| Plan Review Notes For Permit 07070268 |
| Permit Number |
07070268 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-31 18:57:27 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | | | | 1. SHT 1 OF 1 INDICATES A 1" WATER SERVICE CONNECTING | | | TO AN EXISTING HOSE BIBB. VERIFICATION IS REQUIRED FOR | | | THE SIZE OF THE WATER SUPPLY LINE TO THE HOSE BIBB. | | | SECTION 604.3. | | | | | | 2. SHT 1 OF 1 EACH COMMERCIAL BUILDING SHALL HAVE AN | | | RPZV BACKFLOW INSTALLED ON THE WATER SERVICE. SECTION | | | 608.13.2. | | | | | | 3. SHT 1 OF 1 EVERY BUILDING SHALL HAVE A SEPARATE | | | CONNECTION WITH THE SEWER. SECTION 701.3. | | | | | | 4. SHT A-1 PER TABLE 403.1 A DRINKING FOUNTAIN AND A | | | SERVICE SINK ARE REQUIRED. | | | | | | 5. SHT A-1 HOT WATER IS REQUIRED FOR THE SERVICE SINK | | | PER SECTION 607.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION | | | MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID | | | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY | | | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|