| 2007-07-25 17:17:30 | *****DENIED***** |
| | |
| | |
| | 1.THE 2003 EDITION OF NFPA 101, LIFE SAFETY CODE, TO |
| | BE REFERENCED. |
| | |
| | 2.LIST THE OCCUPANCY TYPE AND OCCUPANT LOAD FOR THIS |
| | SPACE. |
| | |
| | 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 4.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL |
| | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR |
| | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 5.THE SCOPE OF WORK IN NO WAY SHALL BLOCK, INTERFERE |
| | OR HINDER ACCESS TO OR EGRESS FROM THE SAID BUILDING |
| | FLOOR/SUITE OR OTHER FLOORS/SUITES IN THE BUILDING |
| | (INCLUDING EXITS, EXIT AISLE CORRIDORS). |
| | |
| | 6.PLEASE SPECIFY THE NEW WALL AND CEILING FINISH |
| | MATERIALS FOR THE EXITS, EXIT AISLE CORRIDORS, AND |
| | OTHER SPACES IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | 7.ON SHEET E-2, THERE IS AN EXIT LIGHT (OF WHICH I'VE |
| | CIRCLED IN RED) NOTED.WHERE DOES THIS EXIT LEAD |
| | PERSON(S) ? |
| | |
| | 8.WILL THE SCOPE OF WORK IMPACT THE FIRE SPRINKLERS? |
| | IF SO, SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR |
| | THE SPRINKLER REMODEL. |
| | |
| | 9.WILL THE SCOPE OF WORK IMPACT THE FIRE ALARM |
| | DEVICES?IF SO, SEPARATE PLANS AND PERMIT WILL BE |
| | REQUIRED FOR THE FIRE ALARM REMODEL. |
| | |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS |
| | ADDRESSED. |
| | |
| | |