| 2007-09-04 17:07:07 | |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS NOTE #3 AS THE VALUE SHOWN |
| | IS TO BE BASED ON FAIR MARKET VALUE AND THE TABLES AS |
| | SET-FORTH IN THE FBC AND ADOPTED REFERENCES TO THE FBC. |
| | PLEASE ADJUST. |
| | PLEASE SEE THE APPLIED VALUE FOR THE SCOPE OF WORK |
| | BEING PERFORMED AND WHAT WILL BE REQUIRED BY THE FBC |
| | AND REVIEW COMMENTS WILL BE SUBSTANTIALLY HIGHER THAN |
| | THAT STATED ON PERMIT APPLICATION. |
| | PLEASE ADJUST THE VALUE FOR ALL OF THE PROPOSED WORK. |
| | PLEASE SEE FBC ADMIN SECTION 108.3 |
| | |
| | 2) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS |
| | REVIEW. |
| | PLEASE SEE THE NEW CALCULATIONS ARE NOT SIGNED, DATED |
| | AND *SEALED* AS REQUIRED PER 13-103.1.1.1. |
| | PLEASE SEE THE LIGHTING INFORMATION ON THE INPUT DATA |
| | REPORT DOES NOT MATCH WITH PLANS. |
| | PLEASE SEE THE NUMBER OF FIXTURES IN THE IDR ONLY |
| | INDICATES ONE LIGHT FIXTURE. HOW IS THIS POSSIBLE WHEN |
| | THE PLANS INDICATE SEVERAL? |
| | PLEASE SEE THE RESPONSE LETTER MENTIONS TO SEE SHEET |
| | A-1 HOWEVER NO ELECTRICAL INFORMATION FOR COMMENT WAS |
| | ON THIS SHEET AS NOTED. |
| | PLEASE SEE THE PREVIOUS NOTE BELOW WHICH STILL STANDS. |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS WERE SUBMITTED WITHOUT ANY DESIGNS FOR |
| | FBC CHAPTER 13. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE THAT EVEN IF NOT CREATING ANY NEW A/C SPACE |
| | (WHICH IS BEING DONE) PERFORMANCE CALCULATIONS ARE |
| | STILL REQUIRED. |
| | PLEASE SEE 13-415.1.AB.1.1, 13-415.2 ETC FOR ENERGY |
| | CALCULATIONS/PERFORMANCE CALCULATIONS. |
| | PLEASE BE SURE THE FIXTURE LEGEND ON PLANS IS COMPLETE |
| | WITH ALL INFORMATION FOR FIXTURES/LUMINARIES. PLEASE BE |
| | SURE ALL THIS INFORMATION FOR FIXTURES ETC COORDINATES |
| | WITH THE PERFORMANCE CALCULATIONS. |
| | PLEASE SUBMIT THE TIMES ON DEVICES OR SYSTEM IF SYSTEM |
| | IS PROPOSED. PLEASE INDICATE MAXIMUM OVER RIDE TIMES. |
| | PLEASE SEE THAT LOCATIONS ARE REQUIRED TO MEET THE |
| | ABOVE SECTIONS. |
| | ** PLEASE SEE AS NO DESIGNS WERE SUBMITTED FOR FBC |
| | CHAPTER 13, A REVIEW OF THESE ITEMS CAN NOT BE DONE AT |
| | THIS TIME. |
| | |
| | |
| | 3) NOTE: THIS IS THE SAME NOTE FROM PREVIOUS REVIEW. |
| | PLEASE SEE LOAD CALCULATIONS MUST MEET NEC 220.12, |
| | 220.14, 220.42, 220.44, 220.87 ETC |
| | PLEASE SEE THAT LOADS MUST INCLUDE THE KNOWN LOADS AND |
| | NOT AN ESTIMATED AMOUNT BASED ON THE 3VA PER FT. PLEASE |
| | SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN AT 125%. |
| | THE LOAD CALCULATIONS SAYS *CONTINUOUS LOADS* HOWEVER |
| | THE FIGURES AS SHOWN ARE NOT FIGURED THAT WAY.215.3, |
| | 230.42 ETC. |
| | FBC 106.3.5.1.2 |
| | |
| | |
| | ** PLEASE BE SURE TO SEE POSSIBLE COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL PLANS AND IN FACT |
| | ALL SHEETS IN SETS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |