| 2007-08-30 09:53:15 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA |
| | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). |
| | |
| | *** DENIED *** |
| | 1) AS REQUESTED IN LAST REVIEW 7-20-07. PLEASE SUBMIT |
| | COMPLETE DETAILED MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS AND SPECIFICATIONS FOR DIESEL GENERATOR |
| | AND FUEL TANK (MUST SHOW FUEL TANK CAPACITY). |
| | |
| | 2) PLAN SHOWS THE GENERATOR NEXT TO A DOOR, SEE NFPA |
| | 37. A PERMIT WILL BE REQUIRED AND THE DOOR WILL NEED TO |
| | BE CLOSED OFF BEFORE THE GENERATOR PERMIT CAN BE |
| | ISSUED. |
| | |
| | 3)INFORMATION MISSING IN TITLE BLOCK FOR ARCHITECT |
| | (PRINTED NAME OF PERSON SEALING PLANS) SEE FAC |
| | 61G1-16.004 TITLE BLOCK. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS" |
| | SEE CITY WPB AMEND. 106.1.1). |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | |
| | 4) THE WORKERS COMP. EXEMPT CARD SUBMITTED FOR KARL |
| | SCHIBINGER, EXEMPTION IS FOR SALES ONLY THE PERMIT |
| | APPLICATION IS FOR THE INSTALLATION OF A GENERATOR, |
| | PLEASE CORRECT. |
| | |
| | NFPA 37 INSTALLATION & USE OF STATIONARY |
| | COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES |
| | (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT |
| | FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES |
| | HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT |
| | REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE |
| | RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF |
| | ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, |
| | AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE |
| | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE |
| | MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1 |
| | EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES |
| | OR |
| | WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION |
| | INTAKES. |
| | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS |
| | LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE |
| | TERMINATION POINT |
| | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF |
| | STRUCTURE. |
| | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL |
| | EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, |
| | GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED |
| | CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E. |
| | FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS. |
| | FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES |
| | AROUND EQUIPMENT FOR SERVICING,AND PROVIDE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE |
| | FOR THE FIELD INSPECTOR. |
| | |