| Plan Review Notes For Permit 07070268 |
| Permit Number |
07070268 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-09-14 14:16:05 | *****DENIED**** | | | | | | | | | 01.THE COMPLETE ADDRESS SHALL BE IN THE TITLE BLOCK | | | OF EACH PLAN SHEET AND OTHER SUBMITTALS. | | | | | | 02.SPECIFY THE CONTENTS OF THE NEW OCCUPANCY AS BEING | | | CLASSIFIED AS LOW, ORDINARY, OR HIGH HAZARD. | | | | | | 03.PROVIDE AN APPROVED AISLE OR SEATING/CLASSROOM | | | DIAGRAM FOR THE OCCUPANCY. | | | | | | 04.INDICATE THE PRESCIPTIVE STRENGHT FOR | | | HANDRAILS/GUARDRAILS. | | | | | | 05.AISLES SHALL NOT BE LESS THAN 30" WIDE.PLEASE BE | | | ADVISED THAT THE SPACE BETWEEN PARALLEL ROWS OF SEATS | | | SHALL NOT BE SUBJECT TO MINIMUM AISLE WIDTH, PROVIDED | | | THAT THE NUMBE OF SEATS THAT INTERVENE BETWEEN ANY SEAT | | | AND AISLE DOES NOT EXCEED SIX. | | | | | | 06.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE | | | WALLS AND CEILINGS IN TERMS OF CLASS A, CLASS B, OR | | | CLASS C.SPECIFY INTERIOR FLOOR FINISH IN TERMS OF | | | CLASS I OR CLASS II. | | | | | | 07.ILLUSTRATE THE LOCATION OF THE EXIT LIGHTS AND | | | EMERGENCY LIGHTS. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLANEACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE ON THE PLAN EACH ITEM WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | | | | | | | | | | | | | | | | | | | |
|