Plan Review Notes
Plan Review Notes For Permit 07070268
Permit Number 07070268
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-16 21:50:30BUILDING PLAN REVIEW
 PERMIT: 07070268
 ADD: 5800 CORPORATE WAY
 CONT: LTL BUILDERS, INC.
 TEL: (561)628-9753
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) THE PLANS SUBMITTED FROM THE PALM BEACH COUNTY
 SCHOOL BOARD FOR A PORTABLE DO NOT APPEAR TO HAVE
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS APPROVAL SINCE
 THERE IS NO DCA APPROVAL NUMBERS PRESENT. A LETTER FROM
 THOMAS HOGARTH P.E. ALSO ADDS DOUBT THAT THIS UNIT WAS
 DESIGNED UNDER THE DCA'S MANUFACTURED BUILDING ACT. IF
 SO PLEASE SEE PAGES PULLED OFF THE DCA WEBSITE WITH
 INFORMATION AS HOW TO GO ABOUT RETRIEVING OLD PLANS
 THAT HAD BEEN DESIGNED UNDER THE STANDARD BUILDING
 CODE. NOTE QUESTION# 4 AS HOW DO I KNOW IF A
 MANUFACTURED (MODULAR) BUILDING IS DCA APPROVED.
  
 4) SEE QUESTION # 6 HOW DOES A SCHOOL OBTAIN A DCA
 INSIGNIA FOR AN EXISTING PORTABLE CLASSROOM. THIS IS
 COMMENTS THAT DEALS WITH PORTABLES STILL OWNED BY THE
 SCHOOL BOARD.
  
 5) THE ISSUES ARE THIS BUILDING WILL NOW BE A PERMANENT
 BUILDING AND WOULD NOT BE CLASSIFIED AS A TEMPORARY
 STRUCTURE TO BE USED LESS THAN 180 DAYS. THIS WOULD
 MEAN A PERMANENT FOUNDATION MEETING THE REQUIREMENTS OF
 THE BOTTOM OF THE FOUNDATION TO BE 12" BELOW GRADE.
 1805.2 DEPTH OF FOOTINGS. THE MINIMUM DEPTH OF FOOTINGS
 BELOW THE UNDISTURBED GROUND SURFACE SHALL BE 12 INCHES
 (305 MM). WHERE APPLICABLE, THE DEPTH OF FOOTINGS SHALL
 ALSO CONFORM TO SECTIONS 1805.2.1 THROUGH 1805.2.3 .
 EXISTING BUILDING CODE 1102.2 THE FOUNDATION SYSTEM OF
 RELOCATED BUILDINGS SHALL COMPLY WITH THE FLORIDA
 BUILDING CODE, BUILDING.
  
 6) IF THE BUILDING WAS NOT MANUFACTURED UNDER THE STATE
 DCA PROGRAM THEN THE BUILDING BEING MOVED WILL NEED TO
 MEET THE REQUIREMENTS OFTHE 2004 EXISTING BUILDING
 CODE CHAPTER 11.
  
 6A) EXISTING BUILDING CODE 1102.1 LOCATION ON THE LOT.
 THE BUILDING SHALL BE LOCATED ON THE LOT IN ACCORDANCE
 WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING. PLEASE PROVIDE A SITE PLAN WITH THE LOCATION
 OF THIS NEW BUILDING ANDTHE EXISTING BUILDING BEING
 USED FOR A SCHOOL. PLEASE PROVIDE THE DISTANCE BETWEEN
 BUILDINGS.
  
 6B)PLEASE LOOK AT MULTIPLE BUILDINGS ON SAME LOT.
 503.1.3 BUILDINGS ON SAME LOT.
 TWO OR MORE BUILDINGS ON THE SAME LOT SHALL BE
 REGULATED AS SEPARATE BUILDINGS OR SHALL BE CONSIDERED
 AS PORTIONS OF ONE BUILDING IF THE HEIGHT OF EACH
 BUILDING AND THE AGGREGATE AREA OF BUILDINGS ARE WITHIN
 THE LIMITATIONS OF TABLE 503 AS MODIFIED BY SECTIONS
 504 AND 506 . THE PROVISIONS OF THIS CODE APPLICABLE TO
 THE AGGREGATE BUILDING SHALL BE APPLICABLE TO EACH
 BUILDING.
 PLEASE INDICATE IF THE TWO BUILDINGS ON THE SAME LOT
 WILL BE CLASSIFIED AS ONE LARGER BUILDING WITH NO FIRE
 SEPARATION BETWEEN THEM OR TWO
 SEPARATE BUILDINGS WITH FIRE SEPARATION BETWEEN THE 2
 BUILDINGS.
  
