Plan Review Notes
Plan Review Notes For Permit 07070315
Permit Number 07070315
Review Stop E
Sequence Number 1
Notes
Date Text
2007-08-08 12:29:462007-08-07 12:29:46
  
  
 ** DENIED **
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES AT
 A MINIMUM ARE STATED ON PLANS FOR MINIMUM DESIGN. THIS
 IS REQUIRED ON ARCHITECTURAL TITLE/COVER SHEET AS WELL
 AS ELECTRICAL PLANS.
 PLEASE SEE NOTE ON ELECTRICAL PLANS WHICH MENTIONS
 LOCAL CODE PER PALM BEACH COUNTY JURISDICTION. PLEASE
 KNOW THIS JOB AS APPLIED IS LOCATION IN THE CITY OF
 WEST PALM BEACH.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70 (NEC)
 2003 NFPA-101
 2002 NFPA-72
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WHICH MAY
 REQUIRE OTHER CODES.
  
 2) NOTE: PLEASE SEE THAT ONCE THE ADDRESS OF THE
 PROJECT IS CONFIRMED ALONG WITH TENANT SUITE/UNIT
 NUMBERS FROM THE ADDRESSING REVIEWER, PLEASE BE SURE TO
 COMPLETE TITLE BLOCK WITH ALL INFORMATION AS
 DETERMINED.
 FLORIDA ADMINISTRATIVE CODE61G1-16.004, 61G15-23.002
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 3) NOTE: PLEASE SEE THE PERMIT APPLICATION REQUESTS FOR
 THE PROJECT TO BE DESCRIBED IN DETAIL, HOWEVER THE
 APPLICATION ONLY STATES *NEW BUILD*? PLEASE SEE THE SQ
 FT ON PERMIT APPLICATION DOES NOT MATCH WITH THE ENERGY
 CALCULATIONS ETC.
 PLEASE COORDINATE AND SEE POSSIBLE COMMENTS FROM OTHER
 TRADES.
  
 4) NOTE: PLEASE SEE THAT THE LANDSCAPE LIGHTING PLANS
 ARE REQUIRED TO BE SIGNED, DATED AND SEALED BY THE
 DESIGNER OF RECORD. PLEASE SEE SHEET 1 OF 1. FLORIDA
 STATUTES 481.221
 PLEASE SEE OTHER LANDSCAPE PLANS WHICH WERE NOT DATED
 WHEN SIGNED AND SEALED AS REQUIRED PER ABOVE FLORIDA
 STATUTES.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 5) NOTE: PLEASE SEE PLANS INDICATE A NEW GENERATOR,
 FUEL TANK AND ATS. PLEASE SUBMIT MANUFACTURES SPECS/CUT
 SHEETS FOR THESE ITEMS. PLEASE KNOW AS THE PLANS SEEM
 TO INDICATE A BI-FUEL UNIT, PLEASE OBTAIN THE LISTING
 AND INFORMATION ON THIS UNIT. IT IS KNOWN TO THIS
 OFFICE THAT THE GAS COMBUSTION CHAMBER AND ACCESSORIES
 ARE ADDED TO EQUIPMENT AFTER EQUIPMENT. IT IS ALSO THE
 UNDERSTANDING OF THIS OFFICE THAT THE EPA CERTIFICATION
 IS LOST ALONG WITH LISTING FROM THE MANUFACTURE AS THE
 DIESEL UNITS ARE MADE TO A LISTED STANDARD. PLEASE KNOW
 IF THESE ITEMS ARE ADDED AS AN AFTER MARKET CONVERSION,
 THE UNIT WILL BE REQUIRED TO BE RE-LISTED, AND
 CERTIFICATION FROM EPA WILL BE REQUIRED.
 PLEASE SUPPLY MORE INFORMATION ON UNIT AND
 SPECIFICATIONS AS REQUESTED. PLEASE SEE POSSIBLE
 COMMENTS FROM OTHER TRADES.
 NEC 110.3, 90.7.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 6) NOTE: PLEASE SUBMIT CORRECTED AND COMPLETE ENERGY
 CALCULATIONS WITH COORDINATION WITH THE ELECTRICAL
 PLANS SUBMITTED.
 PLEASE SEE THE INPUT DATA REPORT AS THIS DOES NOT
 CORRELATE WITH PLANS FOR LUMINARIES TYPE, LUMINARIES
 WATTAGE, THE NUMBER OF LUMINARIES, METHOD OF CONTROLS,
 AREAS ETC.
 PLEASE SEE PAGE #2 FOR EXAMPLE OF THE INPUT DATA REPORT
 WHICH ONLY INDICATES A TOTAL OF TWO LUMINARIES WHEN THE
 PLANS IN FACT INDICATE A FAR GREAT NUMBER.
 PLEASE SEE THE ENERGY CALCULATIONS DO NOT INDICATE ANY
 LIGHTING ENTERED FOR EXTERIOR LIGHTING?? HOW IS THIS
 POSSIBLE WHEN THE PLANS INDICATE NUMEROUS FIXTURES FOR
 EXTERIOR LIGHTING?
 PLEASE SEE 13-4, 13-101.1, 13-414.2(2)(3)M
 13-415.1.ABC.2, 13-415.1.ABC.1.4, 13-415.2.ABC.1.3
 ETC.
 PLEASE COORDINATE ALL FIXTURES, CONTROLS, AREAS,
 WATTAGE AND INFORMATION ON PLANS WITH THE ENERGY
 CALCULATIONS.
 PLEASE BE SURE TO UPDATE THE PROJECT ADDRESS
 INFORMATION ON THE CALCULATIONS COVER SHEET. PLEASE
 KNOW THAT AT THIS TIME THERE SEVERAL AREAS WHICH NEED
 TO BE ADDRESSED AND CHANGED AND REVISED CALCULATIONS
 MAY VERY WELL CONTAIN NEW COMMENTS AS THERE ARE ITEMS
 NOT YET SUBMITTED FOR REVIEW.
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 SUCH AS MECHANICAL REVIEW WHICH MAY AFFECT ENERGY
 CALCULATIONS AND METHOD USED.
  
