| 2007-10-05 17:24:13 | DENIED BY BUILDING |
| | |
| | 1) SUBMIT A DRAINAGE PLAN OR SITE PLAN SHOWING |
| | COMPLIANCE WITH R401.3 DRAINAGE . |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| | CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS |
| | TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO |
| | DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE |
| | GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM |
| | OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048 |
| | MM). |
| | EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| | PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| | WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| | PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| | |
| | 2) THE TRUSS BOTTOM CORD LIVE LOAD SPECIFIED ON A3 AS 0 |
| | IS INCORRECT. TABLE R301.5 REQUIRES A LIVE LOAD OF 10 |
| | PSF FOR ATTICS WITHOUT STORAGE AND 20 PSF WITH STORAGE. |
| | PLEASE CORRECT. |
| | |
| | 3)ROOF SHEATHING IS REQUIRED TO BE FASTENED IN |
| | ACCORDANCE WITH SECTION R803.2.3.1 OF 2006 REVISIONS TO |
| | 2004 FBC RESIDENTIAL CODE. WHICH REQUIRES 8D RING-SHANK |
| | NAILS TO BE USED IN ALL ROOF ZONES. PLEASE REVISE THE |
| | TYPICAL ROOF NOTES ON A3. |
| | |
| | 4) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND LISTING |
| | INFORMATION FOR THE BUILT IN BBQ AND HOOD. SEE |
| | G2447.1. |
| | |
| | 5) SUBMIT PRODUCT APPROVALS FOR THE CASEMENT WINDOWS AS |
| | REQUIRED BY FAC RULE 9B-72. |
| | BATHROOM WINDOWS TO BE SAFETY GLAZING OR IMPACT RATED |
| | TO COMPLY WITH R308. |
| | |
| | 6) THE DESIGN PRESSURES FOR THE DALTON SECTIONAL GARAGE |
| | DOORS ARE LOWER THAN THE REQUIRED COMPONENT AND |
| | CLADDING PRESSURES LISTED ON THE PLANS. |
| | |
| | 7) THE SBCCI REPORT #2203 HAS BEEN REVISED AND REISSUED |
| | AS AN ICC LEGACY REPORT ON JAN. 1, 2005. PLEASE SUBMIT |
| | THE REVISED REPORT THAT IS POSTED ON THE STATE PRODUCT |
| | APPROVAL WEBSITE. PLEASE SPECIFY WHICH ONE OF THE ROOF |
| | TILES FROM THE REPORT WILL BE INSTALLED. |
| | |
| | 8) ONE OF THE REVISED A2 SHEETS OF THE PLANS HAS A |
| | HANDWRITTEN NOTE ACROSS THE PAGE. PLEASE SUBMIT CLEAN |
| | DRAWINGS. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |