Notes
Date Text
2007-10-30 13:56:29PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE MECHANICAL PLAN UTILITY ROOM 6" T-FIN IS TO
 SMALL AN OPENING FOR MAKE-UP AIR FOR THE GAS CLOTHES
 DRYER. SEE FBC/R G2439.4 (614.5) MAKEUP AIR.
 INSTALLATIONS EXHAUSTING MORE THAN 200 CFM (0.09 M 3
 /S) SHALL BE PROVIDED WITH MAKEUP AIR. WHERE A CLOSET
 IS DESIGNED FOR THE INSTALLATION OF A CLOTHES DRYER, AN
 OPENING HAVING AN AREA OF NOT LESS THAN 100 SQUARE
 INCHES (0.0645 M 2 ) FOR MAKEUP AIR SHALL BE PROVIDED
 IN THE CLOSET ENCLOSURE, OR MAKEUP AIR SHALL BE
 PROVIDED BY OTHER APPROVED MEANS. PLEASE CORRECT.
  
 2) CHANGES TO PLANS MAY NOT BE MADE BY HAND, AS THE
 PLANS MAY HAVE BEEN CHANGED ANY TIME AFTER THE REVIEW.
 PLEASE MAKE NEEDED CORRECTIONS TO MECHANICAL PLANS
 BEFORE RE-COPYING.
  
 3) PLEASE SHOW THE JOB ADDRESS IN THE TITLE BLOCK OF
 THE MECHANICAL PLAN, SEE WPB AMEND. 106.1.3.
  
 *** NO FEE TO BE CHARGED ON NEXT MECHANICAL REVIEW AS
 REVIEW ON 9-13-07 MISSED THE MECH. REVIEW. ***
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]