 7) NOTE: PLEASE SEE THAT LIGHTING CONTROLS FOR FBC
 CHAPTER 13 NEED SOME CLARIFICATION. PLEASE SEE THERE
 ARE AREAS ON PLANS WHICH DO NOT CONTAIN ANY OVER RIDE
 DEVICES ON PLANS. PLEASE SEE *COMMON AREAS* FOR EXAMPLE
 ON SHEET E1.2, WHICH ONLY CONTAIN STANDARD SWITCHES.
 PLEASE PROVIDE SCHEDULING FOR SYSTEM(S). A BASE TIME ON
 PLANS SHALL BE INDICATED.
 PLEASE PROVIDE MAXIMUM TIMES FOR ALL OVER RIDE DEVICES.
 THIS WOULD INCLUDE TIMERS, OCCUPANCY SENSOR DEVICES
 ETC.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 8) NOTE: PLEASE KNOW AS REQUIRED PER LIFE SAFETY CODE
 AND THE FIRE MARSHALS OFFICE, THE FIRST FLOOR TENANT
 SPACES WHICH ARE NOT GOING TO BE BUILT AT THIS TIME
 WILL STILL REQUIRE SOME TYPE OF NORMAL LIGHTING WITH
 AUTOMATIC SHUT OFF CONTROLS.
 THIS CAN BE A MINIMUM OF FIXTURES.
 PLEASE SEE LS 101 7.8 AND 7.9. BATTERY BACK UP FIXTURES
 ARE ALREADY SHOWN BUT MAY NOT MEET THE MINIMUM NEEDED
 FOR MINIMUM LIGHTING LEVELS.
  
 9) NOTE: PLEASE SEE THE PLANS ARE MISSING MINIMUM
 EGRESS LIGHTING IN MANY AREAS. PLEASE SEE FOR EXAMPLE
 THE FOYER AREA ON THE FIRST FLOOR WHERE NO BATTERY BACK
 UP LIGHTING FIXTURES COULD BE LOCATED TO THE PUBLIC
 RIGHT OF WAY. PLEASE ALSO SEE 2ND FLOOR COMMON ARE
 CORRIDORS FOR ANOTHER EXAMPLE.
 PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR EGRESS PATHS
 INDICATING THE MINIMUM LIGHTING LEVELS FOR FLAT EGRESS
 SURFACES AS WELL AS BOTH STAIR AREAS. PLEASE SEE LS 101
 7.8.1.3, 7.9.2.2.
 PLEASE ALSO SEE THE FLORIDA ADMINISTRATIVE CODE
 61G15-33.004 AS THIS IS REQUIRED.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
 ** PLEASE KNOW AS NO LIGHTING LEVELS WERE SUBMITTED
 NONE COULD BE REVIEWED AT THIS TIME.
  
 10) NOTE: PLEASE SEE PLANS ARE MISSING THE MINIMUM
 LEVELS FOR ADA COMPLIANCE FOR HORNS, STROBES AND
 HORN/STROBES.
 PLEASE SEE FBC 11-4.28.1, .2 AND .3(4) FOR MINIMUM
 LEVELS TO BE PLACED ON PLANS FOR SYMBOL LEGEND FOR FIRE
 ALARM DEVICES AND OR FA PLANS.
 PLEASE KNOW THAT EVEN AS THE FIRE ALARM PLANS WILL BE
 UNDER SEPARATE PERMITS, THE BASE DESIGN ON BASE
 BUILDING PLANS ARE REQUIRED TO MEET THE MINIMUM DESIGN
 LEVELS PER THE FBC.
  
 11) NOTE: PLEASE BE SURE TO CORRELATE THE LANDSCAPE
 LIGHTING PLANS WITH THE ELECTRICAL PLANS FOR FIXTURES,
 LOADS AND CIRCUITING. LANDSCAPE PLANS DO SHOW LIGHTING
 AT THIS TIME AND THE INTENT OF INSTALLATION.
 PLANS ALONG WITH THE ENERGY CALCULATIONS WILL BE
 REQUIRED TO BE UPDATED.
 310.16, 240.4, 408.4 ETC
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION
 REQUIRED ON PLANS.
  
 12) NOTE: PLEASE KNOW THE WIND LOAD ENGINEERING FOR
 SITE LIGHTING POLES WILL BE NEED FOR REVIEW FROM THIS
 STRUCTURAL REVIEWER. THIS IS BEING NOTED FOR
 INFORMATION AT THIS TIME.
  
 13) NOTE: PLEASE SEE THE SITE LIGHTING PLANS INDICATE A
 TITLE AND A BLOCK FOR *CITY OF WEST PALM BEACH LIGHTING
 REQUIRED*. PLEASE CLARIFY WHERE THIS INFORMATION IS
 FOUND AS THIS OFFICE CONTAINS NO SUCH REQUIREMENTS.
 THERE IS MAXIMUM ALLOWED WATTAGE AND ENERGY USE AS
 STATED IN THE FLORIDA BUILDING CODE AND CHAPTER 13 BUT
 WE DO NOT REQUIRE SPECIFICS AS STATED ABOVE. PLEASE
 CLARIFY.
 FBC 106.1.2
  
 14) NOTE: PLEASE GIVE CONSIDERATION FOR THE TYPE OF
 DEVICES BEING CHOSEN FOR NOT ONLY THE ELECTRICAL ROOM
 BUT FOR BOTH ELECTRICAL ROOMS AND ELEVATOR MACHINE ROOM
 LIGHTS.
 PLEASE SEE 110.26E FOR THE TYPE OF DEVICE.
  
