2007-08-30 19:09:022004 FBC
 INSTALL RESIDENTIAL GENERATOR
 2ND REVIEW
  
 DENIED BY BUILDING
  
  
  
 1)GENERATOR SLAB & ANCHOR REQUIREMENT
 PLEASE PROVIDE SIZE OF GENERATOR(WXL),
 PLUS PROVIDE PLANS WITH THE INFORMATION
 DEPICTING HOLD DOWN BRACKETS, TYPE OF
 FASTENER, AND THE MINIMUM EDGE DISTANCE
 THE DEVICE REQUIRES WITHOUT LOAD
 REDUCTION.
 SECOND, PROVIDE INFORMATION ON THE
 SLAB, THICKNESS, WIDTH AND LENGTH, IF
 WIREMESH, FIBER MESH OR IF STEEL REBAR
 WILL BE USED.
 THE NEW SLAB AND HOLD DOWN DETAILS:
 104.2.1* ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 PLANS MUST SHOW THAT THE GENERATOR IS ADEQUATELY
 ANCHORED TO RESIST OVERTURNING, UPLIFT AND SLIDING AS
 REQUIRED BY FBC 1609.1.3.
  
  
 2) A SEPARATE PERMIT IS REQURED TO INSTALL THE GLASS
 BLOCK AND THE WORK WILL HAVE TO BE COMPLETED AND
 APPROVED BY THE CITY BUILDING DEPARTMENT BEFORE THE
 GENERATOR PERMIT CAN BE ISSUED.
  
 3) ADDRESS REVIEW COMMENTS OF OTHER TRADES.
  