Plan Review Notes
Plan Review Notes For Permit 07070312
Permit Number 07070312
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-07-25 17:17:30*****DENIED*****
  
  
 1.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE, TO
 BE REFERENCED.
  
 2.LIST THE OCCUPANCY TYPE AND OCCUPANT LOAD FOR THIS
 SPACE.
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 5.THE SCOPE OF WORK IN NO WAY SHALL BLOCK, INTERFERE
 OR HINDER ACCESS TO OR EGRESS FROM THE SAID BUILDING
 FLOOR/SUITE OR OTHER FLOORS/SUITES IN THE BUILDING
 (INCLUDING EXITS, EXIT AISLE CORRIDORS).
  
 6.PLEASE SPECIFY THE NEW WALL AND CEILING FINISH
 MATERIALS FOR THE EXITS, EXIT AISLE CORRIDORS, AND
 OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 7.ON SHEET E-2, THERE IS AN EXIT LIGHT (OF WHICH I'VE
 CIRCLED IN RED) NOTED.WHERE DOES THIS EXIT LEAD
 PERSON(S) ?
  
 8.WILL THE SCOPE OF WORK IMPACT THE FIRE SPRINKLERS?
 IF SO, SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR
 THE SPRINKLER REMODEL.
  
 9.WILL THE SCOPE OF WORK IMPACT THE FIRE ALARM
 DEVICES?IF SO, SEPARATE PLANS AND PERMIT WILL BE
 REQUIRED FOR THE FIRE ALARM REMODEL.
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED.
  
  