| 2007-07-17 09:50:29 | *** DENIED *** |
| | 1) PLEASE SUBMIT COMPLETE DETAILED MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS AND SPECIFICATIONS FOR DIESEL |
| | GENERATOR AND FUEL TANK. |
| | |
| | 2) PLAN SHOWS THE GENERATOR NEXT TO A GARAGE DOOR, SEE |
| | NFPA 37, PLEASE CORRECT. |
| | |
| | NFPA 37 INSTALLATION & USE OF STATIONARY |
| | COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES |
| | (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT |
| | FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES |
| | HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT |
| | REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE |
| | RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF |
| | ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, |
| | AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE |
| | ENCLOSURE WILL NOT IGNITE COMBUSTIBLE |
| | MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1 |
| | EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES |
| | OR |
| | WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION |
| | INTAKES. |
| | 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS |
| | LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE |
| | TERMINATION POINT |
| | SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF |
| | STRUCTURE. |
| | PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL |
| | EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, |
| | GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED |
| | CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E. |
| | FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS. |
| | FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES |
| | AROUND EQUIPMENT FOR SERVICING,AND PROVIDE |
| | MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE |
| | FOR THE FIELD INSPECTOR. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729. |