| 2007-07-24 12:58:33 | BUILDING PLAN REVIEW |
| | PERMIT: 07070312 |
| | ADD: 700 S.ROSEMARY AVE |
| | CONT: VENTURA ARCH. |
| | TEL: (561)856-6655 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2006 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW 1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) 2004 FBC EXISTING |
| | 301.5A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 3)61G1-16.004 TITLE BLOCK. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | |
| | 4)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD) MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 5)715.3 FIRE DOOR AND SHUTTER ASSEMBLIES. APPROVED |
| | FIRE DOOR AND FIRE SHUTTER ASSEMBLIES SHALL BE |
| | CONSTRUCTED OF ANY MATERIAL OR ASSEMBLY OF COMPONENT |
| | MATERIALS THAT CONFORMS TO THE TEST REQUIREMENTS OF |
| | SECTION 715.3.1 , 715.3.2 OR 715.3.3 AND THE FIRE |
| | PROTECTION RATING INDICATED IN TABLE 715.3 . FIRE DOOR |
| | ASSEMBLIES AND SHUTTERS SHALL BE INSTALLED IN |
| | ACCORDANCE WITH THE PROVISIONS OF THIS SECTION AND NFPA |
| | 80. STATE THE FIRE PROTECTION RATING OF THE DOORS IN |
| | NEW 2 HOUR FIRE PARTITION INCLUDING THOSE ENCLOSING THE |
| | EXISTING AV EQUIPMENT ROOM. SEE SHEET A-2 DOOR |
| | SCHEDULE. |
| | |
| | 6)110.2* W. P. B. ADMINISTRATIVE |
| | CODE, INFORMATION THAT IS REQUIRED FOR |
| | RECORD KEEPING |
| | A) THE EDITION OFTHE CODE UNDER WHICH |
| | THE PROJECT IS DESIGNED. |
| | B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| | WITH THE PROVISIONS OF CHAPTER 3. |
| | C) THE TYPE OF CONSTRUCTION AS DEFINED |
| | IN CHAPTER 6, TABLE 601. |
| | D) THE OCCUPANT LOAD, SEE 1004. |
| | E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED |
| | F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. |
| | . ------------------------------------- |
| | ) NUMBER OF FLOORS |
| | |
| | 7)SUBMIT THE LIFE SAFETY PLAN SHOWING THE MEANS OF |
| | EGRESS. |
| | |
| | 8)1005.2 DOOR ENCROACHMENT. |
| | DOORS OPENING INTO THE PATH OF EGRESS TRAVEL SHALL NOT |
| | REDUCE THE REQUIRED WIDTH TO LESS THAN ONE-HALF DURING |
| | THE COURSE OF THE SWING. WHEN FULLY OPEN, THE DOOR |
| | SHALL NOT PROJECT MORE THAN 7 INCHES (178 MM) INTO THE |
| | REQUIRED WIDTH.SEE SHEET A-1 DOUBLE DOORS. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | 805-6726 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |