| 2007-07-30 10:26:32 | |
| | *** UNSAT *** |
| | |
| | *** PLANS NOW SUBMITTED UNDER A NEW PERMIT APPLICATION |
| | FOR VOID PERMIT 06010504 |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE SPECIFIC CHANGES IN THE 2005 NEC |
| | WHICH REQUIRES ITEMS ON PLANS TO BE REVISED ALONG WITH |
| | OTHER CODE REQUIRED CHANGES. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 2) NOTE: PLEASE SEE THE BUILDING IS STILL BEING |
| | SUBMITTED UNDER ONE PERMIT. AS STATED ON PERVIOUS |
| | REVIEW, IF THESE ARE FEE SIMPLE *TOWN HOMES* BY |
| | DEFINITION OF THE FBC, THEN SEE BUILDING REVIEW |
| | COMMENTS AS THESE ARE EACH UNDER A SEPARATE PCN AS |
| | STATED ON LETTER FROM PBC AND WILL REQUIRE PERMIT |
| | APPLICATIONS AND PLANS FOR EACH AS THESE ARE EACH A |
| | SEPARATE LEGAL PROPERTY ETC. |
| | PLEASE ALSO SEE THE PLANS STILL CALL FOR THIS AS A |
| | *MULTI-FAMILY* BUILDING WHICH DOES NOT COORDINATE WITH |
| | PLANS, STATEMENTS, PERMIT APPLICATION ETC. |
| | PLEASE ALSO SEE THAT IF THESE ARE SEPARATE |
| | *BUILDINGS*/TOWN HOUSES,* PLEASE SEE DEFINITIONS OF |
| | BUILDING IN THE FBC AND REQUIREMENTS FOR TYPE OF WALL |
| | CONSTRUCTION AND SEPARATION. THIS IS TO BE CONFIRMED |
| | WITH THE BUILDING REVIEWER AS THE REQUIRED *FIRE WALL* |
| | DOES NOT SEEM TO BE SHOWN ON PLANS. THE FIRE WALL |
| | REQUIRES COLLAPSE OF THE STRUCTURE ON EITHER SIDE |
| | WITHOUT AFFECTING THE STRUCTURAL INTEGRITY OF THE |
| | OTHER. |
| | BASED ON PLANS SUBMITTED AND SINGLE PERMIT APPLICATION, |
| | THIS IS A *MULTI-FAMILY* BUILDING AND ONLY ONE |
| | ELECTRICAL SERVICE WILL BE GRANTED PER 230.2. PLEASE BE |
| | SURE TO GROUP ALL MAINS PER 230.72 INTO ONE SERVICE. |
| | 230.70, 230.71, 250.66, 240.4, 310.16 ETC. PLEASE |
| | REVISE RISER WITH ALL NEW REQUIREMENTS FOR CONDUCTORS, |
| | GROUNDING ETC. |
| | PLEASE KNOW THAT A COMPLETE REVIEW OF THIS RISER CAN |
| | NOT BE DONE AT THIS TIME AS PLANS SHOW THIS A SINGLE |
| | SERVICE FOR EACH. |
| | |
| | 3) NOTE: PLEASE SEE PLANS SHOW *SD* FOR SMOKE |
| | DETECTORS, YET THESE ARE SHOWN AS 120V W/ BATTERY BACK |
| | UP. IF THESE ARE INDEED SMOKE DETECTORS, PLEASE SEE |
| | THAT THESE WOULD NOT BE AS SHOWN. PLEASE INCLUDE |
| | SOUNDING DEVICES ON PLANS. PLEASE SEE NFPA-72 |
| | DEFINITIONS AS THESE MOST LIKELY ARE *SA* SMOKE ALARMS. |
| | BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| | DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| | NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| | HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| | SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| | SHOWN) AND WOULD DETECT AND SOUND AN ALARM. |
| | PLEASE SEE THAT THE PLANS ALSO INDICATE UP TO FOUR |
| | CIRCUITS FOR THESE DEVICES. AS THEY ARE REQUIRED TO BE |
| | WIRED *IN-LINE* THIS WOULD NOT BE POSSIBLE WITH |
| | MULTIPLE CIRCUITS AS SHOWN. |
| | PLEASE ADJUST CIRCUITING. |
| | PLEASE SEE SOME ARE MISSING CIRCUITS. |
| | PLEASE COMPLETE AND COORDINATE. |
| | ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| | RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| | IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE*. |
| | PLEASE SEE NFPA-72 11.5.1.1, 11.8.3 |
| | |
| | |
| | 4) NOTE: PLEASE SUBMIT A REVISED PANEL SCHEDULE TO |
| | SPECIFICALLY INDICATE ALL CIRCUITS ON PANEL SCHEDULE |
| | WHICH CORRELATES WITH PLANS/ROOMS/AREA LAYOUTS. PLEASE |
| | SEE 408.4 AND THE FOLLOWING TEXT BELOW WHICH IS FROM |
| | THE NEC. |
| | |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 5) NOTE: PLEASE SEE 210.4B AS THE DISHWASHER AND |
| | DISPOSAL IS SHOWN TO THE SAME DEVICE YET ARE SHOWN ON |
| | SINGLE POLE BREAKERS. |
| | PLEASE REVISE AS THESE ARE REQUIRED TO BE FROM ONE |
| | 2-POLE BREAKER. |
| | |
| | 6) NOTE: PLEASE SEE 422.13 AS THE LOAD FOR THE WATER |
| | HEATER NEEDS TO BE SHOWN AT 125%. THIS IS NEW UNDER THE |
| | 2005 NEC. PREVIOUS CODE REQUIRED 125% FOR BRANCH |
| | CIRCUIT, CODE NOW REQUIRES LOAD AT 125% ALSO AS A |
| | CONTINUOUS LOAD. |
| | |
| | 7) NOTE: PLEASE SEE THE VALUE AS APPLIED SEEMS LOW AND |
| | WILL BE REVIEWED PER THE TABLES ADOPTED INTO THE FBC |
| | 108.3. |
| | |
| | ** PLEASE KNOW AS THERE ARE ITEMS WHICH HAVE NOT YET |
| | BEEN SUBMITTED FOR REVIEW, NEW COMMENTS MAY BE FOUND ON |
| | THE NEXT REVIEW. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-07-27 16:49:54 | IN ELEC FOR REVIEW. |