| Plan Review Notes For Permit 07070253 |
| Permit Number |
07070253 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-08-24 18:14:36 | *****DENIED***** | | | | | | | | | 1.THE STORAGE, USE, AND HANDLING OF FLAMMABLE AND | | | COMBUSTIBLE LIQUIDS SHALL COMPLY WITH NFPA 30. | | | | | | 2.PROPER UL LISTINGS ARE REQUIRED FOR THE TANK. | | | | | | 3.DISPLAY PROPER SETBACKS TO THE PROPERTY LINE AND | | | THE BUILDING(S). | | | | | | 4.ABOVEGROUND STORAGE TANKS SHALL BE GROUNDED AND/OR | | | BONDED. | | | | | | 5.NFPA 704 LABELS WILL BE REQUIRED TO IDENTIFY THE | | | FIRE HAZARDS OF THE TANK AND THE TANK'S CONTENT.NO | | | SMOKING AND PRODUCT IDENTITY LABELS WILL BE NEEDED. | | | | | | 6. PLEASE DETAIL HOW THE TANK WILL BE PROTECTED FROM | | | TAMPERING OR TREPASSING. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|