Plan Review Notes
Plan Review Notes For Permit 07070253
Permit Number 07070253
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-17 16:04:44*** DENIED *****
  
 ** PLEASE SEE THIS IS THE FIRST REVIEW FOR ELECTRICAL
 AS PREVIOUS PLANS DID NOT INDICATE AN ELECTRICAL.
 PLEASE SEE THE BELOW COMMENTS.
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE REQUIRED ON
 PLANS FOR ELECTRICAL .
 2005 NFPA-70.
  
 2) NOTE: PLEASE SEE THE TITLE BLOCKS ON ALL SHEETS ARE
 MISSING THE REQUIRED CERTIFICATE OF AUTHORIZATION
 NUMBER AS REQUIRED PER FLORIDA ADMINISTRATIVE CODE
 61G15-23.002, FS 471.023.
 IF FIRM DOES CONTAIN A CA NUMBER PLEASE SEE THAT THE
 FAC REQUIRES THIS TO BE ON TITLE BLOCKS. (PER STATE
 WEBSITE WITH THE DEPARTMENT OF BUSINESS AND
 PROFESSIONAL REGULATION, THIS NUMBER APPEARS TO BE
 6574
  
 3) NOTE: PLEASE SHOW A DETAIL FOR ANY ELECTRICAL
 LOCATED WITH THE CLASS AND DIVISION LOCATION PER NEC
 500.1, 500.2, 500.5.
 PLEASE SEE POSSIBLE CLASS 1, DIVISION 1 OR 2
 REQUIREMENTS. THERE ARE SOME UNANSWERED QUESTIONS,
 WHICH MAY AFFECT DIVISION. THESE WILL NOT AFFECT THE
 CLASS.
 PLEASE PROVIDE A LAYOUT OF ANY ELECTRICAL WITHIN THE
 CLASS LOCATION AND PLEASE ADJUST ELECTRICAL WHICH MAY
 BE IN THOSE AREAS.
 THE PLANS SHOW THE LOCATION OF THE TANK APPROX 5FT FROM
 BUILDINGWHICH IS OF CONCERN TO THIS REVIEWER FOR
 ELECTRICAL IGNITION SOURCES.
 PLEASE EXPLAIN HOW THE FUEL IS BEING PUMPED TO THE
 GENERATOR. PLEASE CLEARLY INDICATE ON PLANS IF THIS
 FUEL TANK FILLS THE EXISTING SUB-BASE TANK OR FEEDS THE
 GENERATOR DIRECTLY.
 DOES THIS EXISTING SUB-BASE FUEL TANK HAVE A PUMP WHICH
 WILL BE USED TO PUMP FUEL>
 IT THERE A SEPARATE PUMP?
 IF SO, PLEASE SHOW ELECTRICAL DETAILS FOR NEW PUMP.
 CIRCUIT, DISCONNECT, AND ANY EMERGENCY SHUT OFF
 DEVICE.
 IS THERE ANY ELECTRICAL OVER FILL DEVICE ON TANK?
 PLEASE PROVIDE MORE INFORMATION AND DETAILS FOR
 ELECTRICAL.
  
 3) NOTE: PLEASE SEE ASNOTED ON THE PREVIOUS REVIEW
 GROUNDING OF THE TANK FOR STATIC ELECTRICITY IS
 REQUIRED HOWEVER AS THIS FUEL TANK IS BEING CONNECTED
 IN SOME WAY TO SOME SORT OF PUMP, THE EQUAL-POTENTIAL
 OF THESE METALLIC PARTS NEED TO BE BONDED. THE
 EQUIPMENT GROUNDING CONDUCTOR TO THE GROUND ROD IS OK,
 HOWEVER THIS GROUNDING WILL BE REQUIRED TO BE BONDED TO
 ANY EQUIPMENT GROUNDING FOR PUMP/GENERATOR/TANK
 UNIT.501.30A, B, 250.102, 250.104B ETC.
  
 4) NOTE: PLEASE VERIFY 501.35 FOR REQUIRED SURGE
 PROTECTION. (EXISTING OR NEW?).
  
 5) NOTE: PLEASE REMOVE ANY OLD/VOIDED SHEETS FROM
 SETS.
 SETS ONLY NEED TO CONTAIN THE RELEVANT SHEETS FOR
 PROJECT. PLEASE BE SURETO RESUBMITTED ALL SHEETS AND
 SETS WHICH CONTAIN STAMPS FROM OTHER TRADES. NOT ALL
 SHEETS CONTAIN THE FINAL STAMPS.
  
 6) NOTE: PLEASE BE AWARE THAT THE NOTICE OF
 COMMENCEMENT WILL NEED TO BE RE-RECORDED AS IT HAS
 EXPIRED PER FS 713.13(2).
 ANY RECORDED NOC IN WHICH WORK HAS NOT COMMENCED WITHIN
 90DAYS OF RECORDING, ACTUALLY VOIDS THE NOC.
 THIS ONLY NEEDS TO BE RE-RECORDED AND SUBMITTED BEFORE
 PICKING UP PERMIT.
  
  
 ** PLEASE KNOW AS THERE ARE ITEMS WHICH CAN NOT BE
 REVIEWED AT THIS TIME, THERE MAY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 ** PLEASE KNOW DUE TO THE ELECTRICAL REVIEW NOT BEING
 COMPLETED UNDER THE FIRST REVIEW, THE RE-SUB FEE WILL
 NOT BE ASSESSED HOWEVER FIRE REVIEW FEES WHICH WERE NOT
 ASSESSED ON ORIGINAL SUBMISSION MAY BE OWED. THIS IS
 YET TO BE CONFIRMED WITH ROBERT BROWN ABO.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717