 101 7.8 AND 7.9. BATTERY BACK UP FIXTURES |
| | ARE ALREADY SHOWN BUT MAY NOT MEET THE MINIMUM NEEDED |
| | FOR MINIMUM LIGHTING LEVELS. |
| | |
| | 9) NOTE: PLEASE SEE THE PLANS ARE MISSING MINIMUM |
| | EGRESS LIGHTING IN MANY AREAS. PLEASE SEE FOR EXAMPLE |
| | THE FOYER AREA ON THE FIRST FLOOR WHERE NO BATTERY BACK |
| | UP LIGHTING FIXTURES COULD BE LOCATED TO THE PUBLIC |
| | RIGHT OF WAY. PLEASE ALSO SEE 2ND FLOOR COMMON ARE |
| | CORRIDORS FOR ANOTHER EXAMPLE. |
| | PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR EGRESS PATHS |
| | INDICATING THE MINIMUM LIGHTING LEVELS FOR FLAT EGRESS |
| | SURFACES AS WELL AS BOTH STAIR AREAS. PLEASE SEE LS 101 |
| | 7.8.1.3, 7.9.2.2. |
| | PLEASE ALSO SEE THE FLORIDA ADMINISTRATIVE CODE |
| | 61G15-33.004 AS THIS IS REQUIRED. |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | ** PLEASE KNOW AS NO LIGHTING LEVELS WERE SUBMITTED |
| | NONE COULD BE REVIEWED AT THIS TIME. |
| | |
| | 10) NOTE: PLEASE SEE PLANS ARE MISSING THE MINIMUM |
| | LEVELS FOR ADA COMPLIANCE FOR HORNS, STROBES AND |
| | HORN/STROBES. |
| | PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR MINIMUM |
| | LEVELS TO BE PLACED ON PLANS FOR SYMBOL LEGEND FOR FIRE |
| | ALARM DEVICES AND OR FA PLANS. |
| | PLEASE KNOW THAT EVEN AS THE FIRE ALARM PLANS WILL BE |
| | UNDER SEPARATE PERMITS, THE BASE DESIGN ON BASE |
| | BUILDING PLANS ARE REQUIRED TO MEET THE MINIMUM DESIGN |
| | LEVELS PER THE FBC. |
| | |
| | 11) NOTE: PLEASE BE SURE TO CORRELATE THE LANDSCAPE |
| | LIGHTING PLANS WITH THE ELECTRICAL PLANS FOR FIXTURES, |
| | LOADS AND CIRCUITING. LANDSCAPE PLANS DO SHOW LIGHTING |
| | AT THIS TIME AND THE INTENT OF INSTALLATION. |
| | PLANS ALONG WITH THE ENERGY CALCULATIONS WILL BE |
| | REQUIRED TO BE UPDATED. |
| | 310.16, 240.4, 408.4 ETC |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION |
| | REQUIRED ON PLANS. |
| | |
| | 12) NOTE: PLEASE KNOW THE WIND LOAD ENGINEERING FOR |
| | SITE LIGHTING POLES WILL BE NEED FOR REVIEW FROM THIS |
| | STRUCTURAL REVIEWER. THIS IS BEING NOTED FOR |
| | INFORMATION AT THIS TIME. |
| | |
| | 13) NOTE: PLEASE SEE THE SITE LIGHTING PLANS INDICATE A |
| | TITLE AND A BLOCK FOR *CITY OF WEST PALM BEACH LIGHTING |
| | REQUIRED*. PLEASE CLARIFY WHERE THIS INFORMATION IS |
| | FOUND AS THIS OFFICE CONTAINS NO SUCH REQUIREMENTS. |
| | THERE IS MAXIMUM ALLOWED WATTAGE AND ENERGY USE AS |
| | STATED IN THE FLORIDA BUILDING CODE AND CHAPTER 13 BUT |
| | WE DO NOT REQUIRE SPECIFICS AS STATED ABOVE. PLEASE |
| | CLARIFY. |
| | FBC 106.1.2 |
| | |
| | 14) NOTE: PLEASE GIVE CONSIDERATION FOR THE TYPE OF |
| | DEVICES BEING CHOSEN FOR NOT ONLY THE ELECTRICAL ROOM |
| | BUT FOR BOTH ELECTRICAL ROOMS AND ELEVATOR MACHINE ROOM |
| | LIGHTS. |
| | PLEASE SEE 110.26E FOR THE TYPE OF DEVICE. |
| | |
| | 15) NOTE: PLEASE SEE THE LIGHTING PLANS FOR SECOND AND |
| | FIRST FLOORS CONTAINS A *KEYED NOTE* #2 WHICH MENTIONS |
| | THE CONNECTION OF LIGHTING AHEAD OF SWITCHES AND |
| | OCCUPANCY TYPE DEVICES. |
| | PLEASE SEE FBC 1006.1.2 AND LS 101 7.8.1.2.2 AUTOMATIC, |
| | MOTION SENSOR?TYPE LIGHTING SWITCHES SHALL BE PERMITTED |
| | WITHIN THE MEANS OF EGRESS, PROVIDED THAT THE SWITCH |
| | CONTROLLERS ARE EQUIPPED FOR FAIL-SAFE OPERATION, THE |
| | ILLUMINATION TIMERS ARE SET FOR A MINIMUM 15-MINUTE |
| | DURATION, AND THE MOTION SENSOR IS ACTIVATED BY ANY |
| | OCCUPANT MOVEMENT IN THE AREA SERVED BY THE LIGHTING |
| | UNITS. |
| | PLEASE SEE 7.8 AND 7.9 AS THE FAILURE OF A SINGLE |
| | CONTROL DEVICE SHALL NOT LEAVE ANY ONE AREA IN TOTAL |
| | DARKNESS. |
| | |
| | 16) NOTE: PLEASE KNOW AS INFORMATION, THE LOW VOLTAGE |
| | AS SHOWN ON PLANS WILL BE REQUIRED TO BE UNDER A |
| | SEPARATE PERMIT. THESE PLANS MAY BE REFERENCED FOR THE |
| | WORK AS APPLIED AND SHOWN. |
| | ** INFORMATION ONLY AT THIS TIME AND NO CHANGES ARE |
| | NEEDED TO PLANS. |
| | |
| | 17) NOTE: PLEASE SEE 110.26 OF THE NEC AS THE MINIMUM |
| | WIDTHS FOR DISCONNECTS AT THE CONDENSING UNITS IS NOT |
| | MET BY THE PLANS AND THE SCALE AS NOTED AND SHOWN. |
| | PLEASE SEE E4.2 FOR NORTH AND SOUTH YARDS. |
| | |
| | 18) NOTE: PLEASE BE SURE PANEL SCHEDULES ARE SPECIFIC |
| | TO ALL ROOMS AND AREAS IN WHICH THEY FEED. PLEASE SEE |
| | THE USE OF *GENERAL RECEPTACLES AND GENERAL LIGHTS* |
| | NEEDS TO BE SPECIFIC. PLEASE SEE THIS COMMENT IS FOR |
| | ALL PANEL SCHEDULE WITH GENERAL DESIGNATIONS. PLEASE |
| | KNOW THE DESIGNATION MAY BE THE NUMERICAL DESIGNATION |
| | AS NOTED ON PLANS. |
| | PLEASE SEE 408.4 AND COMMENTARY AS EXTRACTED FROM THE |
| | NEC BELOW. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 19) NOTE: PLEASE CORRELATE RISER DIAGRAM WITH THE PANEL |
| | SCHEDULES FOR EQUIPMENT AS SUBMITTED. |
| | PLEASE SEE RISER SHEET E5.1 FOR EXAMPLE AS SHEET |
| | INDICATES A MAIN CIRCUIT BREAKER PANEL AND RISER DOES |
| | NOT. |
| | FBC 106.1.2 |
| | |
| | 20) NOTE: PLEASE SEE MISSING MEANS OF DISCONNECTS AT |
| | THE MAIN BUILDING AS THIS IS CONSIDERED A DETACHED |
| | STRUCTURE AND WOULD NEED TO COMPLY WITH 225.31-225.39. |
| | PLEASE LABEL ALL EQUIPMENT FOR MAINS AT THIS BUILDING. |
| | THE SERVICE MAIN OUTSIDE CAN NOT BE CONSIDERED THIS |
| | MAIN AS IT IS NOT PART OF THE BUILDING. |
| | PLEASE ADJUST AND PLACE NOTES ON PLANS FOR SIGNS OF THE |
| | BUILDING MAINS AND LOCATION FOR SERVICE MAIN. |
| | |
| | 21) NOTE: PLEASE CLARIFY THE LOCATION OF THE GROUNDING |
| | ELECTRODE SYSTEM AS SHOWN. PLEASE SEE THE SYSTEM AS |
| | SHOWN APPEARS TO BE AT THE MAIN BUILDING WHICH IS |
| | REQUIRED AS IT IS A DETACHED STRUCTURE PER 250.32, |
| | HOWEVER PLEASE CLARIFY SYSTEM AT THE SERVICE MAIN |
| | LOCATION PER 250.50. |
| | |
| | |
| | 22) NOTE: PLEASE CLARIFY FIRE SPRINKLER BOND PER |
| | 250.104. THE DETAIL ON 7.1 INDICATES WATER PIPE, |
| | HOWEVER NOT CLEAR AS THIS APPEARS TO BE THE ONE FOR THE |
| | BUILDING. |
| | |
| | 23) NOTE: PLEASE SEE 620.24C,AS THE ELEVATOR ROOM |
| | AND PIT LIGHTS/RECEPTACLES ARE REQUIRED TO BE ON A |
| | DEDICATED BRANCH CIRCUITS. PLEASE SEE SHEET FOR |
| | LIGHTING AND ELEVATOR ROOMS ON E4.1 AS SOME OF THESE |
| | CIRCUITS AS SHOWN ACTUALLY FEED OTHER AREAS. (EXAMPLE |
| | ELECTRICAL ROOM). |
| | |
| | 24) NOTE: PLEASE PROVIDE INFORMATION ON PLANS FOR OVER |
| | CURRENT PROTECTION FOR ELEVATOR CAB LIGHTS. PLEASE SEE |
| | THE DETAIL ON E4.1 SHOWS THE DISCONNECT AS REQUIRED |
| | HOWEVER DOES NOT INDICATE THE OVER CURRENT PROTECTION |
| | WHICH IS REQUIRED TO BE THE SAME ROOM PER 620.22A. |
| | |
| | 25) NOTE: PLEASE CLARIFY THE *TELCO* ROOM THAT THIS IS |
| | OR IS NOT AN IT ROOM BY DEFINITIONS. |
| | IF THIS IS GOING TO BE AN IT ROOM OR IF ANY OTHER |
| | LOCATION IS GOING TO BE USED FOR THIS SAME REASON, |
| | PLEASE SEE NEC 645. |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 26) NOTE: PLEASE INDICATE THE SIZE/AMERAGE OF THE METER |
| | CANS ON THE RISER. PLEASE SEE THE METER WHICH IS SHOWN |
| | ONE E-4.2 FOR MAIN IS NOT INCLUDED ON RISER DIAGRAM |
| | SHEET E-5.1. |
| | PLEASE COORDINATE AND ADJUST PLANS AND SHOW SIZES OF |
| | EQUIPMENT. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 27) NOTE: PLEASE INDICATE THE SIZE OF FEEDERS FROM |
| | WIRE-WAY TO METERS TO MAINS ON E5.1. |
| | 310.16, 215.5, 240.4 |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 28) NOTE: PLEASE BE SURE TO INDICATE THE OVER CURRENT |
| | PROTECTION ON THE GENERATOR. PLEASE SEE E5.1 AS AT THIS |
| | TIME THE CONDUCTORS FROM THE GENERATOR CAN NOT BE |
| | VERIFIED PER 445.13, 310.16 AND 240.4. |
| | |
| | 29) NOTE: PLEASE CLARIFY THE DIMENSIONS ON THE WIRE-WAY |
| | AS THIS IS CURRENTLY SHOWN AS 8X8. PLEASE PROVIDE |
| | CALCULATIONS BASED ON THE CONDUCTORS AND RADIUS/BENDING |
| | SPACE ETC. |
| | PLEASE SEE 376.22 |
| | |
| | 30) NOTE: PLEASE SEE RISER SHEET E5.1 STATES THE |
| | AVAILABLE FAULT CURRENT HAS BEEN ASSUMED AND ALSO |
| | CONTAINS AN ADDITIONAL NOTE ON RISER WHICH MENTIONS TO |
| | BE VERIFIED BY CONTRACTOR. |
| | CONTACT SHOULD BE MADE TO THE FPL SERVICE PLANNER AT |
| | THIS TIME FOR THE CORRECT AVAILABLE FAULT CURRENT AND |
| | PLACE THE MINIMUM RATINGS ON THE PLANS AT THIS TIME. |
| | PLEASE SEE 110.9, 110.10 |
| | PLEASE KNOW THIS IS REQUIRED ON THE DESIGN |
| | PROFESSIONALS PLANS AT THIS TIME. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-08-07 21:28:15 | 2007-08-07 21:28:15 |
| | |
| | REVIEW COMPLETED. REVIEW NOTES TO FOLLOW ON 8/8/07 |
| 2007-08-07 07:12:43 | 2007-08-07 07:12:43 |
| | |
| | 1-SET IN ELEC FOR REVIEW. |