 6C)) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FORRECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 6C)(A) THE EDITION OF THE CODE UNDER WHICH THE PROJECT
 IS DESIGNED.
 6C)(B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 6C)(C) THE TYPE OF CONSTRUCTION AS DEFINED IN
 CHAPTER 6, TABLE 601.
 6C)(D) THE OCCUPANT LOAD, SEE 1004.
 6C)(E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED
 6C)(F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED. 6C)(G)
 ANY SPECIAL STIPULATIONS & CONDITIONS
 OF THE BUILDING PERMIT
 6C)(.H) SQ. FT. FOOTPRINT
 6C)(I) FLOOD ZONE DESIGNATIONA-8 MINIMUM ELEVATION
 FINISH FLOOR AND A/C EQUIPMENT 14'-6". 2004 FL. BLD
 CODE 1603.1.4 THE
 6C)(J) THE FOLLOWING INFORMATION RELATED TO WIND SHALL
 BE SHOWN ON THE CONSTRUCTION DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN WIND
 PRESSURES IN TERMS OF PSF.
 6C)(K) OPENING PROTECTIVE'S:1609.1.4 PROTECTION
 OF OPENINGS. IN WIND-BORNE DEBRIS REGIONS, EXTERIOR
 GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN
 BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE
 BALANCE OF GLAZED OPENINGS IN THE REST OF
 THE BUILDING SHALL BE ASSUMED TO BE ZERO UNLESS
 SUCH GLAZING THAT RECEIVES POSITIVE PRESSURE IS IMPACT
 RESISTANT OR PROTECTED WITH AN
 IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS OF
 SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE TAS
 201, 202
 AND 203 REFERENCED THEREIN AS FOLLOWS:
 1.GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M)
 OF GRADE SHALL MEET THE REQUIREMENTS OF THE LARGE
 MISSILE TEST. 2.GLAZED OPENINGS LOCATED MORE THAN
 30 FEET (9.1 M) ABOVE GRADE SHALL MEET
 THE PROVISIONS OF THE SMALL MISSILE
 TEST.
 6D)ON THE SITE PLAN PLEASE INDICATE THE ACCESSIBLE
 ROUTE:11-4.1.6 ACCESSIBLE BUILDINGS: ALTERATIONS. THIS
 EDITION OF THE CODE DOES NOT APPLY TO BUILDINGS,
 STRUCTURES OR FACILITIES WHICH WERE IN EXISTENCE ON
 OCTOBER 1,1997, UNLESS:
 (I) THE BUILDING, STRUCTURE OR FACILITY IS BEING
 CONVERTED FROM RESIDENTIAL TO NONRESIDENTIAL OR MIXED
 USE, AS DEFINED BY LOCAL LAW.
 (II) THE PROPOSED ALTERATION OR RENOVATION OF THE
 BUILDING, STRUCTURE OR FACILITY WILL AFFECT USABILITY
 OR ACCESSIBILITY TO A DEGREE WHICH INVOKES THE
 REQUIREMENTS OF SECTION 303(A) OF THE ADA OF 1990, OR
 (III) THE ORIGINAL CONSTRUCTION OR ANY FORMER
 ALTERATION OR RENOVATION OF THE BUILDING, STRUCTURE OR
 FACILITY WAS CARRIED OUT IN VIOLATION OF APPLICABLE
 PERMITTING LAW:
 (1) GENERAL. ALTERATIONS TO EXISTING BUILDINGS AND
 FACILITIES SHALL COMPLY WITH THE FOLLOWING:
 (A)NO ALTERATION SHALL BE UNDERTAKEN WHICH
 DECREASES OR HAS THE EFFECT OF DECREASING ACCESSIBILITY
 OR USABILITY OF A BUILDING OR FACILITY BELOW THE
 REQUIREMENTS FOR NEW CONSTRUCTION AT THE TIME OF
 ALTERATION.
 (B)IF EXISTING ELEMENTS, SPACES, OR COMMON AREAS
 ARE ALTERED, THEN EACH SUCH ALTERED ELEMENT, SPACE,
 FEATURE, OR AREA SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF SECTION 11-4.1.1 TO SECTION 11-4.1.3 ,
 MINIMUM REQUIREMENTS FOR NEW CONSTRUCTION. IF THE
 APPLICABLE PROVISION FOR NEW CONSTRUCTION REQUIRES THAT
 AN ELEMENT, SPACE, OR COMMON AREA BE ON AN ACCESSIBLE
 ROUTE , THE ALTERED ELEMENT, SPACE, OR COMMON AREA IS
 NOT REQUIRED TO BE ON AN ACCESSIBLE ROUTE EXCEPT AS
 PROVIDED IN SECTION 11-4.1.6 (2), ALTERATIONS TO AN
 AREA CONTAINING A PRIMARY FUNCTION
  
 7) PROVIDE FLOOD ZONE ELEVATION CERTIFICATE FOR NEW
 CONSTRUCTION WITH BASE FLOOD ELEVATION, CITY CODE
 REQUIRES
 AN ADDITIONAL 6". OR 14'-6".
  
 8) 1102.2 THE CONNECTION OF THE RELOCATED BUILDING TO
 THE FOUNDATION SHALL COMPLY WITH THE FLORIDA BUILDING
 CODE, BUILDING.
  
 9) 1102.3 WIND LOADS, BUILDINGS SHALL COMPLY WITH THE
 FLORIDA BUILDING CODE, BUILDING
 EXCEPTIONS;
 1) STRUCTURAL ELEMENTS WHOSE STRESS IS NOT INCREASED BY
 MORE THAN 5 PER CENT.
 2) MANUFACTURED BUILDINGS AS APPROVED BY THE
 MANUFACTURED BUILDING PROGRAM, FLORIDA DEPARTMENT OF
 COMMUNITY AFFAIRS.
  
 10)PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND BEING
 FILED FOR PUBLIC RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED TO THE
 DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 11)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 BUILDING PLAN REVIEW II
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  