1 |
|
| Notes |
| Date |
Text |
| 2007-07-18 14:02:26 | *** DENIED *** | | | 1) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT | | | ALSO, PER 2004 FBC 13-600.3.ABC.2. | | | | | | 2) SEE YELLOW HIGH LIGHTS ON MECHANICAL PLANS SHOWING | | | DUCTS (FLEX) THAT NEEDS TO BE SIZED. | | | | | | 3) PLEASE SHOW ON MECHANICAL PLAN COMBUSTION AIR | | | CALCULATIONS, PROVIDE COMBUSTION AIR IF NEEDED FOR GAS | | | CLOTHES DRYER AND OR MAKE-UP AIR. | | | | | | 4)ALL INFORMATION, DRAWINGS, MECHANICAL PLANS, | | | SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE | | | PRINTED NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | | FOR THE DESIGN. PER FBC 104.2.1 . | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|