| 2007-07-19 13:54:58 | *** DENIED *** | | | 1) AS ROOM SIZES HAVE CHANGED THE REQUIRED CFM'S OF | | | SUPPLY AIR MAY HAVE CHANGED, PLEASE SHOW THE CFM'S AT | | | ALL SUPPLY AIR GRILLS TO ROOMS THAT HAVE BEEN ALTERED. | | | | | | 2) NOTE #1 ON MECHANICAL PLAN STATES RELOCATE | | | DIFFUSERS, WERE PLAN SHOWS #1 AS RELOCATED GRILL. AND | | | NOTE #4 STATES EXTEND FLEX, WERE PLAN SHOWS NEW FLEX. | | | PLEASE CORRECT MECHANICAL PLAN SO EXACT WORK TO BE DONE | | | IS CLEAR. | | | | | | 3) MECHANICAL PLAN SHOWS AN EXISTING RETURN DUCT NEXT | | | TO IT IS A RELOCATED FIRE DAMPER. IS THE RETURN DUCT TO | | | BE RELOCATED TO THE FIRE DAMPER OR IS THE FIRE DAMPER | | | FOR SOMETHING ELSE. PLEASE CLARIFY. | | | | | | 4) PLEASE ADD TO MECHANICAL PLAN A DETAIL SHOWING THE | | | INSTALLATION OF THE FIRE DAMPER. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|