Plan Review Notes
Plan Review Notes For Permit 07070306
Permit Number 07070306
Review Stop B
Sequence Number 2
Notes
Date Text
2007-10-05 17:24:13DENIED BY BUILDING
  
 1) SUBMIT A DRAINAGE PLAN OR SITE PLAN SHOWING
 COMPLIANCE WITH R401.3 DRAINAGE .
 SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER
 CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION SO AS
 TO NOT CREATE A HAZARD. LOTS SHALL BE GRADED SO AS TO
 DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. THE
 GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A MINIMUM
 OF 6 INCHES (152 MM) WITHIN THE FIRST 10 FEET (3048
 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 PROVIDED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
  
 2) THE TRUSS BOTTOM CORD LIVE LOAD SPECIFIED ON A3 AS 0
 IS INCORRECT. TABLE R301.5 REQUIRES A LIVE LOAD OF 10
 PSF FOR ATTICS WITHOUT STORAGE AND 20 PSF WITH STORAGE.
 PLEASE CORRECT.
  
 3)ROOF SHEATHING IS REQUIRED TO BE FASTENED IN
 ACCORDANCE WITH SECTION R803.2.3.1 OF 2006 REVISIONS TO
 2004 FBC RESIDENTIAL CODE. WHICH REQUIRES 8D RING-SHANK
 NAILS TO BE USED IN ALL ROOF ZONES. PLEASE REVISE THE
 TYPICAL ROOF NOTES ON A3.
  
 4) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND LISTING
 INFORMATION FOR THE BUILT IN BBQ AND HOOD. SEE
 G2447.1.
  
 5) SUBMIT PRODUCT APPROVALS FOR THE CASEMENT WINDOWS AS
 REQUIRED BY FAC RULE 9B-72.
 BATHROOM WINDOWS TO BE SAFETY GLAZING OR IMPACT RATED
 TO COMPLY WITH R308.
  
 6) THE DESIGN PRESSURES FOR THE DALTON SECTIONAL GARAGE
 DOORS ARE LOWER THAN THE REQUIRED COMPONENT AND
 CLADDING PRESSURES LISTED ON THE PLANS.
  
 7) THE SBCCI REPORT #2203 HAS BEEN REVISED AND REISSUED
 AS AN ICC LEGACY REPORT ON JAN. 1, 2005. PLEASE SUBMIT
 THE REVISED REPORT THAT IS POSTED ON THE STATE PRODUCT
 APPROVAL WEBSITE. PLEASE SPECIFY WHICH ONE OF THE ROOF
 TILES FROM THE REPORT WILL BE INSTALLED.
  
 8) ONE OF THE REVISED A2 SHEETS OF THE PLANS HAS A
 HANDWRITTEN NOTE ACROSS THE PAGE. PLEASE SUBMIT CLEAN
 DRAWINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  
  
  
  
  
  
  
  
  
  