Plan Review Notes
Plan Review Notes For Permit 07070312
Permit Number 07070312
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-17 18:51:27 
 ** UNSAT **
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 ** PLEASE SEE REFERENCES ON PLANS WHICH CONTAIN NOTES
 WHICH REFLECT THE SOUTH FLORIDA BUILDING CODE? THIS
 CODE HAS NOT BEEN IN EFFECT SINCE THE ADOPTION OF THE
 2001 FBC.
  
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES.
  
 2) NOTE: PLEASE SEE MISSING LICENSE INFORMATION IN
 TITLE BLOCKS FOR THE FIRM AS LISTED. PLEASE SEE THAT
 ANY CONSTRUCTION FIRM WHICH ALSO OFFERS ARCHITECTURAL
 SERVICES SHALL OBTAIN A CERTIFICATE OF AUTHORIZATION
 NUMBER FROM THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION.
 PLEASE SEE FAC 61G1-16.004 AND FS 481.219
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER TRADE
 REVIEWER(S).
  
 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR THE SCOPE OF
 WORK BEING PERFORMED AND WHAT WILL BE REQUIRED BY THE
 FBC AND REVIEW COMMENTS WILL BE SUBSTANTIALLY HIGHER
 THAN THAT STATED ON PERMIT APPLICATION.
 PLEASE ADJUST THE VALUE FOR ALL OF THE PROPOSED WORK.
 PLEASE SEE FBC ADMIN SECTION 108.3
  
 4) NOTE: PLEASE SEE PLANS WERE SUBMITTED WITHOUT ANY
 DESIGNS FOR FBC CHAPTER 13.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE SEE THAT EVEN IF NOT CREATING ANY NEW A/C SPACE
 (WHICH IS BEING DONE) PERFORMANCE CALCULATIONS ARE
 STILL REQUIRED.
 PLEASE SEE 13-415.1.AB.1.1, 13-415.2 ETC FOR ENERGY
 CALCULATIONS/PERFORMANCE CALCULATIONS.
 PLEASE BE SURE THE FIXTURE LEGEND ON PLANS IS COMPLETE
 WITH ALL INFORMATION FOR FIXTURES/LUMINARIES. PLEASE BE
 SURE ALL THIS INFORMATION FOR FIXTURES ETC COORDINATES
 WITH THE PERFORMANCE CALCULATIONS.
 PLEASE SUBMIT THE TIMES ON DEVICES OR SYSTEM IF SYSTEM
 IS PROPOSED. PLEASE INDICATE MAXIMUM OVER RIDE TIMES.
 PLEASE SEE THAT LOCATIONS ARE REQUIRED TO MEET THE
 ABOVE SECTIONS.
 ** PLEASE SEE AS NO DESIGNS WERE SUBMITTED FOR FBC
 CHAPTER 13, A REVIEW OF THESE ITEMS CAN NOT BE DONE AT
 THIS TIME.
  
 5) NOTE: PLEASE SEE THE SPACES WHICH CONTAIN AV
 EQUIPMENT ARE NOT LOCATED IN A RATED CORRIDOR WITH OUT
 ANY INFORMATION FOR SEPARATION. PLEASE SEE LOCATIONS OF
 ELECTRICAL EQUIPMENT AS SHOWN IS NOT PERMITTED IN RATED
 EGRESS AREAS. PLEASE SEE BUILDING REVIEW COMMENTS FOR
 THIS. PLEASE SEE CHAPTER 10 OF THE FBC.
 PLEASE SEE PLANS WERE REDLINED UNDER 06080951 OF
 EQUIPMENT WHICH IS NOT PERMITTED IN RATED STAIRS OR
 HALLS.
  
 6) NOTE: PLEASE PROVIDE INFORMATION FOR ELECTRICAL WORK
 AND AREAS FOR THE AV PANEL AND EQUIPMENT WHICH IS BEING
 SHOWN ON PLANS AS EXISTING. THE PLANS DATED BACK FOR
 SECURITY WORK WHICH WAS PERMIT #06080951 DID NOT
 INCLUDE THE ELECTRICAL PANEL AND OTHER EQUIPMENT AS
 SHOWN ON THESE PLANS.
 PLEASE PROVIDE DOCUMENTATION FOR THIS WORK AS NOT
 RECORD COULD BE LOCATED FOR THIS FOR SUITE #200 BASED
 ON THIS ADDRESS OF 700 S. ROSEMARY.
 PLEASE SUBMIT INFORMATION FOR THIS *EXISTING* AV
 PANEL.
  
 7) NOTE: PLEASESEE LOAD CALCULATIONS MUST MEET NEC
 220.12, 220.14, 220.42, 220.44,220.87 ETC
 PLEASE SEE THAT LOADS MUST INCLUDE THE KNOWN LOADS AND
 NOT AN ESTIMATED AMOUNT BASED ON THE 3VA PER FT. PLEASE
 SEE THAT ALL CONTINUOUS LOADS ARE TO BE SHOWN AT 125%.
 THE LOAD CALCULATIONS SAYS *CONTINUOUS LOADS* HOWEVER
 THE FIGURES AS SHOWN ARE NOT FIGURED THAT WAY.215.3,
 230.42 ETC.
 FBC 106.3.5.1.2
  
 8) NOTE: PLEASE SEE 408.4 AS THE ROOMS AND AREAS ON
 PLANS SHALL CONTAIN DESIGNATIONS AND THESE DESIGNATIONS
 NEED TO CORRELATE WITH THE PANEL SCHEDULE. THE USE OF
 *LIGHTING* OR *RECEPTACLES* IS NOT ACCEPTABLE. PLEASE
 KNOW NUMERICAL DESIGNATIONS ARE PERMITTED. PLEASE SEE
 THE FOLLOWING TEXT WHICH IS TAKEN FROM THE 2005 NEC.
 *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE
 THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 9) NOTE: PLEASE SEE FBC 2004 11-4.28.1, .2 AND .3(4)
 AND STATE THE MINIMUM HORN, STROBE LEVELS ON PLANS FOR
 ADA REQUIRED AREAS.PLEASE SHOW LOCATIONS AS REQUIRED
 AND LEVELS AS REQUIRED. THIS BUILDING DOES CONTAIN A FA
 SYSTEM.
 ** PLEASE KNOW THAT EVEN THOUGH THE FIRE ALARM WILL BE
 UNDER A SEPARATE PERMIT THE BASE LIFE SAFETY SYSTEM IS
 REQUIRED ON BASE PLANS TO COMPLY WITH THE FBC AND FS
 633.
 FBC 106.3.5.1.2
  
 10) NOTE: PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT
 SUBMITTED FOR REVIEW, THERE MAY VERY WELL BE NEW
 COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE
 AT THIS TIME.
  
 ** PLEASE BE SURE TO SEE POSSIBLE COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL PLANS AND IN FACT
 ALL SHEETS IN SETS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]