| 2007-07-17 18:51:27 | |
| | ** UNSAT ** |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE SEE REFERENCES ON PLANS WHICH CONTAIN NOTES |
| | WHICH REFLECT THE SOUTH FLORIDA BUILDING CODE? THIS |
| | CODE HAS NOT BEEN IN EFFECT SINCE THE ADOPTION OF THE |
| | 2001 FBC. |
| | |
| | THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. |
| | |
| | 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION IN |
| | TITLE BLOCKS FOR THE FIRM AS LISTED. PLEASE SEE THAT |
| | ANY CONSTRUCTION FIRM WHICH ALSO OFFERS ARCHITECTURAL |
| | SERVICES SHALL OBTAIN A CERTIFICATE OF AUTHORIZATION |
| | NUMBER FROM THE DEPARTMENT OF BUSINESS AND PROFESSIONAL |
| | REGULATION. |
| | PLEASE SEE FAC 61G1-16.004 AND FS 481.219 |
| | ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES |
| | WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE |
| | REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR THE SCOPE OF |
| | WORK BEING PERFORMED AND WHAT WILL BE REQUIRED BY THE |
| | FBC AND REVIEW COMMENTS WILL BE SUBSTANTIALLY HIGHER |
| | THAN THAT STATED ON PERMIT APPLICATION. |
| | PLEASE ADJUST THE VALUE FOR ALL OF THE PROPOSED WORK. |
| | PLEASE SEE FBC ADMIN SECTION 108.3 |
| | |
| | 4) NOTE: PLEASE SEE PLANS WERE SUBMITTED WITHOUT ANY |
| | DESIGNS FOR FBC CHAPTER 13. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | PLEASE SEE THAT EVEN IF NOT CREATING ANY NEW A/C SPACE |
| | (WHICH IS BEING DONE) PERFORMANCE CALCULATIONS ARE |
| | STILL REQUIRED. |
| | PLEASE SEE 13-415.1.AB.1.1, 13-415.2 ETC FOR ENERGY |
| | CALCULATIONS/PERFORMANCE CALCULATIONS. |
| | PLEASE BE SURE THE FIXTURE LEGEND ON PLANS IS COMPLETE |
| | WITH ALL INFORMATION FOR FIXTURES/LUMINARIES. PLEASE BE |
| | SURE ALL THIS INFORMATION FOR FIXTURES ETC COORDINATES |
| | WITH THE PERFORMANCE CALCULATIONS. |
| | PLEASE SUBMIT THE TIMES ON DEVICES OR SYSTEM IF SYSTEM |
| | IS PROPOSED. PLEASE INDICATE MAXIMUM OVER RIDE TIMES. |
| | PLEASE SEE THAT LOCATIONS ARE REQUIRED TO MEET THE |
| | ABOVE SECTIONS. |
| | ** PLEASE SEE AS NO DESIGNS WERE SUBMITTED FOR FBC |
| | CHAPTER 13, A REVIEW OF THESE ITEMS CAN NOT BE DONE AT |
| | THIS TIME. |
| | |
| | 5) NOTE: PLEASE SEE THE SPACES WHICH CONTAIN AV |
| | EQUIPMENT ARE NOT LOCATED IN A RATED CORRIDOR WITH OUT |
| | ANY INFORMATION FOR SEPARATION. PLEASE SEE LOCATIONS OF |
| | ELECTRICAL EQUIPMENT AS SHOWN IS NOT PERMITTED IN RATED |
| | EGRESS AREAS. PLEASE SEE BUILDING REVIEW COMMENTS FOR |
| | THIS. PLEASE SEE CHAPTER 10 OF THE FBC. |
| | PLEASE SEE PLANS WERE REDLINED UNDER 06080951 OF |
| | EQUIPMENT WHICH IS NOT PERMITTED IN RATED STAIRS OR |
| | HALLS. |
| | |
| | 6) NOTE: PLEASE PROVIDE INFORMATION FOR ELECTRICAL WORK |
| | AND AREAS FOR THE AV PANEL AND EQUIPMENT WHICH IS BEING |
| | SHOWN ON PLANS AS EXISTING. THE PLANS DATED BACK FOR |
| | SECURITY WORK WHICH WAS PERMIT #06080951 DID NOT |
| | INCLUDE THE ELECTRICAL PANEL AND OTHER EQUIPMENT AS |
| | SHOWN ON THESE PLANS. |
| | PLEASE PROVIDE DOCUMENTATION FOR THIS WORK AS NOT |
| | RECORD COULD BE LOCATED FOR THIS FOR SUITE #200 BASED |
| | ON THIS ADDRESS OF 700 S. ROSEMARY. |
| | PLEASE SUBMIT INFORMATION FOR THIS *EXISTING* AV |
| | PANEL. |
| | |
| | 7) NOTE: PLEASESEE LOAD CALCULATIONS MUST MEET NEC |
| | 220.12, 220.14, 220.42, 220.44,220.87 ETC |
| | PLEASE SEE THAT LOADS MUST INCLUDE THE KNOWN LOADS AND |
| | NOT AN ESTIMATED AMOUNT BASED ON THE 3VA PER FT. PLEASE |
| | SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN AT 125%. |
| | THE LOAD CALCULATIONS SAYS *CONTINUOUS LOADS* HOWEVER |
| | THE FIGURES AS SHOWN ARE NOT FIGURED THAT WAY.215.3, |
| | 230.42 ETC. |
| | FBC 106.3.5.1.2 |
| | |
| | 8) NOTE: PLEASE SEE 408.4 AS THE ROOMS AND AREAS ON |
| | PLANS SHALL CONTAIN DESIGNATIONS AND THESE DESIGNATIONS |
| | NEED TO CORRELATE WITH THE PANEL SCHEDULE. THE USE OF |
| | *LIGHTING* OR *RECEPTACLES* IS NOT ACCEPTABLE. PLEASE |
| | KNOW NUMERICAL DESIGNATIONS ARE PERMITTED. PLEASE SEE |
| | THE FOLLOWING TEXT WHICH IS TAKEN FROM THE 2005 NEC. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 9) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4) |
| | AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR |
| | ADA REQUIRED AREAS.PLEASE SHOW LOCATIONS AS REQUIRED |
| | AND LEVELS AS REQUIRED. THIS BUILDING DOES CONTAIN A FA |
| | SYSTEM. |
| | ** PLEASE KNOW THAT EVEN THOUGH THE FIRE ALARM WILL BE |
| | UNDER A SEPARATE PERMIT THE BASE LIFE SAFETY SYSTEM IS |
| | REQUIRED ON BASE PLANS TO COMPLY WITH THE FBC AND FS |
| | 633. |
| | FBC 106.3.5.1.2 |
| | |
| | 10) NOTE: PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT |
| | SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| | AT THIS TIME. |
| | |
| | ** PLEASE BE SURE TO SEE POSSIBLE COMMENTS FROM OTHER |
| | TRADES WHICH MAY AFFECT ELECTRICAL PLANS AND IN FACT |
| | ALL SHEETS IN SETS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |