Plan Review Notes For Permit 07070307
Permit Number 07070307
Review Stop B
Sequence Number 4
Notes
Date Text
2007-08-31 11:10:29****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)SPAN OF 7.5' REQUIERS USE OF THE 8' ROWS.SEE
 OPENING 1, 91 1/2" SPAN AND SHEET 14 OF THE PRODUCT
 APPROVAL.FOR A DESIGN PRESSURE OF -56.15, YOU MUST
 USE THE -60PSF CHART, 8.5" REQUIRED.YOU'VE HIGHLGHTED
 THE -75PSF COLUMN (7") BUT HAVE WRITTEN 9" ON THE
 INSTALLATION SCHEDULE.
  
 2.)OPENING 2, SPAN OF 61", 67.32 PSF, REQUIRES USE OF
 THE 6', 75PSF COLUMN, 8"SPACING FOR CONNECTION E, SEE
 SHEET 14.
  
 IF YOU DO NOT UNDERSTAND THESE COMMENTS, PLEASE HAVE
 THE QUALIFIER CONTACT ME.IT APPEARS FROM THE
 INSTALLATION SCHEDULE THAT YOU UNDERSTAND WHAT
 INFORMATION WE ARE ASKING FOR BUT ARE USING THE WRONG
 COLUMN OR ROWS (WRONG SPANS).THE SPAN SHOULD BE ONE
 NUMBER, BLADE LENGTH, FOR ACCORDIONS.YOU HAVE TWO
 DIMENSIONS BUT ANCHOR SPACING DOES NOT COMPLY WITH THE
 SMALLEST DIMENSION WHICH IN EACH CASE IS THE SHUTTER
 HEIGHT.
  