Plan Review Notes
Plan Review Notes For Permit 07070312
Permit Number 07070312
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-04 17:07:07 
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM THE PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE PREVIOUS NOTE #3 AS THE VALUE SHOWN
 IS TO BE BASED ON FAIR MARKET VALUE AND THE TABLES AS
 SET-FORTH IN THE FBC AND ADOPTED REFERENCES TO THE FBC.
 PLEASE ADJUST.
 PLEASE SEE THE APPLIED VALUE FOR THE SCOPE OF WORK
 BEING PERFORMED AND WHAT WILL BE REQUIRED BY THE FBC
 AND REVIEW COMMENTS WILL BE SUBSTANTIALLY HIGHER THAN
 THAT STATED ON PERMIT APPLICATION.
 PLEASE ADJUST THE VALUE FOR ALL OF THE PROPOSED WORK.
 PLEASE SEE FBC ADMIN SECTION 108.3
  
 2) NOTE:THIS IS THE SAME COMMENT FROM PREVIOUS
 REVIEW.
 PLEASE SEE THE NEW CALCULATIONS ARE NOT SIGNED, DATED
 AND *SEALED* AS REQUIRED PER 13-103.1.1.1.
 PLEASE SEE THE LIGHTING INFORMATION ON THE INPUT DATA
 REPORT DOES NOT MATCH WITH PLANS.
 PLEASE SEE THE NUMBER OF FIXTURES IN THE IDR ONLY
 INDICATES ONE LIGHT FIXTURE. HOW IS THIS POSSIBLE WHEN
 THE PLANS INDICATE SEVERAL?
 PLEASE SEE THE RESPONSE LETTER MENTIONS TO SEE SHEET
 A-1 HOWEVER NO ELECTRICAL INFORMATION FOR COMMENT WAS
 ON THIS SHEET AS NOTED.
 PLEASE SEE THE PREVIOUS NOTE BELOW WHICH STILL STANDS.
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS WERE SUBMITTED WITHOUT ANY DESIGNS FOR
 FBC CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THAT EVEN IF NOT CREATING ANY NEW A/C SPACE
 (WHICH IS BEING DONE) PERFORMANCE CALCULATIONS ARE
 STILL REQUIRED.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2 ETC FOR ENERGY
 CALCULATIONS/PERFORMANCE CALCULATIONS.
 PLEASE BE SURE THE FIXTURE LEGEND ON PLANS IS COMPLETE
 WITH ALL INFORMATION FOR FIXTURES/LUMINARIES. PLEASE BE
 SURE ALL THIS INFORMATION FOR FIXTURES ETC COORDINATES
 WITH THE PERFORMANCE CALCULATIONS.
 PLEASE SUBMIT THE TIMES ON DEVICES OR SYSTEM IF SYSTEM
 IS PROPOSED. PLEASE INDICATE MAXIMUM OVER RIDE TIMES.
 PLEASE SEE THAT LOCATIONS ARE REQUIRED TO MEET THE
 ABOVE SECTIONS.
 ** PLEASE SEE AS NO DESIGNS WERE SUBMITTED FOR FBC
 CHAPTER 13, A REVIEW OF THESE ITEMS CAN NOT BE DONE AT
 THIS TIME.
  
  
 3) NOTE: THIS IS THE SAME NOTE FROM PREVIOUS REVIEW.
 PLEASE SEE LOAD CALCULATIONS MUST MEET NEC 220.12,
 220.14, 220.42, 220.44, 220.87 ETC
 PLEASE SEE THAT LOADS MUST INCLUDE THE KNOWN LOADS AND
 NOT AN ESTIMATED AMOUNT BASED ON THE 3VA PER FT. PLEASE
 SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN AT 125%.
 THE LOAD CALCULATIONS SAYS *CONTINUOUS LOADS* HOWEVER
 THE FIGURES AS SHOWN ARE NOT FIGURED THAT WAY.215.3,
 230.42 ETC.
 FBC 106.3.5.1.2
  
  
 ** PLEASE BE SURE TO SEE POSSIBLE COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL PLANS AND IN FACT
 ALL SHEETS IN SETS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  