 15) NOTE: PLEASE SEE THE LIGHTING PLANS FOR SECOND AND
 FIRST FLOORS CONTAINS A *KEYED NOTE* #2 WHICH MENTIONS
 THE CONNECTION OF LIGHTING AHEAD OF SWITCHES AND
 OCCUPANCY TYPE DEVICES.
 PLEASE SEE FBC 1006.1.2 AND LS 101 7.8.1.2.2 AUTOMATIC,
 MOTION SENSOR?TYPE LIGHTING SWITCHES SHALL BE PERMITTED
 WITHIN THE MEANS OF EGRESS, PROVIDED THAT THE SWITCH
 CONTROLLERS ARE EQUIPPED FOR FAIL-SAFE OPERATION, THE
 ILLUMINATION TIMERS ARE SET FOR A MINIMUM 15-MINUTE
 DURATION, AND THE MOTION SENSOR IS ACTIVATED BY ANY
 OCCUPANT MOVEMENT IN THE AREA SERVED BY THE LIGHTING
 UNITS.
 PLEASE SEE 7.8 AND 7.9 AS THE FAILURE OF A SINGLE
 CONTROL DEVICE SHALL NOT LEAVE ANY ONE AREA IN TOTAL
 DARKNESS.
  
 16) NOTE: PLEASE KNOW AS INFORMATION, THE LOW VOLTAGE
 AS SHOWN ON PLANS WILL BE REQUIRED TO BE UNDER A
 SEPARATE PERMIT. THESE PLANS MAY BE REFERENCED FOR THE
 WORK AS APPLIED AND SHOWN.
 ** INFORMATION ONLY AT THIS TIME AND NO CHANGES ARE
 NEEDED TO PLANS.
  
 17) NOTE: PLEASE SEE 110.26 OF THE NEC AS THE MINIMUM
 WIDTHS FOR DISCONNECTS AT THE CONDENSING UNITS IS NOT
 MET BY THE PLANS AND THE SCALE AS NOTED AND SHOWN.
 PLEASE SEE E4.2 FOR NORTH AND SOUTH YARDS.
  
 18) NOTE: PLEASE BE SURE PANEL SCHEDULES ARE SPECIFIC
 TO ALL ROOMS AND AREAS IN WHICH THEY FEED. PLEASE SEE
 THE USE OF *GENERAL RECEPTACLES AND GENERAL LIGHTS*
 NEEDS TO BE SPECIFIC. PLEASE SEE THIS COMMENT IS FOR
 ALL PANEL SCHEDULE WITH GENERAL DESIGNATIONS. PLEASE
 KNOW THE DESIGNATION MAY BE THE NUMERICAL DESIGNATION
 AS NOTED ON PLANS.
 PLEASE SEE 408.4 AND COMMENTARY AS EXTRACTED FROM THE
 NEC BELOW.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 19) NOTE: PLEASE CORRELATE RISER DIAGRAM WITH THE PANEL
 SCHEDULES FOR EQUIPMENT AS SUBMITTED.
 PLEASE SEE RISER SHEET E5.1 FOR EXAMPLE AS SHEET
 INDICATES A MAIN CIRCUIT BREAKER PANEL AND RISER DOES
 NOT.
 FBC 106.1.2
  
 20) NOTE: PLEASE SEE MISSING MEANS OF DISCONNECTS AT
 THE MAIN BUILDING AS THIS IS CONSIDERED A DETACHED
 STRUCTURE AND WOULD NEED TO COMPLY WITH 225.31-225.39.
 PLEASE LABEL ALL EQUIPMENT FOR MAINS AT THIS BUILDING.
 THE SERVICE MAIN OUTSIDE CAN NOT BE CONSIDERED THIS
 MAIN AS IT IS NOT PART OF THE BUILDING.
 PLEASE ADJUST AND PLACE NOTES ON PLANS FOR SIGNS OF THE
 BUILDING MAINS AND LOCATION FOR SERVICE MAIN.
  
 21) NOTE: PLEASE CLARIFY THE LOCATION OF THE GROUNDING
 ELECTRODE SYSTEM AS SHOWN. PLEASE SEE THE SYSTEM AS
 SHOWN APPEARS TO BE AT THE MAIN BUILDING WHICH IS
 REQUIRED AS IT IS A DETACHED STRUCTURE PER 250.32,
 HOWEVER PLEASE CLARIFY SYSTEM AT THE SERVICE MAIN
 LOCATION PER 250.50.
  
  
 22) NOTE: PLEASE CLARIFY FIRE SPRINKLER BOND PER
 250.104. THE DETAIL ON 7.1 INDICATES WATER PIPE,
 HOWEVER NOT CLEAR AS THIS APPEARS TO BE THE ONE FOR THE
 BUILDING.
  
 23) NOTE: PLEASE SEE 620.24C,AS THE ELEVATOR ROOM
 AND PIT LIGHTS/RECEPTACLES ARE REQUIRED TO BE ON A
 DEDICATED BRANCH CIRCUITS. PLEASE SEE SHEET FOR
 LIGHTING AND ELEVATOR ROOMS ON E4.1 AS SOME OF THESE
 CIRCUITS AS SHOWN ACTUALLY FEED OTHER AREAS. (EXAMPLE
 ELECTRICAL ROOM).
  
 24) NOTE: PLEASE PROVIDE INFORMATION ON PLANS FOR OVER
 CURRENT PROTECTION FOR ELEVATOR CAB LIGHTS. PLEASE SEE
 THE DETAIL ON E4.1 SHOWS THE DISCONNECT AS REQUIRED
 HOWEVER DOES NOT INDICATE THE OVER CURRENT PROTECTION
 WHICH IS REQUIRED TO BE THE SAME ROOM PER 620.22A.
  
 25) NOTE: PLEASE CLARIFY THE *TELCO* ROOM THAT THIS IS
 OR IS NOT AN IT ROOM BY DEFINITIONS.
 IF THIS IS GOING TO BE AN IT ROOM OR IF ANY OTHER
 LOCATION IS GOING TO BE USED FOR THIS SAME REASON,
 PLEASE SEE NEC 645.
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
  
 26) NOTE: PLEASE INDICATE THE SIZE/AMERAGE OF THE METER
 CANS ON THE RISER. PLEASE SEE THE METER WHICH IS SHOWN
 ONE E-4.2 FOR MAIN IS NOT INCLUDED ON RISER DIAGRAM
 SHEET E-5.1.
 PLEASE COORDINATE AND ADJUST PLANS AND SHOW SIZES OF
 EQUIPMENT.
 FBC 106.1.2, 106.3.5.1.2
  
 27) NOTE: PLEASE INDICATE THE SIZE OF FEEDERS FROM
 WIRE-WAY TO METERS TO MAINS ON E5.1.
 310.16, 215.5, 240.4
 FBC 106.1.2, 106.3.5.1.2
  
 28) NOTE: PLEASE BE SURE TO INDICATE THE OVER CURRENT
 PROTECTION ON THE GENERATOR. PLEASE SEE E5.1 AS AT THIS
 TIME THE CONDUCTORS FROM THE GENERATOR CAN NOT BE
 VERIFIED PER 445.13, 310.16 AND 240.4.
  
 29) NOTE: PLEASE CLARIFY THE DIMENSIONS ON THE WIRE-WAY
 AS THIS IS CURRENTLY SHOWN AS 8X8. PLEASE PROVIDE
 CALCULATIONS BASED ON THE CONDUCTORS AND RADIUS/BENDING
 SPACE ETC.
 PLEASE SEE 376.22
  
 30) NOTE: PLEASE SEE RISER SHEET E5.1 STATES THE
 AVAILABLE FAULT CURRENT HAS BEEN ASSUMED AND ALSO
 CONTAINS AN ADDITIONAL NOTE ON RISER WHICH MENTIONS TO
 BE VERIFIED BY CONTRACTOR.
 CONTACT SHOULD BE MADE TO THE FPL SERVICE PLANNER AT
 THIS TIME FOR THE CORRECT AVAILABLE FAULT CURRENT AND
 PLACE THE MINIMUM RATINGS ON THE PLANS AT THIS TIME.
 PLEASE SEE 110.9, 110.10
 PLEASE KNOW THIS IS REQUIRED ON THE DESIGN
 PROFESSIONALS PLANS AT THIS TIME.
 FBC 106.1.2, 106.3.5.1.2
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-08-07 21:28:152007-08-07 21:28:15
  
 REVIEW COMPLETED. REVIEW NOTES TO FOLLOW ON 8/8/07
2007-08-07 07:12:432007-08-07 07:12:43
  
 1-SET IN ELEC FOR REVIEW.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved